Permit Status of (Open) as of Report Date: 07/01/2019 11:55 am
Permit Details Permit Number: 14-00147
Commercial Tire
289 E 7th N
Building - Commercial
Permit Issued Date: 07/28/2014
Permit Inspection Statistics
25Total Inspections Completed:
18Total Inspections Passed:
Inspection Pass Rate: 72.00%
Permit Inspection History *Refer to Individual Inspection Report for more Details
10/13/2015PassNatalie PowellPlanning and Zoning Final Inspection
10/19/2015PassJoel GrayPublic Works Final Inspection
Building Inspection Type
08/04/2014PassQuinton OwensCommercial Footing Inspection
Spot footings for Building excluding outer canopy footings.Inspector Comments:
08/07/2014FailQuinton OwensCommercial Footing Inspection
*** East side: one section of footing rebar needs clearance to forms.***Inspector Comments:
08/08/2014PassQuinton OwensCommercial Footing Inspection
Re-inspection of continuous footings & spot footings for canopy. Special inspector
on site for pour.
Inspector Comments:
08/12/2014PassTed DyeFoundation Inspection
01/20/2015FailQuinton OwensCommercial Framing/Structure Inspection
Column anchor plates and bolts incomplete at Grids D/1 and E/5. Visual
inspection of snug tight bolt connections on structural steel approved.
Inspector Comments:
02/06/2015FailQuinton OwensCommercial Building Final
Seal gaps between non-absorbant wall surface and service sink in restroom.
Restroom dispensers not installed yet. Landscaping not done (check with P&Z).
TEMPORARY OCCUPANCY APPROVED.
Fire Extinguishers Class 4A-80B-C within 50' travel distance approved.
Inspector Comments:
02/06/2015PassQuinton OwensCommercial Framing/Structure Inspection
Reinspection approved. Structural steel "snug tight" connections also approved at
final inspection.
Inspector Comments:
05/21/2015PassQuinton OwensCommercial Building Final
Previous items completed for final.Inspector Comments:
10/19/2015PassJoel GraySidewalk Inspection
Page 1 of 2
(Continued)
Permit Details Permit Number: 14-00147
Commercial Tire
289 E 7th N
Building - Commercial
Permit Status of (Open) as of Report Date: 07/01/2019 11:55 am
Permit
Inspection
Summary
Electrical Inspection Type
01/15/2015PassBret StoddardCOM & MFR Electrical Service Inspection
01/15/2015PassBret StoddardCommercial Electrical Rough-in
02/05/2015FailBret StoddardCOM, COM-A, COM-R, and COM-T Electrical Final Inspection
Need to label main panel, bond to water line, divider in main panel junction box,
need box bonding screws in air compressor and mitsubishi condensing unit
disconnects, mitsubishi condensing unit disconnect needs a 15A fuse max
installed to protect the unit, WR rated receptacles required for all exterior
receptacles (3), call for a re-inspect when ready.
Inspector Comments:
02/06/2015PassBret StoddardCOM, COM-A, COM-R, and COM-T Electrical Final Inspection
Fire Inspection Type
10/13/2015N/ANatalie PowellFire Sprinkler Final Inspection
N/A. Building less than 5,000 sf (903.2.9.1, #4)Inspector Comments:
10/15/2015FailDale PickeringFire Department Final Inspection
Mechanical Inspection Type
02/04/2015PassDon AllenHVAC Final Inspection
Allgood for the c/oInspector Comments:
Plumbing Inspection Type
08/22/2014PassDon AllenPlumbing Underground Inspection
All good to cover the under groundInspector Comments:
10/13/2014PassDon AllenPlumbing Sewer
All good to cover the sewerInspector Comments:
01/20/2015PassDon AllenPlumbing Water
01/20/2015PassDon AllenPlumbing Sewer
01/20/2015PassDon AllenPlumbing Rough-in
plumbing rough in look goodInspector Comments:
02/05/2015FailDon AllenPlumbing Final Inspection
The plumbing in side of the building is all good for the c/o.
Need the water meter raised up to finished grade.call for inspection after done.
Inspector Comments:
02/09/2015PassDon AllenPlumbing Final Inspection
Good for the c/oInspector Comments: