Loading...
HomeMy WebLinkAboutINSPECTION SUMMARY - 14-00065 - 535 S Yellowstone Rd - Woody Smith Ford - Furnace ChangeoutPermit Inspection Summary Permit Status of (Open) as of Report Date: 07/01/2019 3:16 pm Permit Details Permit Number: 14-00065 535 S Yellowstone Rd - Woody Smith Ford - Furnace Changeout 535 S Yellowstone Rd Mechanical Commercial Only Permit Issued Date: 02/14/2014 Permit Inspection Statistics 2Total Inspections Completed: 1Total Inspections Passed: Inspection Pass Rate: 50.00% Permit Inspection History *Refer to Individual Inspection Report for more Details Mechanical Inspection Type 02/18/2014FailQuinton OwensHVAC Final Inspection The furnace condensate connects into the AC condensate drain (Furnace in downflow application). How is the exhaust condensate prevented from draining to the AC? Does the manufacturer approve this application or should both AC & Exhaust condensates be run separate to approved drain? Inspector Comments: 03/06/2014PassQuinton OwensHVAC Final Inspection Called a manufacturer representative (208-322-4066) who said the installation sounds ok. Inspector Comments: