HomeMy WebLinkAboutINSPECTION SUMMARY - 14-00152 - SodaVine - Tenant ImprovementPermit
Inspection
Summary
Permit Status of (Open) as of Report Date: 07/01/2019 8:31 am
Permit Details Permit Number: 14-00152
SodaVine - Tenant Improvement
50 S 2nd W
Commercial Remodel
Permit Issued Date: 04/25/2014
Permit Inspection Statistics
11Total Inspections Completed:
7Total Inspections Passed:
Inspection Pass Rate: 63.64%
Permit Inspection History *Refer to Individual Inspection Report for more Details
Building Inspection Type
05/27/2014FailQuinton OwensCommercial Building Final
Public restroom: Walls within 2 feet of water closets shall have a smooth, hard,
nonabsorbant surface to a minimum height of 4 ft above floor. Install grab bars
in ADA bathroom as required. Finish parking spaces as required, including proper
HC parking stall and HC access to building. Restroom signage needed. Finish
work inside, including furniture setup and kitchen equipment, before reinspection.
Inspector Comments:
10/09/2015FailQuinton OwensCommercial Building Final
Finish parking spaces as required (identification sign missing- bottom of sign to
be 60" min above parking surface)
Inspector Comments:
12/15/2015PassQuinton OwensCommercial Building Final
Corrections made as indicated.Inspector Comments:
Electrical Inspection Type
04/29/2014PassBret StoddardCommercial Electrical Rough-in
05/27/2014FailBret StoddardCOM, COM-A, COM-R, and COM-T Electrical Final Inspection
Need to provide working clearance in front of electrical panels-soda syrup in
front, GFCI protection required in preparing area near sinks, cords for pendant
lights cannot go through ceiling tiles-also not listed(no labeling), strap up MC
cable above ceiling, install receptacle under counter, call for a re-inspect when
ready.
Inspector Comments:
05/29/2014PassBret StoddardCOM, COM-A, COM-R, and COM-T Electrical Final Inspection
Approved for a final and C.O.-Sodavine.Inspector Comments:
Fire Inspection Type
06/05/2014PassDale PickeringFire Department Final Inspection
Page 1 of 2
(Continued)
Permit Details Permit Number: 14-00152
SodaVine - Tenant Improvement
50 S 2nd W
Commercial Remodel
Permit Status of (Open) as of Report Date: 07/01/2019 8:31 am
Permit
Inspection
Summary
Plumbing Inspection Type
All good to cover ground workInspector Comments:
All good to cover ground workInspector Comments:
04/16/2014PassDon AllenPlumbing Underground Inspection
All good to cover ground workInspector Comments:
04/25/2014PassDon AllenPlumbing Rough-in
All good to cover the rough inInspector Comments:
05/27/2014FailDon AllenPlumbing Final Inspection
need to put in a dubble check on the ice maker and a rp on the popInspector Comments:
06/06/2014PassDon AllenPlumbing Final Inspection
All good for the c/oInspector Comments:
Page 2 of 2