HomeMy WebLinkAboutINSPECTION SUMMARY - 14-00091 - 673 Tanglewood Dr - SFRPermit
Inspection
Summary
Permit Status of (Open) as of Report Date: 07/01/2019 12:24 pm
Permit Details Permit Number: 14-00091
673 Tanglewood Dr - SFR
673 Tanglewood Dr
Building - Single Family Residence
Permit Issued Date: 04/17/2014
Permit Inspection Statistics
29Total Inspections Completed:
21Total Inspections Passed:
Inspection Pass Rate: 72.41%
Permit Inspection History *Refer to Individual Inspection Report for more Details
Building Inspection Type
04/18/2014PassTed DyeFooting Inspection
04/21/2014PassTed DyeFoundation Inspection
rebar at 18" centersInspector Comments:
06/18/2014PassTed DyeSheeting
07/09/2014FailTed DyeFraming/Structure Inspection
-Missing some angled nailing on the joist Hangers over the girder trusses.
-provide truss specs
-tighten anchor bolts.
-Anchor bolts are needed on bearing walls in basement.
Inspector Comments:
07/09/2014FailTed DyeFraming/Structure Inspection
-finish nailing the plywood on the bottom of the bay window.Inspector Comments:
07/14/2014PassTed DyeFraming/Structure Inspection
Anchor bolts are needed on bearing walls in basement. Spacing. ...6'on center
maximum.
Inspector Comments:
07/14/2014FailTed DyeFraming/Structure Inspection
Anchor bolts are needed on bearing walls in basement. Spacing. ...6'on center
maximum.
Inspector Comments:
07/16/2014PassTed DyeFraming/Structure Inspection
07/16/2014PassTed DyeInsulation Inspection
07/16/2014PassTed DyeInsulation Inspection
07/28/2014FailTed DyeResidential Sheetrock/Drywall Inspection
remove and replace the half inch sheetrock, in the garage, that is marked
mark,that needs to be five x eighths fire code type X sheetrock.
Inspector Comments:
07/29/2014PassTed DyeResidential Sheetrock/Drywall Inspection
09/24/2014PassTed DyeSidewalk Inspection
Subtract has 6 " plus granular fillInspector Comments:
Page 1 of 3
(Continued)
Permit Details Permit Number: 14-00091
673 Tanglewood Dr - SFR
673 Tanglewood Dr
Building - Single Family Residence
Permit Status of (Open) as of Report Date: 07/01/2019 12:24 pm
Permit
Inspection
Summary
09/24/2014FailTed DyeResidential Building Final
Smoke/C.O. detector needed outside of the master bedroom.
A smoke detector is needed at the bottom(close to) of the stairs.
Finish concrete.
Put washers on the anchor bolts on the bearing walls
Inspector Comments:
09/26/2014PassQuinton OwensResidential Building Final
Items to be re-inspected are completed.Inspector Comments:
09/29/2014FailTed DyeResidential Building Final
With the rain that we have been receiving, the soil has settled around the house
making it so there is no longer a 6" in 10' slope away from the home.
With the wet conditions it will not be possible to fix it soon so in order to close
the home mortgage we will issue a temp. C.O. .
Fix as soon as possible so no damage will happen to the home.
We will allow a max. of one month to correct this action.
Inspector Comments:
10/02/2014FailTed DyeResidential Building Final
10/23/2014PassTed DyeResidential Building Final
Electrical Inspection Type
07/09/2014PassBret StoddardSFR-A,R,B, MFR,MFR-A,R Electrical Rough-in
07/09/2014PassBret StoddardResidential Electrical Service Inspection
09/24/2014PassBret StoddardSFR, SFR-B, SFR-A, SFR-R, MFR, MFR-A, MFR-R Electrical Final Inspection
Mechanical Inspection Type
07/09/2014FailDon AllenHVAC Rough-in
Need to install the duct for the exhaust fan in the kitchen
no gas line was ran
Inspector Comments:
07/15/2014PassDon AllenHVAC Rough-in
Good to cover the hvac rough in
Gas presser held at 60 lb
Inspector Comments:
09/24/2014PassDon AllenHVAC Final Inspection
All lgood for the c/oInspector Comments:
Page 2 of 3
(Continued)
Permit Details Permit Number: 14-00091
673 Tanglewood Dr - SFR
673 Tanglewood Dr
Building - Single Family Residence
Permit Status of (Open) as of Report Date: 07/01/2019 12:24 pm
Permit
Inspection
Summary
Plumbing Inspection Type
05/02/2014PassDon AllenPlumbing Underground Inspection
05/15/2014PassDon AllenPlumbing Sewer
All good to cover the sewerInspector Comments:
05/19/2014PassDon AllenPlumbing Water
Chuck Velmen at the water department ok the water lineInspector Comments:
07/01/2014PassDon AllenPlumbing Rough-in
Good to cover the plumbing rough inInspector Comments:
09/24/2014PassDon AllenPlumbing Final Inspection
All good for the c/oInspector Comments:
Page 3 of 3