HomeMy WebLinkAboutPLANS - 19-00391 - 237 N 2nd E - Solar PanelsSCOPE OF WORK
SYSTEM SIZE:STC: 210 x 350 = 73.500 kW
PTC: 210 x 337.7 = 70.917 kW DC
(210) BOVIET BVM6612-350
(8) SMA SB7.7-US
(1) SMA SB5.0-US
(1) SMA SB3.0-US
ATTACHMENT TYPE: SNAPNRACK CORRUGATED METAL ROOF
OWNER
NAME:BELL BLACK
PROJECT MANAGER
NAME:TREVER GERDES
PHONE: 2085698777
LECTRICIAN
NAMF:BRIAN MEYERS
LIC.NO: ELE-M-23939
AUTHORITIES HAVING JURISDICTION
BUILDING: CITY OF REXBURG
ZONING: CITY OF REXBURG
UTILITY:
DESIGN SPECIFICATIONS
OCCUPANCY: II
CONSTRUCTION:
ZONING:OFFICE
APPLICABLE CODES & STANDARDS
BUILDING: IBC 2015
ELECTRICAL: NEC 2017
FIRE:IFC 2015
PROJECT INFORMATION
NEW PV SYSTEM: 73.500 kWp
BELL BLACK
237 237 N 2ND E #100
REXBURG, ID 83440
2.1.1 SITE NOTES:
2.1.2 A LADDER WILL BE IN PLACE FOR INSPECTION IN COMPLIANCE WITH OSHA
REGULATIONS.
2.1.3 THE PV MODULES ARE CONSIDERED NON-COMBUSTIBLE AND THIS SYSTEM IS A
UTILITY INTERACTIVE SYSTEM WITH NO STORAGE BATTERIES.
2.1.4 THE SOLAR PV INSTALLATION WILL NOT OBSTRUCT ANY PLUMBING, MECHANICAL, OR
BUILDING ROOF VENTS.
2.1.5 PROPER ACCESS AND WORKING CLEARANCE AROUND EXISTING AND PROPOSED
ELECTRICAL EQUIPMENT WILL BE PROVIDED AS PER SECTION NEC 110.26.
2.1.6 ROOF COVERINGS SHALL BE DESIGNED, INSTALLED, AND MAINTAINED IN
ACCORDANCE WITH THIS CODE AND THE APPROVED MANUFACTURER'S
INSTRUCTIONS SUCH THAT THE ROOF COVERING SERVES TO PROTECT THE
BUILDING OR STRUCTURE.
2.2.1 EQUIPMENT LOCATIONS
2.2.2 ALL EQUIPMENT SHALL MEET MINIMUM SETBACKS AS REQUIRED BY NEC 110.26.
2.2.3 WIRING SYSTEMS INSTALLED IN DIRECT SUNLIGHT MUST BE RATED FOR EXPECTED
OPERATING TEMPERATURE AS SPECIFIED BY NEC 690.31 (A),(C) AND NEC TABLES
310.15 (B)(2)(A) AND 310.15 (B)(3)(C).
2.2.3 JUNCTION AND PULL BOXES PERMITTED INSTALLED UNDER PV MODULES
ACCORDING TO NEC 690.34.
2.2.4 ADDITIONAL AC DISCONNECT(S) SHALL BE PROVIDED WHERE THE INVERTER IS NOT
WITHIN SIGHT OF THE AC SERVICING DISCONNECT.
2.2.5 ALL EQUIPMENT SHALL BE INSTALLED ACCESSIBLE TO QUALIFIED PERSONNEL
ACCORDING TO NEC APPLICABLE CODES.
2.2.6 ALL COMPONENTS ARE LISTED FOR THEIR PURPOSE AND RATED FOR OUTDOOR
USAGE WHEN APPROPRIATE.
2.3.1 STRUCTURAL NOTES:
2.3.2 RACKING SYSTEM & PV ARRAY WILL BE INSTALLED ACCORDING TO
CODE-COMPLIANT INSTALLATION MANUAL. TOP CLAMPS REQUIRE A
DESIGNATED SPACE BETWEEN MODULES, AND RAILS MUST ALSO EXTEND A
MINIMUM DISTANCE BEYOND EITHER EDGE OF THE ARRAY/SUBARRAY,
ACCORDING TO RAIL MANUFACTURER’S INSTRUCTIONS.
2.3.3 JUNCTION BOX WILL BE INSTALLED PER MANUFACTURERS' SPECIFICATIONS.
IF ROOF-PENETRATING TYPE, IT SHALL BE FLASHED & SEALED PER LOCAL
REQUIREMENTS.
2.3.4 ROOFTOP PENETRATIONS FOR PV RACEWAY WILL BE COMPLETED AND
SEALED W/ APPROVED CHEMICAL SEALANT PER CODE BY A LICENSED
CONTRACTOR.
2.3.5 ALL PV RELATED ROOF ATTACHMENTS TO BE SPACED NO GREATER THAN THE
SPAN DISTANCE SPECIFIED BY THE RACKING MANUFACTURER.
2.3.6 WHEN POSSIBLE, ALL PV RELATED RACKING ATTACHMENTS WILL BE
STAGGERED AMONGST THE ROOF FRAMING MEMBERS.
2.4.1 GROUNDING NOTES:
2.4.2 GROUNDING SYSTEM COMPONENTS SHALL BE LISTED FOR THEIR PURPOSE, AND
GROUNDING DEVISES EXPOSED TO THE ELEMENTS SHALL BE RATED FOR SUCH
USE.
2.4.3 PV SYSTEMS REQUIRE AN EQUIPMENT GROUNDING CONDUCTOR. ALL METAL
ELECTRICAL EQUIPMENT AND STRUCTURAL COMPONENTS BONDED TO GROUND, IN
ACCORDANCE WITH 250.134 OR 250.136(A). ONLY THE DC CONDUCTORS ARE
UNGROUNDED.
2.4.4 PV EQUIPMENT SHALL BE GROUNDED ACCORDING TO NEC 690.43 AND MINIMUM
NEC TABLE 250.122.
2.4.5 METAL PARTS OF MODULE FRAMES, MODULE RACKING, AND ENCLOSURE
CONSIDERED GROUNDED IN ACCORD WITH 250.134 AND 250.136(A).
2.4.6 EACH MODULE WILL BE GROUNDED USING WEEB GROUNDING CLIPS AS SHOWN IN
MANUFACTURER DOCUMENTATION AND APPROVED BY THE AHJ. IF WEEBS ARE
NOT USED, MODULE GROUNDING LUGS MUST BE INSTALLED AT THE SPECIFIED
GROUNDING LUG HOLES PER THE MANUFACTURERS' INSTALLATION
REQUIREMENTS.
2.4.7 THE GROUNDING CONNECTION TO A MODULE SHALL BE ARRANGED SUCH THAT
THE REMOVAL OF A MODULE DOES NOT INTERRUPT A GROUNDING CONDUCTOR TO
ANOTHER MODULE.
2.4.8 GROUNDING AND BONDING CONDUCTORS, IF INSULATED, SHALL BE COLORED
GREEN OR MARKED GREEN IF #4 AWG OR LARGER [NEC 250.119]
2.4.9 THE GROUNDING ELECTRODE SYSTEM COMPLIES WITH NEC 690.47 AND NEC 250.50
THROUGH 250.106. IF EXISTING SYSTEM IS INACCESSIBLE, OR INADEQUATE, A
GROUNDING ELECTRODE SYSTEM PROVIDED ACCORDING TO NEC 250, NEC 690.47
AND AHJ.
2.4.10 DC PV ARRAYS SHALL BE PROVIDED WITH DC GROUND-FAULT PROTECTION MEETING
THE REQUIREMENTS OF 690.41(B)(1) AND (2) TO REDUCE FIRE HAZARDS
2.5.1 INTERCONNECTION NOTES:
2.5.2 LOAD-SIDE INTERCONNECTION SHALL BE IN ACCORDANCE WITH [NEC 705.12
(B)]
2.5.3 THE SUM OF THE UTILITY OCPD AND INVERTER CONTINUOUS OUTPUT MAY
NOT EXCEED 120% OF BUSBAR RATING [NEC 705.12(B)(2)(3)].
2.5.4 THE SUM OF 125 PERCENT OF THE POWER SOURCE(S) OUTPUT CIRCUIT
CURRENT AND THE RATING OF THE OVERCURRENT DEVICE PROTECTING THE
BUSBAR SHALL NOT EXCEED 120 PERCENT OF THE AMPACITY OF THE
BUSBAR, PV DEDICATED BACKFEED BREAKERS MUST BE LOCATED OPPOSITE
END OF THE BUS FROM THE UTILITY SOURCE OCPD [NEC 705.12(B)(2)(3)].
2.5.5 AT MULTIPLE ELECTRIC POWER SOURCES OUTPUT COMBINER PANEL, TOTAL
RATING OF ALL OVERCURRENT DEVICES SHALL NOT EXCEED AMPACITY OF
BUSBAR. HOWEVER, THE COMBINED OVERCURRENT DEVICE MAY BE
EXCLUDED ACCORDING TO NEC 705.12 (B)(2)(3)(C).
2.5.6 FEEDER TAP INTERCONECTION (LOAD SIDE) ACCORDING TO NEC 705.12
(B)(2)(1)
2.5.7 SUPPLY SIDE TAP INTERCONNECTION ACCORDING TO NEC 705.12 (A) WITH
SERVICE ENTRANCE CONDUCTORS IN ACCORDANCE WITH NEC 230.42
2.5.8 BACKFEEDING BREAKER FOR ELECTRIC POWER SOURCES OUTPUT IS EXEMPT
FROM ADDITIONAL FASTENING [NEC 705.12 (B)(5)].
2.6.1 DISCONNECTION AND OVER-CURRENT PROTECTION NOTES:
2.6.2 DISCONNECTING SWITCHES SHALL BE WIRED SUCH THAT WHEN THE SWITCH
IS OPENED THE CONDUCTORS REMAINING ENERGIZED ARE CONNECTED TO
THE TERMINALS MARKED “LINE SIDE” (TYPICALLY THE UPPER TERMINALS).
2.6.3 DISCONNECTS TO BE ACCESSIBLE TO QUALIFIED UTILITY PERSONNEL, BE
LOCKABLE, AND BE A VISIBLE-BREAK SWITCH.
2.6.4 BOTH POSITIVE AND NEGATIVE PV CONDUCTORS ARE UNGROUNDED.
THEREFORE BOTH MUST OPEN WHERE A DISCONNECT IS REQUIRED,
ACCORDING TO NEC 690.13.
2.6.5 ISOLATING DEVICES OR EQUIPMENT DISCONNECTING MEANS SHALL BE
INSTALLED IN CIRCUITS CONNECTED TO EQUIPMENT AT A LOCATION WITHIN
THE EQUIPMENT, OR WITHIN SIGHT AND WITHIN 10 FT OF THE EQUIPMENT. AN
EQUIPMENT DISCONNECTING MEANS SHALL BE PERMITTED TO BE REMOTE
FROM THE EQUIPMENT WHERE THE EQUIPMENT DISCONNECTING MEANS CAN
BE REMOTELY OPERATED FROM WITHIN 10 FT OF THE EQUIPMENT,
ACCORDING TO NEC 690.15 (A).
2.6.6 PV SYSTEM CIRCUITS INSTALLED ON OR IN BUILDINGS SHALL INCLUDE A
RAPID SHUTDOWN FUNCTION TO REDUCE SHOCK HAZARD FOR EMERGENCY
RESPONDERS IN ACCORDANCE WITH 690.12(A) THROUGH (D)
2.6.7 ALL OCPD RATINGS AND TYPES SPECIFIED ACCORDING TO NEC 690.8, 690.9,
AND 240.
2.6.8 BOTH POSITIVE AND NEGATIVE PV CONDUCTORS ARE UNGROUNDED,
THEREFORE BOTH REQUIRE OVER-CURRENT PROTECTION, ACCORDING TO
NEC 240.21. (SEE EXCEPTION IN NEC 690.9)
2.6.9 IF REQUIRED BY AHJ, SYSTEM WILL INCLUDE ARC-FAULT CIRCUIT PROTECTION
ACCORDING TO NEC 690.11 AND UL1699B.
2.7.1 WIRING & CONDUIT NOTES:
2.7.2 ALL CONDUIT AND WIRE WILL BE LISTED AND APPROVED FOR THEIR PURPOSE.
CONDUIT AND WIRE SPECIFICATIONS ARE BASED ON MINIMUM CODE
REQUIREMENTS AND ARE NOT MEANT TO LIMIT UP-SIZING.
2.7.3 ALL CONDUCTORS SIZED ACCORDING TO NEC 690.8, NEC 690.7.
2.7.4 EXPOSED PV SOURCE CIRCUITS AND OUTPUT CIRCUITS SHALL USE WIRE
LISTED AND IDENTIFIED AS PHOTOVOLTAIC (PV) WIRE [690.31 (C)]. PV
MODULES WIRE LEADS SHALL BE LISTED FOR USE ON PV ARRAYS,
ACCORDING TO NEC 690.31 (A).
2.7.5 PV WIRE BLACK WIRE MAY BE FIELD-MARKED WHITE [NEC 200.6 (A)(6)].
2.7.6 MODULE WIRING SHALL BE LOCATED AND SECURED UNDER THE ARRAY.
2.7.7 ACCORDING TO NEC 200.7, UNGROUNDED SYSTEMS DC CONDUCTORS
COLORED OR MARKED AS FOLLOWS:
DC POSITIVE-RED, OR OTHER COLOR EXCLUDING WHITE, GREY AND
GREEN
DC NEGATIVE- BLACK, OR OTHER COLOR EXCLUDING WHITE, GREY
AND GREEN
2.7.8 AC CONDUCTORS COLORED OR MARKED AS FOLLOWS:
PHASE A OR L1- BLACK
PHASE B OR L2- RED, OR OTHER CONVENTION IF THREE PHASE
PHASE C OR L3- BLUE, YELLOW, ORANGE*, OR OTHER CONVENTION
NEUTRAL- WHITE OR GREY
* IN 4-WIRE DELTA CONNECTED SYSTEMS THE PHASE WITH HIGHER VOLTAGE
TO BE MARKED ORANGE [NEC 110.15].
2017S
A-201
01
E MAIN ENTRANCE DOOR PROPERTY LINE
SOLAR (PV) MODULE
EQUIPMENT GROUND
CONDUIT
FIRE CLEARANCE
(E) UTILITY METERM
S
PNL
VMEP
AC DISCONNECT
AC PANELBOARD
PV REVENUE METERMAIN ELECTRICAL PANEL
DC/AC INVERTER
DC DISCONNECT
COMBINER BOX
JUNCTION BOX
I
DCSW
CBR
JB U UTILITY POLE
TB
RSD
TAP BOX
RAPID SHUTDOWN
SUB (AC) PANEL
METER/MAIN
SUB
M/M
CBR
MODULE STRINGING
(DC) COMBINER BOX
A
B
MODULE STRINGING
MODULE STRINGING
ATTACHMENTS
RAILS
ROOF RAFTERS
N
EW
S
A-201
D1
26
SYMBOL LEGEND
C MODULE STRINGING
D MODULE STRINGING
SHEET KEYNOTE INDICATOR
DETAIL INDICATOR
ELEVATION INDICATOR
NORTH INDICATOR
DISCLAIMER: PLEASE NOTE THAT THE ABBREVIATIONS, ANNOTATIONS, AND SYMBOLS LISTED ARE INTENDED TO ILLUSTRATE THOSE THAT ARE COMMONLY USED; NOT ALL ARE NECESSARILY UTILIZED WITHIN THIS SET OF DRAWINGS.
NEW PV SYSTEM: 73.500 kWp
ENGINEER OF RECORD
DATE:05.25.2019
DESIGN BY:A.L.
CHECKED BY:M.M.
BELL BLACK
237 N 2ND E #100,
REXBURG, ID 83440
PAPER SIZE: 36" x 24" (ARCH D)
A B C D E F G H I J K L M N O
1
2
3
4
5
6
7
8
9
10
11
12
A B C D E F G H I J K L M N O
CONTRACTOR
BLUE MAX ENERGY & CONSULTING LLC
PHONE:2085698777
LIC. NO.:RCE-47820
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN
VIOLATION OF U.S. COPYRIGHT LAWS
AND WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
P
P
NO.DESCRIPTION DATE
PROJECT
REVISION / RELEASE
SHEET NUMBER:
SHEET TITLE:
T-001.00
COVER PAGE
(SHEET 1 OF 19)
01 AERIAL PHOTO
NOT TO SCALE
N
EW
S
02 PLAT MAP
NOT TO SCALE
N
2
N
D
E
#
1
0
0
N
EW
S
SHEET SCHEDULE
SHEET NUMBER SHEET TITLE
T-001 COVER PAGE
A-101 SITE PLAN
A-102 ELECTRICAL PLAN
E-601 SINGLE LINE DIAGRAM #1-6
A-103 SOLAR ATTACHMENT PLAN
E-602 PLACARD #1-6
S-501 ASSEMBLY DETAILS
R-001 - R-002 RESOURCE DOCUMENT
CONSTRUCTION NOTES
GENERAL NOTES
1.FIELD VERIFY ALL MEASUREMENTS
2.ITEMS BELOW MAY NOT BE ON THIS PAGE
NEW PV SYSTEM: 73.500 kWp
ENGINEER OF RECORD
DATE:05.25.2019
DESIGN BY:A.L.
CHECKED BY:M.M.
BELL BLACK
237 N 2ND E #100,
REXBURG, ID 83440
PAPER SIZE: 36" x 24" (ARCH D)
A B C D E F G H I J K L M N O
1
2
3
4
5
6
7
8
9
10
11
12
A B C D E F G H I J K L M N O
CONTRACTOR
BLUE MAX ENERGY & CONSULTING LLC
PHONE:2085698777
LIC. NO.:RCE-47820
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN
VIOLATION OF U.S. COPYRIGHT LAWS
AND WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
P
P
NO.DESCRIPTION DATE
PROJECT
REVISION / RELEASE
SHEET NUMBER:
SHEET TITLE:
N
EW
S
01/32" = 1'-0"
SITE PLAN01 16'32'
A-101.00
SITE PLAN
(SHEET 2 OF 19)
N
2
N
D
E
#
1
0
0
INVERTERS
COMBINER PANEL
AC DISCONNECT
INVERTER
AC DISCONNECT
INVERTER
AC DISCONNECT
INVERTER
AC DISCONNECT
INVERTERS
COMBINER PANEL
AC DISCONNECT
INVERTERS
COMBINER PANEL
AC DISCONNECT
81
'
-
4
"
9'-8"
14'-11"
3'-4"
GENERAL NOTES
1.FIELD VERIFY ALL MEASUREMENTS
2.SEE SHEET T-001 FOR LEGEND OF SYMBOLS
MODULE:
BOVIET
BVM6612-350
350 WATTS
37.09"
77
.
0
1
"
NEW PV SYSTEM: 73.500 kWp
ENGINEER OF RECORD
DATE:05.25.2019
DESIGN BY:A.L.
CHECKED BY:M.M.
BELL BLACK
237 N 2ND E #100,
REXBURG, ID 83440
PAPER SIZE: 36" x 24" (ARCH D)
A B C D E F G H I J K L M N O
1
2
3
4
5
6
7
8
9
10
11
12
A B C D E F G H I J K L M N O
CONTRACTOR
BLUE MAX ENERGY & CONSULTING LLC
PHONE:2085698777
LIC. NO.:RCE-47820
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN
VIOLATION OF U.S. COPYRIGHT LAWS
AND WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
P
P
NO.DESCRIPTION DATE
PROJECT
REVISION / RELEASE
SHEET NUMBER:
SHEET TITLE:
03/16" = 1'
ELECTRICAL PLAN012'-8"5'-4"
A-102.00
ELECTRICAL PLAN
(SHEET 3 OF 19)
EXTERIOR EQUIPMENT
(N) (3) INVERTERS
(N) (1) COMBINER PANEL
(N) (1) AC DISCONNECT
(N) (1) INVERTER
(N) (1) AC DISCONNECT
EXTERIOR EQUIPMENT
(N) (2) INVERTERS
(N) (1) COMBINER PANEL
(N) (1) AC DISCONNECT
(N) (1) INVERTER
(N) (1) AC DISCONNECT
(N) (1) INVERTER
(N) (1) AC DISCONNECT
(N) (2) INVERTERS
(N) (1) COMBINER PANEL
(N) (1) AC DISCONNECT
EXTERIOR EQUIPMENT EXTERIOR EQUIPMENT
EXTERIOR EQUIPMENT
EXTERIOR EQUIPMENT
INTERIOR EQUIPMENT
(E) (1) METER/MAIN
INTERIOR EQUIPMENT
(E) (1) METER/MAIN
INTERIOR EQUIPMENT
(E) (1) METER/MAIN
INTERIOR EQUIPMENT
(E) (1) METER/MAIN
INTERIOR EQUIPMENT
(E) (1) METER/MAIN
INTERIOR EQUIPMENT
(E) (1) METER/MAIN
3'-0" FIRE ACCESS PATH
3'-0" FIRE ACCESS PATH
3'-0" FIRE ACCESS PATH
3'-0" FIRE ACCESS PATH
A MODULE STRINGING
FIRE CLEARANCE
B MODULE STRINGING
1-B
1-A
1-B
1-A
1-B
1-A
1-B
1-A
1-B
1-A
1-B
1-A
1-C
2-A
1-C
2-A
1-C
2-A
1-C
2-A
1-C
2-A
1-C
2-A
1-C
2-A
1-C
2-A
2-B
2-C
2-B
2-C
2-B
2-C
2-B
2-C
2-B
2-C
2-B
2-C
2-B
2-C
2-B
2-C
3-A
3-A
3-A
3-A
3-A
3-A
7-A
7-B
7-A
7-B
7-A
7-B
7-A
7-B
7-A
7-B
7-A
7-B
7-A
7-B
7-A
7-B
8-C
8-C
8-C
8-C
8-C
8-C
8-C
8-C
5-A
5-A
5-A
5-A
3-B
5-A
3-B
3-C
3-B
3-C
3-B
3-C
7-C
8-A
7-C
8-A
7-C
8-A
7-C
8-A
7-C
8-A
7-C
8-A
7-C
8-A
8-B
8-B
8-B
8-B
8-B
9-A
8-B
9-A
8-B
9-A 9-A
5-B
5-C
5-B
5-C
5-B
5-C
5-A
5-A
5-A
5-A
4-A
4-B
4-A
4-B
4-A
4-B
4-A
4-B
10-B
10-B
10-B
10-B
10-B
10-B
10-B
10-B
10-B
10-B
10-A
10-A
10-A
10-A
10-A
10-A
10-A
10-A
9-A
9-A
9-A
6-C
9-A
6-C
5-C
6-C
5-C
6-C
5-C
6-C
5-C
6-C
5-C
6-C
6-A
6-B
6-A
6-B
6-A
6-B
6-A
6-B
6-A
6-B
6-A
6-B
6-A
6-B
6-A
6-B
3-B
3-C
3-B
3-C
3-B
3-C
3-B
3-C
4-A
4-B
4-A
4-B
4-A
4-B
4-A
4-B
6-A
6-B
6-A
6-B
3-A
3-A
1-B
1-A
1-B
1-A
5-B
5-B
5-B
5-B5-B
ARRAY 1 - 19.600 kW
[x56] (N) MODULES
TILT: 20 DEGREES
AZIMUTH: 0 DEGREES
ARRAY 2 - 53.900 kW
[x154] (N) MODULES
TILT: 20 DEGREES
AZIMUTH: 180 DEGREES
MODULE:
BOVIET
BVM6612-350
350 WATTS
37.09"
77
.
0
1
"
NEW PV SYSTEM: 73.500 kWp
ENGINEER OF RECORD
DATE:05.25.2019
DESIGN BY:A.L.
CHECKED BY:M.M.
BELL BLACK
237 N 2ND E #100,
REXBURG, ID 83440
PAPER SIZE: 36" x 24" (ARCH D)
A B C D E F G H I J K L M N O
1
2
3
4
5
6
7
8
9
10
11
12
A B C D E F G H I J K L M N O
CONTRACTOR
BLUE MAX ENERGY & CONSULTING LLC
PHONE:2085698777
LIC. NO.:RCE-47820
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN
VIOLATION OF U.S. COPYRIGHT LAWS
AND WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
P
P
NO.DESCRIPTION DATE
PROJECT
REVISION / RELEASE
SHEET NUMBER:
SHEET TITLE:
N
EW
S
03/16" = 1'
ROOF FRAMING PLAN012'-8"5'-4"
A-103.00
ROOF FRAMING PLAN
(SHEET 4 OF 19)
94'-3"
ROOF MATERIAL IS
CORRUGATED METAL
FLUSH MOUNT SOLAR
MODULES ATTACHED TO
ROOF SURFACE (SEE
SHEET S-501 FOR
MOUNTING DETAILS)
91'
G
G
200А AC LOAD CENTER
120/240V, 1Ø, 3W
L1
N
L2
03
L2 N
G
G L1
02
1-A 1-B
SMA
SB 7.7-1SP-US-40-240V
(E) MAIN
A400
TO UTILITY
GRID (UG)
L1 L2
N
(E) GROUNDING
ELECTRODE
GROUND
ROD
(E) MAIN SERVICE PANEL
120/240 V 1Ø, 3W
MAIN BUSS:400A
N
G
(E) UTILITY
METER
TO (E)
LOADS
NN L2 L1
EQUIPMENT ABOVE
LINE IS (N) NEW
EQUIPMENT BELOW
LINE IS (E) EXISTING
UNLESS OTHERWISE
NOTED.
1-C
BOVIET
BVM6612-350
SMA TS4-R-F
OPTIMIZERS
G
125A
03
L2 N
G
G L1
02
2-A 2-B
SMA
SB 7.7-1SP-US-40-240V
2-C
03
L2 N
G
G L1
02
3-A 3-B 3-C
04
05
F1-2
40A/2P
CB1
40A/2P
CB2
40A/2P
CB3
200А AC DISCONNECT
BOVIET
BVM6612-350
SMA TS4-R-F
OPTIMIZERS
BOVIET
BVM6612-350
SMA TS4-R-F
OPTIMIZERS
8 8 8 8 8 8 8 8 7
01 01 01
G G
NEW PV SYSTEM: 73.500 kWp
ENGINEER OF RECORD
DATE:05.25.2019
DESIGN BY:A.L.
CHECKED BY:M.M.
BELL BLACK
237 N 2ND E #100,
REXBURG, ID 83440
PAPER SIZE: 36" x 24" (ARCH D)
A B C D E F G H I J K L M N O
1
2
3
4
5
6
7
8
9
10
11
12
A B C D E F G H I J K L M N O
CONTRACTOR
BLUE MAX ENERGY & CONSULTING LLC
PHONE:2085698777
LIC. NO.:RCE-47820
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN
VIOLATION OF U.S. COPYRIGHT LAWS
AND WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
P
P
NO.DESCRIPTION DATE
PROJECT
REVISION / RELEASE
SHEET NUMBER:
SHEET TITLE:
01 SINGLE LINE DIAGRAM #1
NOT TO SCALE E-601.00
SINGLE LINE DIAGRAM #1
(SHEET 5 OF 19)
CONDUCTOR AND CONDUIT SCHEDULE W/ELECTRICAL CALCULATIONS
ID TYPICAL CONDUCTOR CONDUIT CURRENT-CARRYING CONDUCTORS
IN CONDUIT OCPD EGC TEMP. CORR. FACTOR CONDUIT FILL FACTOR CONT. CURRENT MAX. CURRENT (125%)BASE AMP.DERATED AMP.TERM. TEMP. RATING AMP. @ TERMINAL
01 9 10 AWG PV WIRE, COPPER FREE AIR 2 N/A 6 AWG BARE, COPPER 0.76 (54.9°C)1 11.98A 14.98A 55A 41.8A 75°C 50A
02 3 10 AWG THWN-2, COPPER 0.75" DIA PVC-40 6 N/A 10 AWG THWN-2, COPPER 0.76 (54.9°C)0.8 11.98A 14.98A 40A 24.32A 75°C 35A
03 3 8 AWG THWN-2, COPPER 0.75" DIA PVC-40 2 40A 10 AWG THWN-2, COPPER 0.96 (32.9°C)1 32A 40A 55A 52.8A 75°C 50A
04 1 1 AWG THWN-2, COPPER 1" DIA PVC-40 2 125A 6 AWG THWN-2, COPPER 0.96 (32.9°C)1 96A 120A 150A 144A 75°C 135A
05 1 1 AWG THWN-2, COPPER 1" DIA PVC-40 2 125A 6 AWG THWN-2, COPPER 0.96 (32.9°C)1 96A 120A 150A 144A 75°C 135A
BILL OF MATERIALS
CATEGORY MAKE MODEL NUMBER REF QTY UNIT QTY/UNIT DESCRIPTION
MODULE BOVIET BVM6612-350 PM1-71 71 PIECES 1 BOVIET BVM6612-350 350W 72 CELLS, POLYCRYSTALLINE SILICON
INVERTER SMA SB 7.7-1SP-US-40 (240V)I1-3 3 PIECES 1 SMA SB 7.7-1SP-US-40 (240V) 7680W INVERTER
MODULE OPTIMIZER SMA TS4-R-F PO1-71 71 PIECES 1 SMA TS4-R-F OPTIMIZER (REQUIRED PART OF INVERTER'S DISTRIBUTED DC ARCHITECTURE)
DISCONNECT SQUARE D D224NRB SW1 1 PIECE 1 SQUARE D D224NRB, 2-POLE, 200A, 240VAC OR EQUIVALENT
WIRING GEN-10-AWG-PV-WIRE-CU WR1 TBD FEET 1 10 AWG PV WIRE, COPPER (POSITIVE AND NEGATIVE)
WIRING GEN-6-AWG-BARE-CU WR1 TBD FEET 1 6 AWG BARE, COPPER (GROUND)
WIRING GEN-10-AWG-THWN-2-CU-RD WR2 TBD FEET 1 10 AWG THWN-2, COPPER, RED (LINE 1)
WIRING GEN-10-AWG-THWN-2-CU-BLK WR2 TBD FEET 1 10 AWG THWN-2, COPPER, BLACK (LINE 2)
WIRING GEN-10-AWG-THWN-2-CU-GR WR2-3 TBD FEET 1 10 AWG THWN-2, COPPER, GREEN (GROUND)
WIRING GEN-8-AWG-THWN-2-CU-RD WR3 TBD FEET 1 8 AWG THWN-2, COPPER, RED (LINE 1)
WIRING GEN-8-AWG-THWN-2-CU-BLK WR3 TBD FEET 1 8 AWG THWN-2, COPPER, BLACK (LINE 2)
WIRING GEN-8-AWG-THWN-2-CU-WH WR3 TBD FEET 1 8 AWG THWN-2, COPPER, WHITE (NEUTRAL)
WIRING GEN-1-AWG-THWN-2-CU-RD WR3-4 TBD FEET 1 1 AWG THWN-2, COPPER, RED (LINE 1)
WIRING GEN-1-AWG-THWN-2-CU-BLK WR3-4 TBD FEET 1 1 AWG THWN-2, COPPER, BLACK (LINE 2)
WIRING GEN-1-AWG-THWN-2-CU-WH WR3-4 TBD FEET 1 1 AWG THWN-2, COPPER, WHITE (NEUTRAL)
WIRING GEN-6-AWG-THWN-2-CU-GR WR3-5 TBD FEET 1 6 AWG THWN-2, COPPER, GREEN (GROUND)
WIREWAY GEN-PVC-40-0.75" DIA WW2-3 TBD FEET 1 PVC-40 CONDUIT, 0.75'' DIA
WIREWAY GEN-PVC-40-1" DIA WW4-5 TBD FEET 1 PVC-40 CONDUIT, 1'' DIA
OCPD GENERIC MANUFACTURER GEN-FU-125A-240VAC F1-2 2 PIECES 1 FUSE, 125A, 240VAC
SYSTEM SUMMARY
INVERTER #1 INVERTER #1 INVERTER #1
MPPT #1 MPPT #2 MPPT #3 MPPT #1 MPPT #2 MPPT #3 MPPT #1 MPPT #2 MPPT #3
MODULES IN SERIES 8 8 8 8 8 8 8 8 7
ARRAY VMP 308.8V 308.8V 308.8V 308.8V 308.8V 308.8V 308.8V 308.8V 270.2V
ARRAY IMP 9.07A 9.07A 9.07A 9.07A 9.07A 9.07A 9.07A 9.07A 9.07A
ARRAY VOC 376V 376V 376V 376V 376V 376V 376V 376V 329V
ARRAY MAX VOC 440.3V 440.3V 440.3V 440.3V 440.3V 440.3V 440.3V 440.3V 385.3V
ARRAY ISC 9.58A 9.58A 9.58A 9.58A 9.58A 9.58A 9.58A 9.58A 9.58A
ARRAY STC POWER 8,400W 8,400W 8,050W
ARRAY PTC POWER 7,721W 7,721W 7,399W
MAX AC CURRENT 32A 32A 32A
MAX AC POWER 7,680W 7,680W 7,680W
ARRAY STC POWER 24,130W
ARRAY PTC POWER 22,841W
MAX AC CURRENT 96AW
MAX AC POWER 23,040W
DESIGN TEMPERATURES
ASHRAE EXTREME LOW -30.2°C (-22.4°F), SOURCE: REXBURG MADISON CO (43.83°; -111.88°)
ASHRAE 2% HIGH 32.9°C (91.2°F), SOURCE: REXBURG MADISON CO (43.83°; -111.88°)
INVERTERS
REF.QTY.MAKE AND MODEL AC VOLTAGE GROUND OCPD
RATING RATED POWER MAX OUTPUT
CURRENT
MAX INPUT
CURRENT MAX INPUT VOLTAGE CEC WEIGHTED
EFFICIENCY
I1-3 3 SMA SB 7.7-1SP-US-40 (240V)240V FLOATING 40A 7680W 32A 3X18A 600V 97.0%
MODULES
REF.QTY.MAKE AND MODEL PMAX PTC ISC IMP VOC VMP TEMP. COEFF. OF VOC FUSE RATING
PM1-71 71 BOVIET BVM6612-350 350W 321.7W 9.58A 9.07A 47V 38.6V -0.146V/°C (-0.31%/°C)15A
DISCONNECTS
REF.QTY.MAKE AND MODEL RATED CURRENT MAX RATED VOLTAGE
SW1 1 SQUARE D D224NRB OR EQUIV.200A 240VAC
OCPDS
REF.QTY.RATED CURRENT MAX VOLTAGE
F1-2 2 125A 240VAC
POWER OPTIMIZERS
REF.QTY.MODEL RATED INPUT POWER MAX OUTPUT CURRENT MAX INPUT ISC MAX DC VOLTAGE WEIGHTED EFFICIENCY
PO1-71 71 SMA TS4-R-F 475W 15A 12A 75V 100.0%
NEW PV SYSTEM: 73.500 kWp
ENGINEER OF RECORD
DATE:05.25.2019
DESIGN BY:A.L.
CHECKED BY:M.M.
BELL BLACK
237 N 2ND E #100,
REXBURG, ID 83440
PAPER SIZE: 36" x 24" (ARCH D)
A B C D E F G H I J K L M N O
1
2
3
4
5
6
7
8
9
10
11
12
A B C D E F G H I J K L M N O
CONTRACTOR
BLUE MAX ENERGY & CONSULTING LLC
PHONE:2085698777
LIC. NO.:RCE-47820
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN
VIOLATION OF U.S. COPYRIGHT LAWS
AND WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
P
P
NO.DESCRIPTION DATE
PROJECT
REVISION / RELEASE
SHEET NUMBER:
SHEET TITLE:
FRONTPV ARRAY
BACK
!CAUTION!
POWER TO THIS BUILDING IS ALSO SUPPLIED
FROM ROOF MOUNTED SOLAR ARRAYS WITH
SAFETY DISCONNECTS AS SHOWN:
N
EW
S
E-602.00
PLACARDS #1
(SHEET 6 OF 19)
MAIN DISTRIBUTION
UTILITY DISCONNECT
! WARNING !
DUAL POWER SOURCES.
SECOND SOURCE IS PV SYSTEM
LABEL 6
PHOTOVOLTAIC
AC DISCONNECT
OPERATING CURRENT: 96 A AC
OPERATING VOLTAGE: 240 V AC
LABEL 5
AT POINT OF INTERCONNECTION, MARKED
AT DISCONNECTING MEANS
[NEC 690.54]
! WARNING !
ELECTRIC SHOCK HAZARD
TERMINALS ON BOTH LINE AND LOAD SIDES
MAY BE ENERGIZED IN THE OPEN POSITION.
LABEL 3
AT EACH DISCONNECTING MEANS FOR
PHOTOVOLTAIC EQUIPMENT
[NEC 690.13 AND 690.15]
PHOTOVOLTAIC
AC DISCONNECT
WARNING: PHOTOVOLTAIC
POWER SOURCE
LABEL 11
AT EXPOSED RACEWAYS, CABLE TRAYS, AND OTHER WIRING
METHODS; SPACED AT MAXIMUM 10 FT SECTION OR WHERE
SEPARATED BY ENCLOSURES, WALLS, PARTITIONS, CEILINGS,
OR FLOORS.
[NEC 690.31(G)]
LETTERS AT LEAST 3/8 INCH; WHITE ON RED BACKGROUND;
REFLECTIVE
[IFC 605.11.1.1]
LABEL 12
AT EACH AC DISCONNECTING MEANS
[NEC 690.13(B)]
! CAUTION !
PHOTOVOLTAIC SYSTEM
CIRCUIT IS BACKFED
! WARNING !
POWER SOURCE OUTPUT
CONNECTION - DO NOT RELOCATE
THIS OVERCURRENT DEVISE
LABEL 13
AT POINT OF INTERCONNECTION
OVERCURRENT DEVICE
[NEC 705.12(B)(2)(3)(B)]
INTERACTIVE PHOTOVOLTAIC SYSTEM
CONNECTED
LABEL 8
AT UTILITY METER
[NEC 690.56(B)]
PHOTOVOLTAIC SYSTEM
EQUIPPED WITH RAPID
SHUTDOWN
LABEL 10
AT RAPID SHUTDOWN SWITCH
[NEC 690.56(C)].
LETTERS AT LEAST 3/8 INCH; WHITE ON RED
BACKGROUND; REFLECTIVE
[IFC 605.11.1.1]
LABEL 7
LABELING NOTES
1.1 LABELING REQUIREMENTS BASED ON THE 2017 NATIONAL ELECTRICAL CODE, INTERNATIONAL FIRE CODE 605.11, OSHA
STANDARD 1910.145, ANSI Z535
1.2 MATERIAL BASED ON THE REQUIREMENTS OF THE AUTHORITY HAVING JURISDICTION.
1.3 LABELS TO BE OF SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENT INVOLVED.
1.4 LABELS TO BE A MINIMUM LETTER HEIGHT OF 3/8” AND PERMANENTLY AFFIXED.
1.5 ALERTING WORDS TO BE COLOR CODED. “DANGER” WILL HAVE RED BACKGROUND; “WARNING” WILL HAVE ORANGE
BACKGROUND; “CAUTION” WILL HAVE YELLOW BACKGROUND. [ANSI Z535]
DIRECTORY
PERMANENT PLAQUE OR DIRECTORY PROVIDING THE
LOCATION OF THE SERVICE DISCONNECTING MEANS
AND THE PHOTOVOLTAIC SYSTEM DISCONNECTING
MEANS IF NOT IN THE SAME LOCATION
[NEC 690.56(B)]
PLAQUE
AT POINT OF INTERCONNECTION; LABEL, SUCH AS LABEL 5 OR LABEL 6 MUST IDENTIFY
PHOTOVOLTAIC SYSTEM
[NEC 705.12(B)(4)]
WHERE THE PV SYSTEMS ARE REMOTELY LOCATED FROM EACH
OTHER, A DIRECTORY IN ACCORDANCE WITH 705.10 SHALL BE
PROVIDED AT EACH PV SYSTEM DISCONNECTING MEANS.
PV SYSTEM EQUIPMENT AND DISCONNECTING MEANS SHALL NOT BE
INSTALLED IN BATHROOMS
[NEC 690.4(D),(E)]
SOLAR PV SYSTEM EQUIPPED
WITH RAPID SHUTDOWN
TURN RAPID SHUTDOWN
SWICH TO THE "OFF"
POSITION TO SHUTDOWN
PV SYSTEM AND REDUCE
SHOCK HAZARD IN ARRAY
SOLAR ELECTRIC
PV PANELS
LABEL 1
AT RAPID SHUTDOWN SYSTEM
[NEC 690.56(C)(1)(A)].
LABEL 3 INVERTER #1-3
AT EACH APPLICABLE DC DISCONNECTING
MEANS
[NEC 690.53]
OPERATING CURRENT: 9.07 A DC
OPERATING VOLTAGE:308.8 V DC
MAX SHORT CURRENT:9.58 A DC
MAX VOLTAGE:440.3 V DC
INTERACTIVE PHOTOVOLTAIC SYSTEM
CONNECTED
PHOTOVOLTAIC SYSTEM DISCONNECT LOCATED
SOUTH SIDE OF THE BUILDING
03
L2 N
G
G L1
01
(E) MAIN
A100
TO UTILITY
GRID (UG)
L1 L2
N
(E) GROUNDING
ELECTRODE
GROUND
ROD
(E) MAIN SERVICE PANEL
120/240 V 1Ø, 3W
MAIN BUSS:100A
N
G
(E) UTILITY
METER
TO (E)
LOADS
NN L2 L1
EQUIPMENT ABOVE
LINE IS (N) NEW
EQUIPMENT BELOW
LINE IS (E) EXISTING
UNLESS OTHERWISE
NOTED.
BOVIET
BVM6612-350
SMA TS4-R-F
OPTIMIZERS
G
30A
04
F1-2 60А AC DISCONNECT
8 8
SMA
SB5.0-1SP-US-40-240V
4-A 4-B
G
02
NEW PV SYSTEM: 73.500 kWp
ENGINEER OF RECORD
DATE:05.25.2019
DESIGN BY:A.L.
CHECKED BY:M.M.
BELL BLACK
237 N 2ND E #100,
REXBURG, ID 83440
PAPER SIZE: 36" x 24" (ARCH D)
A B C D E F G H I J K L M N O
1
2
3
4
5
6
7
8
9
10
11
12
A B C D E F G H I J K L M N O
CONTRACTOR
BLUE MAX ENERGY & CONSULTING LLC
PHONE:2085698777
LIC. NO.:RCE-47820
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN
VIOLATION OF U.S. COPYRIGHT LAWS
AND WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
P
P
NO.DESCRIPTION DATE
PROJECT
REVISION / RELEASE
SHEET NUMBER:
SHEET TITLE:
01 SINGLE LINE DIAGRAM #2
NOT TO SCALE E-603.00
SINGLE LINE DIAGRAM #2
(SHEET 7 OF 19)
CONDUCTOR AND CONDUIT SCHEDULE W/ELECTRICAL CALCULATIONS
ID TYPICAL CONDUCTOR CONDUIT CURRENT-CARRYING CONDUCTORS
IN CONDUIT OCPD EGC TEMP. CORR. FACTOR CONDUIT FILL FACTOR CONT. CURRENT MAX. CURRENT (125%)BASE AMP.DERATED AMP.TERM. TEMP. RATING AMP. @ TERMINAL
01 2 10 AWG PV WIRE, COPPER FREE AIR 2 N/A 6 AWG BARE, COPPER 0.76 (54.9°C)1 11.98A 14.98A 55A 41.8A 75°C 50A
02 1 10 AWG THWN-2, COPPER 0.75" DIA PVC-40 4 N/A 10 AWG THWN-2, COPPER 0.76 (54.9°C)0.8 11.98A 14.98A 40A 24.32A 75°C 35A
03 1 8 AWG THWN-2, COPPER 0.75" DIA PVC-40 2 30A 10 AWG THWN-2, COPPER 0.96 (32.9°C)1 24A 30A 55A 52.8A 75°C 50A
04 1 6 AWG THWN-2, COPPER 0.75" DIA PVC-40 2 N/A 10 AWG THWN-2, COPPER 0.96 (32.9°C)1 24A 30A 75A 72A 75°C 65A
BILL OF MATERIALS
CATEGORY MAKE MODEL NUMBER REF QTY UNIT QTY/UNIT DESCRIPTION
MODULE BOVIET BVM6612-350 PM72-87 16 PIECES 1 BOVIET BVM6612-350 350W 72 CELLS, POLYCRYSTALLINE SILICON
INVERTER SMA SB 5.0-1SP-US-40 (240V)I4 1 PIECE 1 SMA SB 5.0-1SP-US-40 (240V) 5000W INVERTER
MODULE OPTIMIZER SMA TS4-R-F PO72-87 16 PIECES 1 SMA TS4-R-F OPTIMIZER (REQUIRED PART OF INVERTER'S DISTRIBUTED DC ARCHITECTURE)
DISCONNECT SQUARE D D222NRB SW1 1 PIECE 1 SQUARE D D222NRB, 2-POLE, 60A, 240VAC OR EQUIVALENT
WIRING GEN-10-AWG-PV-WIRE-CU WR1 TBD FEET 1 10 AWG PV WIRE, COPPER (POSITIVE AND NEGATIVE)
WIRING GEN-6-AWG-BARE-CU WR1 TBD FEET 1 6 AWG BARE, COPPER (GROUND)
WIRING GEN-10-AWG-THWN-2-CU-RD WR2 TBD FEET 1 10 AWG THWN-2, COPPER, RED (LINE 1)
WIRING GEN-10-AWG-THWN-2-CU-BLK WR2 TBD FEET 1 10 AWG THWN-2, COPPER, BLACK (LINE 2)
WIRING GEN-10-AWG-THWN-2-CU-GR WR2-4 TBD FEET 1 10 AWG THWN-2, COPPER, GREEN (GROUND)
WIRING GEN-8-AWG-THWN-2-CU-RD WR3 TBD FEET 1 8 AWG THWN-2, COPPER, RED (LINE 1)
WIRING GEN-8-AWG-THWN-2-CU-BLK WR3 TBD FEET 1 8 AWG THWN-2, COPPER, BLACK (LINE 2)
WIRING GEN-8-AWG-THWN-2-CU-WH WR3 TBD FEET 1 8 AWG THWN-2, COPPER, WHITE (NEUTRAL)
WIRING GEN-6-AWG-THWN-2-CU-RD WR4 TBD FEET 1 6 AWG THWN-2, COPPER, RED (LINE 1)
WIRING GEN-6-AWG-THWN-2-CU-BLK WR4 TBD FEET 1 6 AWG THWN-2, COPPER, BLACK (LINE 2)
WIRING GEN-6-AWG-THWN-2-CU-WH WR4 TBD FEET 1 6 AWG THWN-2, COPPER, WHITE (NEUTRAL)
WIREWAY GEN-PVC-40-0.75" DIA WW2-3 TBD FEET 1 PVC-40 CONDUIT, 0.75'' DIA
OCPD GENERIC MANUFACTURER GEN-FU-30A-240VAC F1-2 2 PIECES 1 FUSE, 30A, 240VAC
SYSTEM SUMMARY
MPPT #1 MPPT #2
MODULES IN SERIES 8 8
ARRAY VMP 308.8V 308.8V
ARRAY IMP 9.07A 9.07A
ARRAY VOC 376V 376V
ARRAY MAX VOC 440.3V 440.3V
ARRAY ISC 9.58A 9.58A
ARRAY STC POWER 5,600W
ARRAY PTC POWER 5,147W
MAX AC CURRENT 24A
MAX AC POWER 5,000W
DERATED (CEC) AC POWER 4,681W
DESIGN TEMPERATURES
ASHRAE EXTREME LOW -30.2°C (-22.4°F), SOURCE: REXBURG MADISON CO (43.83°; -111.88°)
ASHRAE 2% HIGH 32.9°C (91.2°F), SOURCE: REXBURG MADISON CO (43.83°; -111.88°)
INVERTERS
REF.QTY.MAKE AND MODEL AC VOLTAGE GROUND OCPD
RATING RATED POWER MAX OUTPUT
CURRENT
MAX INPUT
CURRENT MAX INPUT VOLTAGE CEC WEIGHTED
EFFICIENCY
I4 1 SMA SB 5.0-1SP-US-40 (240V)240V FLOATING 30A 5000W 24A 3X18A 600V 97.0%
MODULES
REF.QTY.MAKE AND MODEL PMAX PTC ISC IMP VOC VMP TEMP. COEFF. OF VOC FUSE RATING
PM72-87 16 BOVIET BVM6612-350 350W 321.7W 9.58A 9.07A 47V 38.6V -0.146V/°C (-0.31%/°C)15A
DISCONNECTS
REF.QTY.MAKE AND MODEL RATED CURRENT MAX RATED VOLTAGE
SW1 1 SQUARE D D222NRB OR EQUIV.60A 240VAC
OCPDS
REF.QTY.RATED CURRENT MAX VOLTAGE
F1-2 2 30A 240VAC
POWER OPTIMIZERS
REF.QTY.MODEL RATED INPUT POWER MAX OUTPUT CURRENT MAX INPUT ISC MAX DC VOLTAGE WEIGHTED EFFICIENCY
PO72-87 6 SMA TS4-R-F 475W 15A 12A 75V 100.0%
E-604.00
PLACARDS #2
(SHEET 8 OF 19)
NEW PV SYSTEM: 73.500 kWp
ENGINEER OF RECORD
DATE:05.25.2019
DESIGN BY:A.L.
CHECKED BY:M.M.
BELL BLACK
237 N 2ND E #100,
REXBURG, ID 83440
PAPER SIZE: 36" x 24" (ARCH D)
A B C D E F G H I J K L M N O
1
2
3
4
5
6
7
8
9
10
11
12
A B C D E F G H I J K L M N O
CONTRACTOR
BLUE MAX ENERGY & CONSULTING LLC
PHONE:2085698777
LIC. NO.:RCE-47820
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN
VIOLATION OF U.S. COPYRIGHT LAWS
AND WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
P
P
NO.DESCRIPTION DATE
PROJECT
REVISION / RELEASE
SHEET NUMBER:
SHEET TITLE:
FRONTPV ARRAY
BACK
!CAUTION!
POWER TO THIS BUILDING IS ALSO SUPPLIED
FROM ROOF MOUNTED SOLAR ARRAYS WITH
SAFETY DISCONNECTS AS SHOWN:
N
EW
S
MAIN DISTRIBUTION
UTILITY DISCONNECT
! WARNING !
DUAL POWER SOURCES.
SECOND SOURCE IS PV SYSTEM
LABEL 6
PHOTOVOLTAIC
AC DISCONNECT
OPERATING CURRENT: 24 A AC
OPERATING VOLTAGE: 240 V AC
LABEL 5
AT POINT OF INTERCONNECTION, MARKED
AT DISCONNECTING MEANS
[NEC 690.54]
! WARNING !
ELECTRIC SHOCK HAZARD
TERMINALS ON BOTH LINE AND LOAD SIDES
MAY BE ENERGIZED IN THE OPEN POSITION.
LABEL 3
AT EACH DISCONNECTING MEANS FOR
PHOTOVOLTAIC EQUIPMENT
[NEC 690.13 AND 690.15]
PHOTOVOLTAIC
AC DISCONNECT
WARNING: PHOTOVOLTAIC
POWER SOURCE
LABEL 11
AT EXPOSED RACEWAYS, CABLE TRAYS, AND OTHER WIRING
METHODS; SPACED AT MAXIMUM 10 FT SECTION OR WHERE
SEPARATED BY ENCLOSURES, WALLS, PARTITIONS, CEILINGS,
OR FLOORS.
[NEC 690.31(G)]
LETTERS AT LEAST 3/8 INCH; WHITE ON RED BACKGROUND;
REFLECTIVE
[IFC 605.11.1.1]
LABEL 12
AT EACH AC DISCONNECTING MEANS
[NEC 690.13(B)]
! CAUTION !
PHOTOVOLTAIC SYSTEM
CIRCUIT IS BACKFED
! WARNING !
POWER SOURCE OUTPUT
CONNECTION - DO NOT RELOCATE
THIS OVERCURRENT DEVISE
LABEL 13
AT POINT OF INTERCONNECTION
OVERCURRENT DEVICE
[NEC 705.12(B)(2)(3)(B)]
INTERACTIVE PHOTOVOLTAIC SYSTEM
CONNECTED
LABEL 8
AT UTILITY METER
[NEC 690.56(B)]
PHOTOVOLTAIC SYSTEM
EQUIPPED WITH RAPID
SHUTDOWN
LABEL 10
AT RAPID SHUTDOWN SWITCH
[NEC 690.56(C)].
LETTERS AT LEAST 3/8 INCH; WHITE ON RED
BACKGROUND; REFLECTIVE
[IFC 605.11.1.1]
LABEL 7
LABELING NOTES
1.1 LABELING REQUIREMENTS BASED ON THE 2017 NATIONAL ELECTRICAL CODE, INTERNATIONAL FIRE CODE 605.11, OSHA
STANDARD 1910.145, ANSI Z535
1.2 MATERIAL BASED ON THE REQUIREMENTS OF THE AUTHORITY HAVING JURISDICTION.
1.3 LABELS TO BE OF SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENT INVOLVED.
1.4 LABELS TO BE A MINIMUM LETTER HEIGHT OF 3/8” AND PERMANENTLY AFFIXED.
1.5 ALERTING WORDS TO BE COLOR CODED. “DANGER” WILL HAVE RED BACKGROUND; “WARNING” WILL HAVE ORANGE
BACKGROUND; “CAUTION” WILL HAVE YELLOW BACKGROUND. [ANSI Z535]
DIRECTORY
PERMANENT PLAQUE OR DIRECTORY PROVIDING THE
LOCATION OF THE SERVICE DISCONNECTING MEANS
AND THE PHOTOVOLTAIC SYSTEM DISCONNECTING
MEANS IF NOT IN THE SAME LOCATION
[NEC 690.56(B)]
PLAQUE
AT POINT OF INTERCONNECTION; LABEL, SUCH AS LABEL 5 OR LABEL 6 MUST IDENTIFY
PHOTOVOLTAIC SYSTEM
[NEC 705.12(B)(4)]
INTERACTIVE PHOTOVOLTAIC SYSTEM
CONNECTED
PHOTOVOLTAIC SYSTEM DISCONNECT LOCATED
SOUTH SIDE OF THE BUILDING
WHERE THE PV SYSTEMS ARE REMOTELY LOCATED FROM EACH
OTHER, A DIRECTORY IN ACCORDANCE WITH 705.10 SHALL BE
PROVIDED AT EACH PV SYSTEM DISCONNECTING MEANS.
PV SYSTEM EQUIPMENT AND DISCONNECTING MEANS SHALL NOT BE
INSTALLED IN BATHROOMS
[NEC 690.4(D),(E)]
SOLAR PV SYSTEM EQUIPPED
WITH RAPID SHUTDOWN
TURN RAPID SHUTDOWN
SWICH TO THE "OFF"
POSITION TO SHUTDOWN
PV SYSTEM AND REDUCE
SHOCK HAZARD IN ARRAY
SOLAR ELECTRIC
PV PANELS
LABEL 1
AT RAPID SHUTDOWN SYSTEM
[NEC 690.56(C)(1)(A)].
LABEL 3 INVERTER #4
AT EACH APPLICABLE DC DISCONNECTING
MEANS
[NEC 690.53]
OPERATING CURRENT: 9.07 A DC
OPERATING VOLTAGE:308.8 V DC
MAX SHORT CURRENT:9.58 A DC
MAX VOLTAGE:440.3 V DC
G
100А AC LOAD CENTER
120/240V, 1Ø, 3W
L1
N
L2
03
L2 N
G
G L1
01
SMA
SB 7.7-1SP-US-40-240V
(E) MAIN
A100
TO UTILITY
GRID (UG)
L1 L2
N
(E) GROUNDING
ELECTRODE
GROUND
ROD
(E) MAIN SERVICE PANEL
120/240 V 1Ø, 3W
MAIN BUSS:100A
N
G
(E) UTILITY
METER
TO (E)
LOADS
NN L2 L1
EQUIPMENT ABOVE
LINE IS (N) NEW
EQUIPMENT BELOW
LINE IS (E) EXISTING
UNLESS OTHERWISE
NOTED.
BOVIET
BVM6612-350
SMA TS4-R-F
OPTIMIZERS
G
100A
03
L2 N
G
G L1
01
SMA
SB 7.7-1SP-US-40-240V
04
05
F1-2
40A/2P
CB1
40A/2P
CB2
100А AC DISCONNECT
BOVIET
BVM6612-350
SMA TS4-R-F
OPTIMIZERS
8 8 8 8 8 7
5-A 5-B 5-C 6-A 6-B 7-C
G
02
G
02
NEW PV SYSTEM: 73.500 kWp
ENGINEER OF RECORD
DATE:05.25.2019
DESIGN BY:A.L.
CHECKED BY:M.M.
BELL BLACK
237 N 2ND E #100,
REXBURG, ID 83440
PAPER SIZE: 36" x 24" (ARCH D)
A B C D E F G H I J K L M N O
1
2
3
4
5
6
7
8
9
10
11
12
A B C D E F G H I J K L M N O
CONTRACTOR
BLUE MAX ENERGY & CONSULTING LLC
PHONE:2085698777
LIC. NO.:RCE-47820
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN
VIOLATION OF U.S. COPYRIGHT LAWS
AND WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
P
P
NO.DESCRIPTION DATE
PROJECT
REVISION / RELEASE
SHEET NUMBER:
SHEET TITLE:
01 SINGLE LINE DIAGRAM #3
NOT TO SCALE E-605.00
SINGLE LINE DIAGRAM #3
(SHEET 9 OF 19)
CONDUCTOR AND CONDUIT SCHEDULE W/ELECTRICAL CALCULATIONS
ID TYPICAL CONDUCTOR CONDUIT CURRENT-CARRYING CONDUCTORS
IN CONDUIT OCPD EGC TEMP. CORR. FACTOR CONDUIT FILL FACTOR CONT. CURRENT MAX. CURRENT (125%)BASE AMP.DERATED AMP.TERM. TEMP. RATING AMP. @ TERMINAL
01 6 10 AWG PV WIRE, COPPER FREE AIR 2 N/A 6 AWG BARE, COPPER 0.76 (54.9°C)1 11.98A 14.98A 55A 41.8A 75°C 50A
02 2 10 AWG THWN-2, COPPER 0.75" DIA PVC-40 6 N/A 10 AWG THWN-2, COPPER 0.76 (54.9°C)0.8 11.98A 14.98A 40A 24.32A 75°C 35A
03 2 8 AWG THWN-2, COPPER 0.75" DIA PVC-40 2 40A 10 AWG THWN-2, COPPER 0.96 (32.9°C)1 32A 40A 55A 52.8A 75°C 50A
04 1 3 AWG THWN-2, COPPER 1" DIA PVC-40 2 100A 8 AWG THWN-2, COPPER 0.96 (32.9°C)1 64A 80A 110A 105.6A 75°C 100A
05 1 3 AWG THWN-2, COPPER 1" DIA PVC-40 2 N/A 8 AWG THWN-2, COPPER 0.96 (32.9°C)1 64A 80A 110A 105.6A 75°C 100A
BILL OF MATERIALS
CATEGORY MAKE MODEL NUMBER REF QTY UNIT QTY/UNIT DESCRIPTION
MODULE BOVIET BVM6612-350 PM88-135 47 PIECES 1 BOVIET BVM6612-350 350W 72 CELLS, POLYCRYSTALLINE SILICON
INVERTER SMA SB 7.7-1SP-US-40 (240V)I5-6 2 PIECES 1 SMA SB 7.7-1SP-US-40 (240V) 7680W INVERTER
MODULE OPTIMIZER SMA TS4-R-F PO88-135 47 PIECES 1 SMA TS4-R-F OPTIMIZER (REQUIRED PART OF INVERTER'S DISTRIBUTED DC ARCHITECTURE)
DISCONNECT SQUARE D D223NRB SW1 1 PIECE 1 SQUARE D D223NRB, 2-POLE, 100A, 240VAC OR EQUIVALENT
WIRING GEN-10-AWG-PV-WIRE-CU WR1 TBD FEET 1 10 AWG PV WIRE, COPPER (POSITIVE AND NEGATIVE)
WIRING GEN-6-AWG-BARE-CU WR1 TBD FEET 1 6 AWG BARE, COPPER (GROUND)
WIRING GEN-10-AWG-THWN-2-CU-RD WR2 TBD FEET 1 10 AWG THWN-2, COPPER, RED (LINE 1)
WIRING GEN-10-AWG-THWN-2-CU-BLK WR2 TBD FEET 1 10 AWG THWN-2, COPPER, BLACK (LINE 2)
WIRING GEN-10-AWG-THWN-2-CU-GR WR2-3 TBD FEET 1 10 AWG THWN-2, COPPER, GREEN (GROUND)
WIRING GEN-8-AWG-THWN-2-CU-RD WR3 TBD FEET 1 8 AWG THWN-2, COPPER, RED (LINE 1)
WIRING GEN-8-AWG-THWN-2-CU-BLK WR3 TBD FEET 1 8 AWG THWN-2, COPPER, BLACK (LINE 2)
WIRING GEN-8-AWG-THWN-2-CU-WH WR3 TBD FEET 1 8 AWG THWN-2, COPPER, WHITE (NEUTRAL)
WIRING GEN-3-AWG-THWN-2-CU-RD WR4-5 TBD FEET 1 3 AWG THWN-2, COPPER, RED (LINE 1)
WIRING GEN-3-AWG-THWN-2-CU-BLK WR4-5 TBD FEET 1 3 AWG THWN-2, COPPER, BLACK (LINE 2)
WIRING GEN-3-AWG-THWN-2-CU-WH WR4-5 TBD FEET 1 3 AWG THWN-2, COPPER, WHITE (NEUTRAL)
WIRING GEN-8-AWG-THWN-2-CU-GR WR4-5 TBD FEET 1 8 AWG THWN-2, COPPER, GREEN (GROUND)
WIREWAY GEN-PVC-40-0.75" DIA WW2-3 TBD FEET 1 PVC-40 CONDUIT, 0.75'' DIA
WIREWAY GEN-PVC-40-1" DIA WW4-5 TBD FEET 1 PVC-40 CONDUIT, 1'' DIA
OCPD GENERIC MANUFACTURER GEN-FU-100A-240VAC F1-2 2 PIECES 1 FUSE, 100A, 240VAC
SYSTEM SUMMARY
INVERTER #5 INVERTER #6
MPPT #1 MPPT #2 MPPT #3 MPPT #1 MPPT #2 MPPT #3
MODULES IN SERIES 8 8 8 8 8 7
ARRAY VMP 308.8V 308.8V 308.8V 308.8V 308.8V 270.2V
ARRAY IMP 9.07A 9.07A 9.07A 9.07A 9.07A 9.07A
ARRAY VOC 376V 376V 376V 376V 376V 329V
ARRAY MAX VOC 440.3V 440.3V 440.3V 440.3V 440.3V 385.3V
ARRAY ISC 9.58A 9.58A 9.58A 9.58A 9.58A 9.58A
ARRAY STC POWER 8,400W 8,050W
ARRAY PTC POWER 7,721W 7,399W
MAX AC CURRENT 32A 32A
MAX AC POWER 7,680W 7,680W
ARRAY STC POWER 16,450W
ARRAY PTC POWER 15,120W
MAX AC CURRENT 64AW
MAX AC POWER 15,360W
DESIGN TEMPERATURES
ASHRAE EXTREME LOW -30.2°C (-22.4°F), SOURCE: REXBURG MADISON CO (43.83°; -111.88°)
ASHRAE 2% HIGH 32.9°C (91.2°F), SOURCE: REXBURG MADISON CO (43.83°; -111.88°)
INVERTERS
REF.QTY.MAKE AND MODEL AC VOLTAGE GROUND OCPD
RATING RATED POWER MAX OUTPUT
CURRENT
MAX INPUT
CURRENT MAX INPUT VOLTAGE CEC WEIGHTED
EFFICIENCY
I5-6 2 SMA SB 7.7-1SP-US-40 (240V)240V FLOATING 40A 7680W 32A 3X18A 600V 97.0%
MODULES
REF.QTY.MAKE AND MODEL PMAX PTC ISC IMP VOC VMP TEMP. COEFF. OF VOC FUSE RATING
PM88-135 47 BOVIET BVM6612-350 350W 321.7W 9.58A 9.07A 47V 38.6V -0.146V/°C (-0.31%/°C)15A
DISCONNECTS
REF.QTY.MAKE AND MODEL RATED CURRENT MAX RATED VOLTAGE
SW1 1 SQUARE D D223NRB OR EQUIV.100A 240VAC
OCPDS
REF.QTY.RATED CURRENT MAX VOLTAGE
F1-2 2 100A 240VAC
POWER OPTIMIZERS
REF.QTY.MODEL RATED INPUT POWER MAX OUTPUT CURRENT MAX INPUT ISC MAX DC VOLTAGE WEIGHTED EFFICIENCY
PO88-135 47 SMA TS4-R-F 475W 15A 12A 75V 100.0%
NEW PV SYSTEM: 73.500 kWp
ENGINEER OF RECORD
DATE:05.25.2019
DESIGN BY:A.L.
CHECKED BY:M.M.
BELL BLACK
237 N 2ND E #100,
REXBURG, ID 83440
PAPER SIZE: 36" x 24" (ARCH D)
A B C D E F G H I J K L M N O
1
2
3
4
5
6
7
8
9
10
11
12
A B C D E F G H I J K L M N O
CONTRACTOR
BLUE MAX ENERGY & CONSULTING LLC
PHONE:2085698777
LIC. NO.:RCE-47820
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN
VIOLATION OF U.S. COPYRIGHT LAWS
AND WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
P
P
NO.DESCRIPTION DATE
PROJECT
REVISION / RELEASE
SHEET NUMBER:
SHEET TITLE:
E-606.00
PLACARDS #3
(SHEET 10 OF 19)
FRONTPV ARRAY
BACK
!CAUTION!
POWER TO THIS BUILDING IS ALSO SUPPLIED
FROM ROOF MOUNTED SOLAR ARRAYS WITH
SAFETY DISCONNECTS AS SHOWN:
N
EW
S
MAIN DISTRIBUTION
UTILITY DISCONNECT
! WARNING !
DUAL POWER SOURCES.
SECOND SOURCE IS PV SYSTEM
LABEL 6
PHOTOVOLTAIC
AC DISCONNECT
OPERATING CURRENT: 64 A AC
OPERATING VOLTAGE: 240 V AC
LABEL 5
AT POINT OF INTERCONNECTION, MARKED
AT DISCONNECTING MEANS
[NEC 690.54]
! WARNING !
ELECTRIC SHOCK HAZARD
TERMINALS ON BOTH LINE AND LOAD SIDES
MAY BE ENERGIZED IN THE OPEN POSITION.
LABEL 3
AT EACH DISCONNECTING MEANS FOR
PHOTOVOLTAIC EQUIPMENT
[NEC 690.13 AND 690.15]
PHOTOVOLTAIC
AC DISCONNECT
WARNING: PHOTOVOLTAIC
POWER SOURCE
LABEL 11
AT EXPOSED RACEWAYS, CABLE TRAYS, AND OTHER WIRING
METHODS; SPACED AT MAXIMUM 10 FT SECTION OR WHERE
SEPARATED BY ENCLOSURES, WALLS, PARTITIONS, CEILINGS,
OR FLOORS.
[NEC 690.31(G)]
LETTERS AT LEAST 3/8 INCH; WHITE ON RED BACKGROUND;
REFLECTIVE
[IFC 605.11.1.1]
LABEL 12
AT EACH AC DISCONNECTING MEANS
[NEC 690.13(B)]
! CAUTION !
PHOTOVOLTAIC SYSTEM
CIRCUIT IS BACKFED
! WARNING !
POWER SOURCE OUTPUT
CONNECTION - DO NOT RELOCATE
THIS OVERCURRENT DEVISE
LABEL 13
AT POINT OF INTERCONNECTION
OVERCURRENT DEVICE
[NEC 705.12(B)(2)(3)(B)]
INTERACTIVE PHOTOVOLTAIC SYSTEM
CONNECTED
LABEL 8
AT UTILITY METER
[NEC 690.56(B)]
PHOTOVOLTAIC SYSTEM
EQUIPPED WITH RAPID
SHUTDOWN
LABEL 10
AT RAPID SHUTDOWN SWITCH
[NEC 690.56(C)].
LETTERS AT LEAST 3/8 INCH; WHITE ON RED
BACKGROUND; REFLECTIVE
[IFC 605.11.1.1]
LABEL 7
LABELING NOTES
1.1 LABELING REQUIREMENTS BASED ON THE 2017 NATIONAL ELECTRICAL CODE, INTERNATIONAL FIRE CODE 605.11, OSHA
STANDARD 1910.145, ANSI Z535
1.2 MATERIAL BASED ON THE REQUIREMENTS OF THE AUTHORITY HAVING JURISDICTION.
1.3 LABELS TO BE OF SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENT INVOLVED.
1.4 LABELS TO BE A MINIMUM LETTER HEIGHT OF 3/8” AND PERMANENTLY AFFIXED.
1.5 ALERTING WORDS TO BE COLOR CODED. “DANGER” WILL HAVE RED BACKGROUND; “WARNING” WILL HAVE ORANGE
BACKGROUND; “CAUTION” WILL HAVE YELLOW BACKGROUND. [ANSI Z535]
DIRECTORY
PERMANENT PLAQUE OR DIRECTORY PROVIDING THE
LOCATION OF THE SERVICE DISCONNECTING MEANS
AND THE PHOTOVOLTAIC SYSTEM DISCONNECTING
MEANS IF NOT IN THE SAME LOCATION
[NEC 690.56(B)]
PLAQUE
AT POINT OF INTERCONNECTION; LABEL, SUCH AS LABEL 5 OR LABEL 6 MUST IDENTIFY
PHOTOVOLTAIC SYSTEM
[NEC 705.12(B)(4)]
WHERE THE PV SYSTEMS ARE REMOTELY LOCATED FROM EACH
OTHER, A DIRECTORY IN ACCORDANCE WITH 705.10 SHALL BE
PROVIDED AT EACH PV SYSTEM DISCONNECTING MEANS.
PV SYSTEM EQUIPMENT AND DISCONNECTING MEANS SHALL NOT BE
INSTALLED IN BATHROOMS
[NEC 690.4(D),(E)]
SOLAR PV SYSTEM EQUIPPED
WITH RAPID SHUTDOWN
TURN RAPID SHUTDOWN
SWICH TO THE "OFF"
POSITION TO SHUTDOWN
PV SYSTEM AND REDUCE
SHOCK HAZARD IN ARRAY
SOLAR ELECTRIC
PV PANELS
LABEL 1
AT RAPID SHUTDOWN SYSTEM
[NEC 690.56(C)(1)(A)].
LABEL 3 INVERTER #5-6
AT EACH APPLICABLE DC DISCONNECTING
MEANS
[NEC 690.53]
OPERATING CURRENT: 9.07 A DC
OPERATING VOLTAGE:308.8 V DC
MAX SHORT CURRENT:9.58 A DC
MAX VOLTAGE:440.3 V DC
INTERACTIVE PHOTOVOLTAIC SYSTEM
CONNECTED
PHOTOVOLTAIC SYSTEM DISCONNECT LOCATED
SOUTH SIDE OF THE BUILDING
G
100А AC LOAD CENTER
120/240V, 1Ø, 3W
L1
N
L2
03
L2 N
G
G L1
01
SMA
SB 7.7-1SP-US-40-240V
(E) MAIN
A100
TO UTILITY
GRID (UG)
L1 L2
N
(E) GROUNDING
ELECTRODE
GROUND
ROD
(E) MAIN SERVICE PANEL
120/240 V 1Ø, 3W
MAIN BUSS:100A
N
G
(E) UTILITY
METER
TO (E)
LOADS
NN L2 L1
EQUIPMENT ABOVE
LINE IS (N) NEW
EQUIPMENT BELOW
LINE IS (E) EXISTING
UNLESS OTHERWISE
NOTED.
BOVIET
BVM6612-350
SMA TS4-R-F
OPTIMIZERS
G
100A
03
L2 N
G
G L1
01
SMA
SB 7.7-1SP-US-40-240V
04
05
F1-2
40A/2P
CB1
40A/2P
CB2
100А AC DISCONNECT
BOVIET
BVM6612-350
SMA TS4-R-F
OPTIMIZERS
8 8 7 8 7 7
8-A 8-B 8-C 9-A 9-B 9-C
G
02
G
02
NEW PV SYSTEM: 73.500 kWp
ENGINEER OF RECORD
DATE:05.25.2019
DESIGN BY:A.L.
CHECKED BY:M.M.
BELL BLACK
237 N 2ND E #100,
REXBURG, ID 83440
PAPER SIZE: 36" x 24" (ARCH D)
A B C D E F G H I J K L M N O
1
2
3
4
5
6
7
8
9
10
11
12
A B C D E F G H I J K L M N O
CONTRACTOR
BLUE MAX ENERGY & CONSULTING LLC
PHONE:2085698777
LIC. NO.:RCE-47820
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN
VIOLATION OF U.S. COPYRIGHT LAWS
AND WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
P
P
NO.DESCRIPTION DATE
PROJECT
REVISION / RELEASE
SHEET NUMBER:
SHEET TITLE:
01 SINGLE LINE DIAGRAM #4
NOT TO SCALE E-607.00
SINGLE LINE DIAGRAM #4
(SHEET 11 OF 19)
CONDUCTOR AND CONDUIT SCHEDULE W/ELECTRICAL CALCULATIONS
ID TYPICAL CONDUCTOR CONDUIT CURRENT-CARRYING CONDUCTORS
IN CONDUIT OCPD EGC TEMP. CORR. FACTOR CONDUIT FILL FACTOR CONT. CURRENT MAX. CURRENT (125%)BASE AMP.DERATED AMP.TERM. TEMP. RATING AMP. @ TERMINAL
01 6 10 AWG PV WIRE, COPPER FREE AIR 2 N/A 6 AWG BARE, COPPER 0.76 (54.9°C)1 11.98A 14.98A 55A 41.8A 75°C 50A
02 2 10 AWG THWN-2, COPPER 0.75" DIA PVC-40 6 N/A 10 AWG THWN-2, COPPER 0.76 (54.9°C)0.8 11.98A 14.98A 40A 24.32A 75°C 35A
03 2 8 AWG THWN-2, COPPER 0.75" DIA PVC-40 2 40A 10 AWG THWN-2, COPPER 0.96 (32.9°C)1 32A 40A 55A 52.8A 75°C 50A
04 1 3 AWG THWN-2, COPPER 1" DIA PVC-40 2 100A 8 AWG THWN-2, COPPER 0.96 (32.9°C)1 64A 80A 110A 105.6A 75°C 100A
05 1 3 AWG THWN-2, COPPER 1" DIA PVC-40 2 N/A 8 AWG THWN-2, COPPER 0.96 (32.9°C)1 64A 80A 110A 105.6A 75°C 100A
BILL OF MATERIALS
CATEGORY MAKE MODEL NUMBER REF QTY UNIT QTY/UNIT DESCRIPTION
MODULE BOVIET BVM6612-350 PM136-170 45 PIECES 1 BOVIET BVM6612-350 350W 72 CELLS, POLYCRYSTALLINE SILICON
INVERTER SMA SB 7.7-1SP-US-40 (240V)I7-8 2 PIECES 1 SMA SB 7.7-1SP-US-40 (240V) 7680W INVERTER
MODULE OPTIMIZER SMA TS4-R-F PO136-170 45 PIECES 1 SMA TS4-R-F OPTIMIZER (REQUIRED PART OF INVERTER'S DISTRIBUTED DC ARCHITECTURE)
DISCONNECT SQUARE D D223NRB SW1 1 PIECE 1 SQUARE D D223NRB, 2-POLE, 100A, 240VAC OR EQUIVALENT
WIRING GEN-10-AWG-PV-WIRE-CU WR1 TBD FEET 1 10 AWG PV WIRE, COPPER (POSITIVE AND NEGATIVE)
WIRING GEN-6-AWG-BARE-CU WR1 TBD FEET 1 6 AWG BARE, COPPER (GROUND)
WIRING GEN-10-AWG-THWN-2-CU-RD WR2 TBD FEET 1 10 AWG THWN-2, COPPER, RED (LINE 1)
WIRING GEN-10-AWG-THWN-2-CU-BLK WR2 TBD FEET 1 10 AWG THWN-2, COPPER, BLACK (LINE 2)
WIRING GEN-10-AWG-THWN-2-CU-GR WR2-3 TBD FEET 1 10 AWG THWN-2, COPPER, GREEN (GROUND)
WIRING GEN-8-AWG-THWN-2-CU-RD WR3 TBD FEET 1 8 AWG THWN-2, COPPER, RED (LINE 1)
WIRING GEN-8-AWG-THWN-2-CU-BLK WR3 TBD FEET 1 8 AWG THWN-2, COPPER, BLACK (LINE 2)
WIRING GEN-8-AWG-THWN-2-CU-WH WR3 TBD FEET 1 8 AWG THWN-2, COPPER, WHITE (NEUTRAL)
WIRING GEN-3-AWG-THWN-2-CU-RD WR4-5 TBD FEET 1 3 AWG THWN-2, COPPER, RED (LINE 1)
WIRING GEN-3-AWG-THWN-2-CU-BLK WR4-5 TBD FEET 1 3 AWG THWN-2, COPPER, BLACK (LINE 2)
WIRING GEN-3-AWG-THWN-2-CU-WH WR4-5 TBD FEET 1 3 AWG THWN-2, COPPER, WHITE (NEUTRAL)
WIRING GEN-8-AWG-THWN-2-CU-GR WR4-5 TBD FEET 1 8 AWG THWN-2, COPPER, GREEN (GROUND)
WIREWAY GEN-PVC-40-0.75" DIA WW2 TBD FEET 1 PVC-40 CONDUIT, 0.75'' DIA
WIREWAY GEN-PVC-40-1" DIA WW2-3 TBD FEET 1 PVC-40 CONDUIT, 1'' DIA
OCPD GENERIC MANUFACTURER GEN-FU-150A-240VAC F1-2 2 PIECES 1 FUSE, 150A, 240VAC
SYSTEM SUMMARY
INVERTER #7 INVERTER #8
MPPT #1 MPPT #2 MPPT #3 MPPT #1 MPPT #2 MPPT #3
MODULES IN SERIES 7 7 8 8 8 7
ARRAY VMP 270.2V 270.2V 308.8V 308.8V 308.8V 270.2V
ARRAY IMP 9.07A 9.07A 9.07A 9.07A 9.07A 9.07A
ARRAY VOC 329V 329V 376V 376V 376V 329V
ARRAY MAX VOC 385.3V 385.3V 440.3V 440.3V 440.3V 385.3V
ARRAY ISC 9.58A 9.58A 9.58A 9.58A 9.58A 9.58A
ARRAY STC POWER 7,700W 8,050W
ARRAY PTC POWER 7,077W 7,399W
MAX AC CURRENT 32A 32A
MAX AC POWER 7,680W 7,680W
ARRAY STC POWER 15,750W
ARRAY PTC POWER 14,476W
MAX AC CURRENT 64AW
MAX AC POWER 15,360W
DESIGN TEMPERATURES
ASHRAE EXTREME LOW -30.2°C (-22.4°F), SOURCE: REXBURG MADISON CO (43.83°; -111.88°)
ASHRAE 2% HIGH 32.9°C (91.2°F), SOURCE: REXBURG MADISON CO (43.83°; -111.88°)
INVERTERS
REF.QTY.MAKE AND MODEL AC VOLTAGE GROUND OCPD
RATING RATED POWER MAX OUTPUT
CURRENT
MAX INPUT
CURRENT MAX INPUT VOLTAGE CEC WEIGHTED
EFFICIENCY
I7-8 2 SMA SB 7.7-1SP-US-40 (240V)240V FLOATING 40A 7680W 32A 3X18A 600V 97.0%
MODULES
REF.QTY.MAKE AND MODEL PMAX PTC ISC IMP VOC VMP TEMP. COEFF. OF VOC FUSE RATING
PM136-170 45 BOVIET BVM6612-350 350W 321.7W 9.58A 9.07A 47V 38.6V -0.146V/°C (-0.31%/°C)15A
DISCONNECTS
REF.QTY.MAKE AND MODEL RATED CURRENT MAX RATED VOLTAGE
SW1 1 SQUARE D D223NRB OR EQUIV.100A 240VAC
OCPDS
REF.QTY.RATED CURRENT MAX VOLTAGE
F1-2 2 100A 240VAC
POWER OPTIMIZERS
REF.QTY.MODEL RATED INPUT POWER MAX OUTPUT CURRENT MAX INPUT ISC MAX DC VOLTAGE WEIGHTED EFFICIENCY
PO136-170 45 SMA TS4-R-F 475W 15A 12A 75V 100.0%
E-608.00
PLACARDS #4
(SHEET 12 OF 19)
NEW PV SYSTEM: 73.500 kWp
ENGINEER OF RECORD
DATE:05.25.2019
DESIGN BY:A.L.
CHECKED BY:M.M.
BELL BLACK
237 N 2ND E #100,
REXBURG, ID 83440
PAPER SIZE: 36" x 24" (ARCH D)
A B C D E F G H I J K L M N O
1
2
3
4
5
6
7
8
9
10
11
12
A B C D E F G H I J K L M N O
CONTRACTOR
BLUE MAX ENERGY & CONSULTING LLC
PHONE:2085698777
LIC. NO.:RCE-47820
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN
VIOLATION OF U.S. COPYRIGHT LAWS
AND WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
P
P
NO.DESCRIPTION DATE
PROJECT
REVISION / RELEASE
SHEET NUMBER:
SHEET TITLE:
FRONTPV ARRAY
BACK
!CAUTION!
POWER TO THIS BUILDING IS ALSO SUPPLIED
FROM ROOF MOUNTED SOLAR ARRAYS WITH
SAFETY DISCONNECTS AS SHOWN:
N
EW
S
MAIN DISTRIBUTION
UTILITY DISCONNECT
! WARNING !
DUAL POWER SOURCES.
SECOND SOURCE IS PV SYSTEM
LABEL 6
PHOTOVOLTAIC
AC DISCONNECT
OPERATING CURRENT: 64 A AC
OPERATING VOLTAGE: 240 V AC
LABEL 5
AT POINT OF INTERCONNECTION, MARKED
AT DISCONNECTING MEANS
[NEC 690.54]
! WARNING !
ELECTRIC SHOCK HAZARD
TERMINALS ON BOTH LINE AND LOAD SIDES
MAY BE ENERGIZED IN THE OPEN POSITION.
LABEL 3
AT EACH DISCONNECTING MEANS FOR
PHOTOVOLTAIC EQUIPMENT
[NEC 690.13 AND 690.15]
PHOTOVOLTAIC
AC DISCONNECT
WARNING: PHOTOVOLTAIC
POWER SOURCE
LABEL 11
AT EXPOSED RACEWAYS, CABLE TRAYS, AND OTHER WIRING
METHODS; SPACED AT MAXIMUM 10 FT SECTION OR WHERE
SEPARATED BY ENCLOSURES, WALLS, PARTITIONS, CEILINGS,
OR FLOORS.
[NEC 690.31(G)]
LETTERS AT LEAST 3/8 INCH; WHITE ON RED BACKGROUND;
REFLECTIVE
[IFC 605.11.1.1]
LABEL 12
AT EACH AC DISCONNECTING MEANS
[NEC 690.13(B)]
! CAUTION !
PHOTOVOLTAIC SYSTEM
CIRCUIT IS BACKFED
! WARNING !
POWER SOURCE OUTPUT
CONNECTION - DO NOT RELOCATE
THIS OVERCURRENT DEVISE
LABEL 13
AT POINT OF INTERCONNECTION
OVERCURRENT DEVICE
[NEC 705.12(B)(2)(3)(B)]
INTERACTIVE PHOTOVOLTAIC SYSTEM
CONNECTED
LABEL 8
AT UTILITY METER
[NEC 690.56(B)]
PHOTOVOLTAIC SYSTEM
EQUIPPED WITH RAPID
SHUTDOWN
LABEL 10
AT RAPID SHUTDOWN SWITCH
[NEC 690.56(C)].
LETTERS AT LEAST 3/8 INCH; WHITE ON RED
BACKGROUND; REFLECTIVE
[IFC 605.11.1.1]
LABEL 7
LABELING NOTES
1.1 LABELING REQUIREMENTS BASED ON THE 2017 NATIONAL ELECTRICAL CODE, INTERNATIONAL FIRE CODE 605.11, OSHA
STANDARD 1910.145, ANSI Z535
1.2 MATERIAL BASED ON THE REQUIREMENTS OF THE AUTHORITY HAVING JURISDICTION.
1.3 LABELS TO BE OF SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENT INVOLVED.
1.4 LABELS TO BE A MINIMUM LETTER HEIGHT OF 3/8” AND PERMANENTLY AFFIXED.
1.5 ALERTING WORDS TO BE COLOR CODED. “DANGER” WILL HAVE RED BACKGROUND; “WARNING” WILL HAVE ORANGE
BACKGROUND; “CAUTION” WILL HAVE YELLOW BACKGROUND. [ANSI Z535]
DIRECTORY
PERMANENT PLAQUE OR DIRECTORY PROVIDING THE
LOCATION OF THE SERVICE DISCONNECTING MEANS
AND THE PHOTOVOLTAIC SYSTEM DISCONNECTING
MEANS IF NOT IN THE SAME LOCATION
[NEC 690.56(B)]
PLAQUE
AT POINT OF INTERCONNECTION; LABEL, SUCH AS LABEL 5 OR LABEL 6 MUST IDENTIFY
PHOTOVOLTAIC SYSTEM
[NEC 705.12(B)(4)]
WHERE THE PV SYSTEMS ARE REMOTELY LOCATED FROM EACH
OTHER, A DIRECTORY IN ACCORDANCE WITH 705.10 SHALL BE
PROVIDED AT EACH PV SYSTEM DISCONNECTING MEANS.
PV SYSTEM EQUIPMENT AND DISCONNECTING MEANS SHALL NOT BE
INSTALLED IN BATHROOMS
[NEC 690.4(D),(E)]
SOLAR PV SYSTEM EQUIPPED
WITH RAPID SHUTDOWN
TURN RAPID SHUTDOWN
SWICH TO THE "OFF"
POSITION TO SHUTDOWN
PV SYSTEM AND REDUCE
SHOCK HAZARD IN ARRAY
SOLAR ELECTRIC
PV PANELS
LABEL 1
AT RAPID SHUTDOWN SYSTEM
[NEC 690.56(C)(1)(A)].
LABEL 3 INVERTER #7-8
AT EACH APPLICABLE DC DISCONNECTING
MEANS
[NEC 690.53]
OPERATING CURRENT: 9.07 A DC
OPERATING VOLTAGE:308.8 V DC
MAX SHORT CURRENT:9.58 A DC
MAX VOLTAGE:440.3 V DC
INTERACTIVE PHOTOVOLTAIC SYSTEM
CONNECTED
PHOTOVOLTAIC SYSTEM DISCONNECT LOCATED
SOUTH SIDE OF THE BUILDING
L2 N
G
G L1
01
SMA
SB3.0-1SP-US-40-240V
BOVIET
BVM6612-350
SMA TS4-R-F
OPTIMIZERS
8
02
(E) MAIN
A100
TO UTILITY
GRID (UG)
L1 L2
N
(E) GROUNDING
ELECTRODE
GROUND
ROD
(E) MAIN SERVICE PANEL
120/240 V 1Ø, 3W
MAIN BUSS:100A
N
G
(E) UTILITY
METER
TO (E)
LOADS
NN L2
L1
EQUIPMENT ABOVE
LINE IS (N) NEW
EQUIPMENT BELOW
LINE IS (E) EXISTING
UNLESS OTHERWISE
NOTED.
G
20A
04
F1-2 60А AC DISCONNECT
10-A
G
02
NEW PV SYSTEM: 73.500 kWp
ENGINEER OF RECORD
DATE:05.25.2019
DESIGN BY:A.L.
CHECKED BY:M.M.
BELL BLACK
237 N 2ND E #100,
REXBURG, ID 83440
PAPER SIZE: 36" x 24" (ARCH D)
A B C D E F G H I J K L M N O
1
2
3
4
5
6
7
8
9
10
11
12
A B C D E F G H I J K L M N O
CONTRACTOR
BLUE MAX ENERGY & CONSULTING LLC
PHONE:2085698777
LIC. NO.:RCE-47820
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN
VIOLATION OF U.S. COPYRIGHT LAWS
AND WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
P
P
NO.DESCRIPTION DATE
PROJECT
REVISION / RELEASE
SHEET NUMBER:
SHEET TITLE:
01 SINGLE LINE DIAGRAM #5
NOT TO SCALE E-609.00
SINGLE LINE DIAGRAM #5
(SHEET 13 OF 19)
CONDUCTOR AND CONDUIT SCHEDULE W/ELECTRICAL CALCULATIONS
ID TYPICAL CONDUCTOR CONDUIT CURRENT-CARRYING CONDUCTORS
IN CONDUIT OCPD EGC TEMP. CORR. FACTOR CONDUIT FILL FACTOR CONT. CURRENT MAX. CURRENT (125%)BASE AMP.DERATED AMP.TERM. TEMP. RATING AMP. @ TERMINAL
01 2 10 AWG PV WIRE, COPPER FREE AIR 2 N/A 6 AWG BARE, COPPER 0.76 (54.9°C)1 11.98A 14.98A 55A 41.8A 75°C 50A
02 1 10 AWG THWN-2, COPPER 0.75" DIA PVC-40 6 N/A 10 AWG THWN-2, COPPER 0.76 (54.9°C)0.8 11.98A 14.98A 40A 24.32A 75°C 35A
03 1 10 AWG THWN-2, COPPER 0.75" DIA PVC-40 2 20A 10 AWG THWN-2, COPPER 0.96 (32.9°C)1 12.5A 15.63A 40A 38.4A 75°C 35A
04 1 6 AWG THWN-2, COPPER 0.75" DIA PVC-40 2 N/A 10 AWG THWN-2, COPPER 0.96 (32.9°C)1 12.5A 15.63A 75A 72A 75°C 65A
BILL OF MATERIALS
CATEGORY MAKE MODEL NUMBER REF QTY UNIT QTY/UNIT DESCRIPTION
MODULE BOVIET BVM6612-350 PM179-186 8 PIECES 1 BOVIET BVM6612-350 350W 72 CELLS, POLYCRYSTALLINE SILICON
INVERTER SMA SB 3.0-1SP-US-40 (240V)I9 1 PIECE 1 SMA SB 3.0-1SP-US-40 (240V) 3000W INVERTER
MODULE OPTIMIZER SMA TS4-R-F PO179-186 8 PIECES 1 SMA TS4-R-F OPTIMIZER (REQUIRED PART OF INVERTER'S DISTRIBUTED DC ARCHITECTURE)
DISCONNECT SQUARE D D222NRB SW1 1 PIECE 1 SQUARE D D222NRB, 2-POLE, 60A, 240VAC OR EQUIVALENT
WIRING GEN-10-AWG-PV-WIRE-CU WR1 TBD FEET 1 10 AWG PV WIRE, COPPER (POSITIVE AND NEGATIVE)
WIRING GEN-6-AWG-BARE-CU WR1 TBD FEET 1 6 AWG BARE, COPPER (GROUND)
WIRING GEN-10-AWG-THWN-2-CU-RD WR2-3 TBD FEET 1 10 AWG THWN-2, COPPER, RED (LINE 1)
WIRING GEN-10-AWG-THWN-2-CU-BLK WR2-3 TBD FEET 1 10 AWG THWN-2, COPPER, BLACK (LINE 2)
WIRING GEN-10-AWG-THWN-2-CU-WH WR2-3 TBD FEET 1 10 AWG THWN-2, COPPER, WHITE (NEUTRAL)
WIRING GEN-6-AWG-THWN-2-CU-RD WR4 TBD FEET 1 6 AWG THWN-2, COPPER, RED (LINE 1)
WIRING GEN-6-AWG-THWN-2-CU-BLK WR4 TBD FEET 1 6 AWG THWN-2, COPPER, BLACK (LINE 2)
WIRING GEN-6-AWG-THWN-2-CU-WH WR4 TBD FEET 1 6 AWG THWN-2, COPPER, WHITE (NEUTRAL)
WIRING GEN-10-AWG-THWN-2-CU-GR WR2-4 TBD FEET 1 10 AWG THWN-2, COPPER, GREEN (GROUND)
WIREWAY GEN-PVC-40-0.75" DIA WW2-4 TBD FEET 1 PVC-40 CONDUIT, 0.75'' DIA
OCPD GENERIC MANUFACTURER GEN-FU-20A-240VAC F1-2 2 PIECES 1 FUSE, 20A, 240VAC
DESIGN TEMPERATURES
ASHRAE EXTREME LOW -30.2°C (-22.4°F), SOURCE: REXBURG MADISON CO (43.83°; -111.88°)
ASHRAE 2% HIGH 32.9°C (91.2°F), SOURCE: REXBURG MADISON CO (43.83°; -111.88°)
INVERTERS
REF.QTY.MAKE AND MODEL AC VOLTAGE GROUND OCPD
RATING RATED POWER MAX OUTPUT
CURRENT
MAX INPUT
CURRENT MAX INPUT VOLTAGE CEC WEIGHTED
EFFICIENCY
I9 1 SMA SB 3.0-1SP-US-40 (240V)240V FLOATING 20A 3000W 12.5A 2X18A 600V 96.5%
MODULES
REF.QTY.MAKE AND MODEL PMAX PTC ISC IMP VOC VMP TEMP. COEFF. OF VOC FUSE RATING
PM179-186 8 BOVIET BVM6612-350 350W 321.7W 9.58A 9.07A 47V 38.6V -0.146V/°C (-0.31%/°C)15A
DISCONNECTS
REF.QTY.MAKE AND MODEL RATED CURRENT MAX RATED VOLTAGE
SW1 1 SQUARE D D222NRB OR EQUIV.60A 240VAC
OCPDS
REF.QTY.RATED CURRENT MAX VOLTAGE
F1-2 2 20A 240VAC
SYSTEM SUMMARY
MPPT #1
MODULES IN SERIES 8
ARRAY VMP 308.8V
ARRAY IMP 9.07A
ARRAY VOC 376V
ARRAY MAX VOC 440.3V
ARRAY ISC 9.58A
ARRAY STC POWER 2,800W
ARRAY PTC POWER 2,574W
MAX AC CURRENT 12.5A
MAX AC POWER 3,000W
DERATED (CEC) AC POWER 2,484W POWER OPTIMIZERS
REF.QTY.MODEL RATED INPUT POWER MAX OUTPUT CURRENT MAX INPUT ISC MAX DC VOLTAGE WEIGHTED EFFICIENCY
PO179-186 8 SMA TS4-R-F 475W 15A 12A 75V 100.0%
NEW PV SYSTEM: 73.500 kWp
ENGINEER OF RECORD
DATE:05.25.2019
DESIGN BY:A.L.
CHECKED BY:M.M.
BELL BLACK
237 N 2ND E #100,
REXBURG, ID 83440
PAPER SIZE: 36" x 24" (ARCH D)
A B C D E F G H I J K L M N O
1
2
3
4
5
6
7
8
9
10
11
12
A B C D E F G H I J K L M N O
CONTRACTOR
BLUE MAX ENERGY & CONSULTING LLC
PHONE:2085698777
LIC. NO.:RCE-47820
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN
VIOLATION OF U.S. COPYRIGHT LAWS
AND WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
P
P
NO.DESCRIPTION DATE
PROJECT
REVISION / RELEASE
SHEET NUMBER:
SHEET TITLE:
E-610.00
PLACARDS #5
(SHEET 14 OF 19)
FRONTPV ARRAY
BACK
!CAUTION!
POWER TO THIS BUILDING IS ALSO SUPPLIED
FROM ROOF MOUNTED SOLAR ARRAYS WITH
SAFETY DISCONNECTS AS SHOWN:
N
EW
S
MAIN DISTRIBUTION
UTILITY DISCONNECT
! WARNING !
DUAL POWER SOURCES.
SECOND SOURCE IS PV SYSTEM
LABEL 6
PHOTOVOLTAIC
AC DISCONNECT
OPERATING CURRENT: 12.5 A AC
OPERATING VOLTAGE: 240 V AC
LABEL 5
AT POINT OF INTERCONNECTION, MARKED
AT DISCONNECTING MEANS
[NEC 690.54]
! WARNING !
ELECTRIC SHOCK HAZARD
TERMINALS ON BOTH LINE AND LOAD SIDES
MAY BE ENERGIZED IN THE OPEN POSITION.
LABEL 3
AT EACH DISCONNECTING MEANS FOR
PHOTOVOLTAIC EQUIPMENT
[NEC 690.13 AND 690.15]
PHOTOVOLTAIC
AC DISCONNECT
WARNING: PHOTOVOLTAIC
POWER SOURCE
LABEL 11
AT EXPOSED RACEWAYS, CABLE TRAYS, AND OTHER WIRING
METHODS; SPACED AT MAXIMUM 10 FT SECTION OR WHERE
SEPARATED BY ENCLOSURES, WALLS, PARTITIONS, CEILINGS,
OR FLOORS.
[NEC 690.31(G)]
LETTERS AT LEAST 3/8 INCH; WHITE ON RED BACKGROUND;
REFLECTIVE
[IFC 605.11.1.1]
LABEL 12
AT EACH AC DISCONNECTING MEANS
[NEC 690.13(B)]
! CAUTION !
PHOTOVOLTAIC SYSTEM
CIRCUIT IS BACKFED
! WARNING !
POWER SOURCE OUTPUT
CONNECTION - DO NOT RELOCATE
THIS OVERCURRENT DEVISE
LABEL 13
AT POINT OF INTERCONNECTION
OVERCURRENT DEVICE
[NEC 705.12(B)(2)(3)(B)]
INTERACTIVE PHOTOVOLTAIC SYSTEM
CONNECTED
LABEL 8
AT UTILITY METER
[NEC 690.56(B)]
PHOTOVOLTAIC SYSTEM
EQUIPPED WITH RAPID
SHUTDOWN
LABEL 10
AT RAPID SHUTDOWN SWITCH
[NEC 690.56(C)].
LETTERS AT LEAST 3/8 INCH; WHITE ON RED
BACKGROUND; REFLECTIVE
[IFC 605.11.1.1]
LABEL 7
LABELING NOTES
1.1 LABELING REQUIREMENTS BASED ON THE 2017 NATIONAL ELECTRICAL CODE, INTERNATIONAL FIRE CODE 605.11, OSHA
STANDARD 1910.145, ANSI Z535
1.2 MATERIAL BASED ON THE REQUIREMENTS OF THE AUTHORITY HAVING JURISDICTION.
1.3 LABELS TO BE OF SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENT INVOLVED.
1.4 LABELS TO BE A MINIMUM LETTER HEIGHT OF 3/8” AND PERMANENTLY AFFIXED.
1.5 ALERTING WORDS TO BE COLOR CODED. “DANGER” WILL HAVE RED BACKGROUND; “WARNING” WILL HAVE ORANGE
BACKGROUND; “CAUTION” WILL HAVE YELLOW BACKGROUND. [ANSI Z535]
DIRECTORY
PERMANENT PLAQUE OR DIRECTORY PROVIDING THE
LOCATION OF THE SERVICE DISCONNECTING MEANS
AND THE PHOTOVOLTAIC SYSTEM DISCONNECTING
MEANS IF NOT IN THE SAME LOCATION
[NEC 690.56(B)]
PLAQUE
AT POINT OF INTERCONNECTION; LABEL, SUCH AS LABEL 5 OR LABEL 6 MUST IDENTIFY
PHOTOVOLTAIC SYSTEM
[NEC 705.12(B)(4)]
WHERE THE PV SYSTEMS ARE REMOTELY LOCATED FROM EACH
OTHER, A DIRECTORY IN ACCORDANCE WITH 705.10 SHALL BE
PROVIDED AT EACH PV SYSTEM DISCONNECTING MEANS.
PV SYSTEM EQUIPMENT AND DISCONNECTING MEANS SHALL NOT BE
INSTALLED IN BATHROOMS
[NEC 690.4(D),(E)]
SOLAR PV SYSTEM EQUIPPED
WITH RAPID SHUTDOWN
TURN RAPID SHUTDOWN
SWICH TO THE "OFF"
POSITION TO SHUTDOWN
PV SYSTEM AND REDUCE
SHOCK HAZARD IN ARRAY
SOLAR ELECTRIC
PV PANELS
LABEL 1
AT RAPID SHUTDOWN SYSTEM
[NEC 690.56(C)(1)(A)].
LABEL 3 INVERTER #9
AT EACH APPLICABLE DC DISCONNECTING
MEANS
[NEC 690.53]
OPERATING CURRENT: 9.07 A DC
OPERATING VOLTAGE:308.8 V DC
MAX SHORT CURRENT:9.58 A DC
MAX VOLTAGE:440.3 V DC
INTERACTIVE PHOTOVOLTAIC SYSTEM
CONNECTED
PHOTOVOLTAIC SYSTEM DISCONNECT LOCATED
SOUTH SIDE OF THE BUILDING
03
(E) MAIN
A100
TO UTILITY
GRID (UG)
L1 L2
N
(E) GROUNDING
ELECTRODE
GROUND
ROD
(E) MAIN SERVICE PANEL
120/240 V 1Ø, 3W
MAIN BUSS:100A
N
G
(E) UTILITY
METER
TO (E)
LOADS
NN L2
L1
EQUIPMENT ABOVE
LINE IS (N) NEW
EQUIPMENT BELOW
LINE IS (E) EXISTING
UNLESS OTHERWISE
NOTED.
G
40A
04
F1-2 60А AC DISCONNECT
L2 N
G
G L1
01
SMA
SB7.7-1SP-US-40-240V
BOVIET
BVM6612-350
SMA TS4-R-F
OPTIMIZERS
8 8 7
11-A 11-B 11-C
G
02
NEW PV SYSTEM: 73.500 kWp
ENGINEER OF RECORD
DATE:05.25.2019
DESIGN BY:A.L.
CHECKED BY:M.M.
BELL BLACK
237 N 2ND E #100,
REXBURG, ID 83440
PAPER SIZE: 36" x 24" (ARCH D)
A B C D E F G H I J K L M N O
1
2
3
4
5
6
7
8
9
10
11
12
A B C D E F G H I J K L M N O
CONTRACTOR
BLUE MAX ENERGY & CONSULTING LLC
PHONE:2085698777
LIC. NO.:RCE-47820
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN
VIOLATION OF U.S. COPYRIGHT LAWS
AND WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
P
P
NO.DESCRIPTION DATE
PROJECT
REVISION / RELEASE
SHEET NUMBER:
SHEET TITLE:
01 SINGLE LINE DIAGRAM #6
NOT TO SCALE E-611.00
SINGLE LINE DIAGRAM #6
(SHEET 15 OF 19)
CONDUCTOR AND CONDUIT SCHEDULE W/ELECTRICAL CALCULATIONS
ID TYPICAL CONDUCTOR CONDUIT CURRENT-CARRYING CONDUCTORS
IN CONDUIT OCPD EGC TEMP. CORR. FACTOR CONDUIT FILL FACTOR CONT. CURRENT MAX. CURRENT (125%)BASE AMP.DERATED AMP.TERM. TEMP. RATING AMP. @ TERMINAL
01 3 10 AWG PV WIRE, COPPER FREE AIR 2 N/A 6 AWG BARE, COPPER 0.76 (54.9°C)1 11.98A 14.98A 55A 41.8A 75°C 50A
02 1 10 AWG THWN-2, COPPER 0.75" DIA PVC-40 6 N/A 10 AWG THWN-2, COPPER 0.76 (54.9°C)0.8 11.98A 14.98A 40A 24.32A 75°C 35A
03 1 8 AWG THWN-2, COPPER 0.75" DIA PVC-40 2 40A 10 AWG THWN-2, COPPER 0.96 (32.9°C)1 32A 40A 55 52.5A 75°C 45A
04 1 6 AWG THWN-2, COPPER 0.75" DIA PVC-40 2 N/A 10 AWG THWN-2, COPPER 0.96 (32.9°C)1 32A 40A 75A 72A 75°C 65A
BILL OF MATERIALS
CATEGORY MAKE MODEL NUMBER REF QTY UNIT QTY/UNIT DESCRIPTION
MODULE BOVIET BVM6612-350 PM187-210 23 PIECES 1 BOVIET BVM6612-350 350W 72 CELLS, POLYCRYSTALLINE SILICON
INVERTER SMA SB 7.7-1SP-US-40 (240V)I10 1 PIECE 1 SMA SB 7.7-1SP-US-40 (240V) 7680W INVERTER
MODULE OPTIMIZER SMA TS4-R-F PO187-210 23 PIECES 1 SMA TS4-R-F OPTIMIZER (REQUIRED PART OF INVERTER'S DISTRIBUTED DC ARCHITECTURE)
DISCONNECT SQUARE D D222NRB SW1 1 PIECE 1 SQUARE D D222NRB, 2-POLE, 60A, 240VAC OR EQUIVALENT
WIRING GEN-10-AWG-PV-WIRE-CU WR1 TBD FEET 1 10 AWG PV WIRE, COPPER (POSITIVE AND NEGATIVE)
WIRING GEN-6-AWG-BARE-CU WR1 TBD FEET 1 6 AWG BARE, COPPER (GROUND)
WIRING GEN-10-AWG-THWN-2-CU-RD WR2 TBD FEET 1 10 AWG THWN-2, COPPER, RED (LINE 1)
WIRING GEN-10-AWG-THWN-2-CU-BLK WR2 TBD FEET 1 10 AWG THWN-2, COPPER, BLACK (LINE 2)
WIRING GEN-8-AWG-THWN-2-CU-RD WR3 TBD FEET 1 8 AWG THWN-2, COPPER, RED (LINE 1)
WIRING GEN-8-AWG-THWN-2-CU-BLK WR3 TBD FEET 1 8 AWG THWN-2, COPPER, BLACK (LINE 2)
WIRING GEN-8-AWG-THWN-2-CU-WH WR3 TBD FEET 1 8 AWG THWN-2, COPPER, WHITE (NEUTRAL)
WIRING GEN-6-AWG-THWN-2-CU-RD WR4 TBD FEET 1 6 AWG THWN-2, COPPER, RED (LINE 1)
WIRING GEN-6-AWG-THWN-2-CU-BLK WR4 TBD FEET 1 6 AWG THWN-2, COPPER, BLACK (LINE 2)
WIRING GEN-6-AWG-THWN-2-CU-WH WR4 TBD FEET 1 6 AWG THWN-2, COPPER, WHITE (NEUTRAL)
WIRING GEN-10-AWG-THWN-2-CU-GR WR2-4 TBD FEET 1 10 AWG THWN-2, COPPER, GREEN (GROUND)
WIREWAY GEN-PVC-40-0.5" DIA WW2-3 TBD FEET 1 PVC-40 CONDUIT, 0.5'' DIA
WIREWAY GEN-PVC-40-0.75" DIA WW4 TBD FEET 1 PVC-40 CONDUIT, 0.75'' DIA
OCPD GENERIC MANUFACTURER GEN-FU-40A-240VAC F1-2 2 PIECES 1 FUSE, 40A, 240VAC
SYSTEM SUMMARY
MPPT #1 MPPT #2 MPPT #3
MODULES IN SERIES 8 8 7
ARRAY VMP 308.8V 308.8V 270.2V
ARRAY IMP 9.07A 9.07A 9.07A
ARRAY VOC 376V 376V 329V
ARRAY MAX VOC 440.3V 440.3V 385.3V
ARRAY ISC 9.58A 9.58A 9.58A
ARRAY STC POWER 8,050W
ARRAY PTC POWER 7,399W
MAX AC CURRENT 32A
MAX AC POWER 7,680W
DERATED (CEC) AC POWER 7,177W
DESIGN TEMPERATURES
ASHRAE EXTREME LOW -30.2°C (-22.4°F), SOURCE: REXBURG MADISON CO (43.83°; -111.88°)
ASHRAE 2% HIGH 32.9°C (91.2°F), SOURCE: REXBURG MADISON CO (43.83°; -111.88°)
INVERTERS
REF.QTY.MAKE AND MODEL AC VOLTAGE GROUND OCPD
RATING RATED POWER MAX OUTPUT
CURRENT
MAX INPUT
CURRENT MAX INPUT VOLTAGE CEC WEIGHTED
EFFICIENCY
I10 1 SMA SB 7.7-1SP-US-40 (240V)240V FLOATING 40A 7680W 32A 3X18A 600V 97.0%
MODULES
REF.QTY.MAKE AND MODEL PMAX PTC ISC IMP VOC VMP TEMP. COEFF. OF VOC FUSE RATING
PM187-210 23 BOVIET BVM6612-350 350W 321.7W 9.58A 9.07A 47V 38.6V -0.146V/°C (-0.31%/°C)15A
DISCONNECTS
REF.QTY.MAKE AND MODEL RATED CURRENT MAX RATED VOLTAGE
SW1 1 SQUARE D D222NRB OR EQUIV.60A 240VAC
OCPDS
REF.QTY.RATED CURRENT MAX VOLTAGE
F1-2 2 40A 240VAC
POWER OPTIMIZERS
REF.QTY.MODEL RATED INPUT POWER MAX OUTPUT CURRENT MAX INPUT ISC MAX DC VOLTAGE WEIGHTED EFFICIENCY
PO187-210 23 SMA TS4-R-F 475W 15A 12A 75V 100.0%
E-612.00
PLACARDS #6
(SHEET 16 OF 19)
NEW PV SYSTEM: 73.500 kWp
ENGINEER OF RECORD
DATE:05.25.2019
DESIGN BY:A.L.
CHECKED BY:M.M.
BELL BLACK
237 N 2ND E #100,
REXBURG, ID 83440
PAPER SIZE: 36" x 24" (ARCH D)
A B C D E F G H I J K L M N O
1
2
3
4
5
6
7
8
9
10
11
12
A B C D E F G H I J K L M N O
CONTRACTOR
BLUE MAX ENERGY & CONSULTING LLC
PHONE:2085698777
LIC. NO.:RCE-47820
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN
VIOLATION OF U.S. COPYRIGHT LAWS
AND WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
P
P
NO.DESCRIPTION DATE
PROJECT
REVISION / RELEASE
SHEET NUMBER:
SHEET TITLE:
FRONTPV ARRAY
BACK
!CAUTION!
POWER TO THIS BUILDING IS ALSO SUPPLIED
FROM ROOF MOUNTED SOLAR ARRAYS WITH
SAFETY DISCONNECTS AS SHOWN:
N
EW
S
MAIN DISTRIBUTION
UTILITY DISCONNECT
! WARNING !
DUAL POWER SOURCES.
SECOND SOURCE IS PV SYSTEM
LABEL 6
PHOTOVOLTAIC
AC DISCONNECT
OPERATING CURRENT: 32 A AC
OPERATING VOLTAGE: 240 V AC
LABEL 5
AT POINT OF INTERCONNECTION, MARKED
AT DISCONNECTING MEANS
[NEC 690.54]
! WARNING !
ELECTRIC SHOCK HAZARD
TERMINALS ON BOTH LINE AND LOAD SIDES
MAY BE ENERGIZED IN THE OPEN POSITION.
LABEL 3
AT EACH DISCONNECTING MEANS FOR
PHOTOVOLTAIC EQUIPMENT
[NEC 690.13 AND 690.15]
PHOTOVOLTAIC
AC DISCONNECT
WARNING: PHOTOVOLTAIC
POWER SOURCE
LABEL 11
AT EXPOSED RACEWAYS, CABLE TRAYS, AND OTHER WIRING
METHODS; SPACED AT MAXIMUM 10 FT SECTION OR WHERE
SEPARATED BY ENCLOSURES, WALLS, PARTITIONS, CEILINGS,
OR FLOORS.
[NEC 690.31(G)]
LETTERS AT LEAST 3/8 INCH; WHITE ON RED BACKGROUND;
REFLECTIVE
[IFC 605.11.1.1]
LABEL 12
AT EACH AC DISCONNECTING MEANS
[NEC 690.13(B)]
! CAUTION !
PHOTOVOLTAIC SYSTEM
CIRCUIT IS BACKFED
! WARNING !
POWER SOURCE OUTPUT
CONNECTION - DO NOT RELOCATE
THIS OVERCURRENT DEVISE
LABEL 13
AT POINT OF INTERCONNECTION
OVERCURRENT DEVICE
[NEC 705.12(B)(2)(3)(B)]
INTERACTIVE PHOTOVOLTAIC SYSTEM
CONNECTED
LABEL 8
AT UTILITY METER
[NEC 690.56(B)]
PHOTOVOLTAIC SYSTEM
EQUIPPED WITH RAPID
SHUTDOWN
LABEL 10
AT RAPID SHUTDOWN SWITCH
[NEC 690.56(C)].
LETTERS AT LEAST 3/8 INCH; WHITE ON RED
BACKGROUND; REFLECTIVE
[IFC 605.11.1.1]
LABEL 7
LABELING NOTES
1.1 LABELING REQUIREMENTS BASED ON THE 2017 NATIONAL ELECTRICAL CODE, INTERNATIONAL FIRE CODE 605.11, OSHA
STANDARD 1910.145, ANSI Z535
1.2 MATERIAL BASED ON THE REQUIREMENTS OF THE AUTHORITY HAVING JURISDICTION.
1.3 LABELS TO BE OF SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENT INVOLVED.
1.4 LABELS TO BE A MINIMUM LETTER HEIGHT OF 3/8” AND PERMANENTLY AFFIXED.
1.5 ALERTING WORDS TO BE COLOR CODED. “DANGER” WILL HAVE RED BACKGROUND; “WARNING” WILL HAVE ORANGE
BACKGROUND; “CAUTION” WILL HAVE YELLOW BACKGROUND. [ANSI Z535]
DIRECTORY
PERMANENT PLAQUE OR DIRECTORY PROVIDING THE
LOCATION OF THE SERVICE DISCONNECTING MEANS
AND THE PHOTOVOLTAIC SYSTEM DISCONNECTING
MEANS IF NOT IN THE SAME LOCATION
[NEC 690.56(B)]
PLAQUE
AT POINT OF INTERCONNECTION; LABEL, SUCH AS LABEL 5 OR LABEL 6 MUST IDENTIFY
PHOTOVOLTAIC SYSTEM
[NEC 705.12(B)(4)]
WHERE THE PV SYSTEMS ARE REMOTELY LOCATED FROM EACH
OTHER, A DIRECTORY IN ACCORDANCE WITH 705.10 SHALL BE
PROVIDED AT EACH PV SYSTEM DISCONNECTING MEANS.
PV SYSTEM EQUIPMENT AND DISCONNECTING MEANS SHALL NOT BE
INSTALLED IN BATHROOMS
[NEC 690.4(D),(E)]
SOLAR PV SYSTEM EQUIPPED
WITH RAPID SHUTDOWN
TURN RAPID SHUTDOWN
SWICH TO THE "OFF"
POSITION TO SHUTDOWN
PV SYSTEM AND REDUCE
SHOCK HAZARD IN ARRAY
SOLAR ELECTRIC
PV PANELS
LABEL 1
AT RAPID SHUTDOWN SYSTEM
[NEC 690.56(C)(1)(A)].
LABEL 3 INVERTER #10
AT EACH APPLICABLE DC DISCONNECTING
MEANS
[NEC 690.53]
OPERATING CURRENT: 9.07 A DC
OPERATING VOLTAGE:308.8 V DC
MAX SHORT CURRENT:9.58 A DC
MAX VOLTAGE:440.3 V DC
INTERACTIVE PHOTOVOLTAIC SYSTEM
CONNECTED
PHOTOVOLTAIC SYSTEM DISCONNECT LOCATED
SOUTH SIDE OF THE BUILDING
S-501
D5
20
11
121413151822
RO
O
F
S
L
O
P
E
910
10
6 21
7
2
S-501
D4
3
1
54
252423
8
27
SHEET KEYNOTES
1. ROOF MATERIAL: CORRUGATED METAL
2. ROOF STRUCTURE: STEEL FRAME
3. ATTACHMENT TYPE: S!5 STANDING SEAM
4. MODULE MANUFACTURER: BOVIET
5. MODULE MODEL: BVM6612-350
6. MODULE LENGTH: 77.01 IN.
7. MODULE WIDTH: 39.01 IN.
8. MODULE WEIGHT: 58.42 LBS.
9. SEE SHEET A-103 FOR DIMENSION(S)
10. MIN. FIRE OFFSET: 3'-0" FIRE ACCESS PATH
11. STEEL FRAME SPACING: NA IN. O.C.
12. STEEL FRAME SIZE: NA NOMINAL
13. LAG BOLT DIAMETER: NA IN.
14. LAG BOLT EMBEDMENT: NA IN.
15. TOTAL # OF ATTACHMENTS: 383
16. TOTAL AREA: 4381.06 SQ. FT.
17. TOTAL WEIGHT: 14230.4 LBS.
18. WEIGHT PER ATTACHMENT: 37.15 LBS.
19. DISTRIBUTED LOAD: 3.25 PSF.
20. MAX. HORIZONTAL STANDOFF: 78 IN.
21. MAX. VERTICAL STANDOFF:
LANDSCAPE: 26 IN., PORTRAIT: 43 IN.
22. STANDOFF STAGGERING: YES
23. RAIL MANUFACTURER (OR EQUIV.): SNAPNRACK
24. RAIL MODEL (OR EQUIVALENT): SERIES 100
25. RAIL WEIGHT: 0.75 PLF.
26. MAX. STEEL FRAME SPAN: NA FT.
27. MODULE CLEARANCE: 3 IN. MIN., 6 IN. MAX.
NEW PV SYSTEM: 73.500 kWp
ENGINEER OF RECORD
DATE:05.25.2019
DESIGN BY:A.L.
CHECKED BY:M.M.
BELL BLACK
237 N 2ND E #100,
REXBURG, ID 83440
PAPER SIZE: 36" x 24" (ARCH D)
A B C D E F G H I J K L M N O
1
2
3
4
5
6
7
8
9
10
11
12
A B C D E F G H I J K L M N O
CONTRACTOR
BLUE MAX ENERGY & CONSULTING LLC
PHONE:2085698777
LIC. NO.:RCE-47820
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN
VIOLATION OF U.S. COPYRIGHT LAWS
AND WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
P
P
NO.DESCRIPTION DATE
PROJECT
REVISION / RELEASE
SHEET NUMBER:
SHEET TITLE:
S-501.00
ASSEMBLY DETAILS
(SHEET 17 OF 19)D4 DETAIL (TRANSVERSE)
NOT TO SCALE D5 DETAIL (LONGITUDINAL)
NOT TO SCALE
D1 RACKING DETAIL (TRANSVERSE)
NOT TO SCALE
D3 RACKING DETAIL (TOP)
NOT TO SCALE
D2 RACKING DETAIL (LONGITUDINAL)
NOT TO SCALE
NEW PV SYSTEM: 73.500 kWp
ENGINEER OF RECORD
DATE:05.25.2019
DESIGN BY:A.L.
CHECKED BY:M.M.
BELL BLACK
237 N 2ND E #100,
REXBURG, ID 83440
PAPER SIZE: 36" x 24" (ARCH D)
A B C D E F G H I J K L M N O
1
2
3
4
5
6
7
8
9
10
11
12
A B C D E F G H I J K L M N O
CONTRACTOR
BLUE MAX ENERGY & CONSULTING LLC
PHONE:2085698777
LIC. NO.:RCE-47820
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN
VIOLATION OF U.S. COPYRIGHT LAWS
AND WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
P
P
NO.DESCRIPTION DATE
PROJECT
REVISION / RELEASE
SHEET NUMBER:
SHEET TITLE:
R-001.00
RESOURCE DOCUMENTS
(SHEET 18 OF 19)
NEW PV SYSTEM: 73.500 kWp
ENGINEER OF RECORD
DATE:05.25.2019
DESIGN BY:A.L.
CHECKED BY:M.M.
BELL BLACK
237 N 2ND E #100,
REXBURG, ID 83440
PAPER SIZE: 36" x 24" (ARCH D)
A B C D E F G H I J K L M N O
1
2
3
4
5
6
7
8
9
10
11
12
A B C D E F G H I J K L M N O
CONTRACTOR
BLUE MAX ENERGY & CONSULTING LLC
PHONE:2085698777
LIC. NO.:RCE-47820
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN
VIOLATION OF U.S. COPYRIGHT LAWS
AND WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
P
P
NO.DESCRIPTION DATE
PROJECT
REVISION / RELEASE
SHEET NUMBER:
SHEET TITLE:
R-002.00
RESOURCE DOCUMENTS
(SHEET 10 OF 19)