HomeMy WebLinkAboutINSPECTION SUMMARY - 14-00370 - 26 N Center St - Madison Fire Station - Addition & RemodelPermit
Inspection
Summary
Permit Status of (Open) as of Report Date: 06/26/2019 3:27 pm
Permit Details Permit Number: 14-00370
26 N Center St - Madison Fire Station - Addition & Remodel
26 N Center St
Commercial Addition
Permit Issued Date: 12/17/2014
Permit Inspection Statistics
44Total Inspections Completed:
25Total Inspections Passed:
Inspection Pass Rate: 56.82%
Permit Inspection History *Refer to Individual Inspection Report for more Details
Building Inspection Type
12/17/2014PassQuinton OwensCommercial Footing Inspection
12/19/2014PassQuinton OwensFoundation Inspection
Interior foundation for new walls. Only about 6" tall.Inspector Comments:
03/20/2015PassQuinton OwensCommercial Framing/Structure Inspection
Lower metal decking under raised 2nd level floor approved. Support framing not
done yet.
Inspector Comments:
04/23/2015FailQuinton OwensCommercial Framing/Structure Inspection
2nd floor roof sheathing (excluding taller roof). Missing nailing on square sheet in
SW corner, and one row on north side, and just north of SE mech. curb. Spacing
of nails in field are too far on east half.
Inspector Comments:
04/27/2015FailQuinton OwensCommercial Framing/Structure Inspection
Sheathing re-inspect for 2nd floor lower roof. Missed nailing done in SW corner
and north side (west half). Nail spacing still to be corrected (started nailing
during inspection).
Inspector Comments:
04/28/2015PassQuinton OwensSheeting
2nd floor lower roof.Inspector Comments:
04/28/2015N/AQuinton OwensCommercial Framing/Structure Inspection
Framing between double metal floor decks for 2nd floor. (covered before
inspected)
Inspector Comments:
05/19/2015FailQuinton OwensCommercial Framing/Structure Inspection
Windows in sleeping rooms do not meet egress. 2x4 spans supporting ceiling to
be double checked. Ducts block continuation of fire barrier in NE corner of
kitchen. Ducts penetrating Fire barrier does not have fire dampers. Stairs to roof
on north side not done yet. Fire rating will need to be maintained at larger PVC
pipe at top plate of fire barrier. Thermal barrier for foam insulation in attic
required per 2603.4.1.6. Fireblocking/caulking not completed yet.
Inspector Comments:
Page 1 of 4
(Continued)
Permit Details Permit Number: 14-00370
26 N Center St - Madison Fire Station - Addition & Remodel
26 N Center St
Commercial Addition
Permit Status of (Open) as of Report Date: 06/26/2019 3:27 pm
Permit
Inspection
Summary
06/22/2015FailQuinton OwensCommercial Framing/Structure Inspection
Thermal barrier at ceiling or directly on foam insulation (verify requirements with
ESR report).
Properly firecaulk PVC pipe penetrations in fire barrier. Large vertical PVC pipe
section in wall membrane also to be fire rated.
Complete duct over NW sleeping room to be all 26 ga metal duct
Complete fire barrier around metal duct on north end.
Top stair riser going to lower roof is too high compared to other risers (accessory
for R2 - will allow for residential stair limits; tread depth already at 10").
Inspector Comments:
06/22/2015FailQuinton OwensCommercial Sheetrock/Drywall Inspection
Missing some screws on ceiling in shower room 218.
Partial approval to tape already hung drywall, but NOT to cover framing
corrections until approved.
Inspector Comments:
06/23/2015FailQuinton OwensCommercial Sheetrock/Drywall Inspection
Second floor drywall approved for taping.
Thermal protection separating foam insulation to interior of building required.
Inspector Comments:
06/30/2015PassQuinton OwensCommercial Insulation Inspection
Exterior insulation on first floor approved
(Framing inspection not approved on 1st floor).
Inspector Comments:
07/09/2015FailQuinton OwensCommercial Sheetrock/Drywall Inspection
Fire barrier incomplete on main level and horizontal assembly rating not
completed. Drywall approved only at non-rated partitions.
Inspector Comments:
07/16/2015FailQuinton OwensCommercial Sheetrock/Drywall Inspection
Fire barrier on main level between R and B occupancies is completed. Rated
ceiling attached to wood joists still not approved. Main level walls approved for
taping. Partial drywall only approved.
Fire rate penetrations under residential area and have inspected.
Inspector Comments:
07/16/2015FailQuinton OwensCommercial Framing/Structure Inspection
Lower level framing approved. Fire rated separation with single layer drywall at
wood joists is not approved. Add second layer or find listed one hour assembly
that matches the installed floor/ceiling.
Inspector Comments:
07/21/2015FailQuinton OwensCommercial Insulation Inspection
Thermal barrier using mineral wool insulation over foam insulation completed on
west and south walls and above sleeping rooms of upper level. Approved to hang
ceiling in these areas.
Foam insulation above north rooms adjoining kitchen area is intended to receive
ignition barrier of intumescent paint as discussed. (Call for Inspection when
done)
Inspector Comments:
Page 2 of 4
(Continued)
Permit Details Permit Number: 14-00370
26 N Center St - Madison Fire Station - Addition & Remodel
26 N Center St
Commercial Addition
Permit Status of (Open) as of Report Date: 06/26/2019 3:27 pm
Permit
Inspection
Summary
07/27/2015PassQuinton OwensCommercial Sheetrock/Drywall Inspection
Upper ceiling and perimeter wall inspection for rated penetrations in rooms
connected to south garage only.
Approved to hang lower rated ceiling in these rooms.
Penetrations also fire caulked in other area under 2nd level floor joists. Approved
to proceed with rating the main level ceiling as discussed with double layer rated
drywall in east storage room and intumescent paint in remaining area of wood
joists.
Inspector Comments:
08/07/2015PassQuinton OwensCommercial Sheetrock/Drywall Inspection
Fire rated ceiling under R2 portion of buildig: 2nd layer added where available.
Rest of rated ceiling painted with intumescent paint as submitted.
Inspector Comments:
08/07/2015PassQuinton OwensCommercial Insulation Inspection
Foam insulation over pantries sprayed with intumescent paint for an ignition
barrier as discussed.
Inspector Comments:
10/02/2015FailQuinton OwensCommercial Building Final
Fire rate penetrations under sinks in kitchen area, in wall behind laundry
(including around dryer vents), penetrations from ambulance bay in fire rated
wall, and electrical penetration in wall above access panel in bathroom. Access to
inspect fire caulking at top of column and south wall on main floor rated ceiling.
None of the glass in the fire rated doors is fire rated. Fire rate gaps between stair
enclosure and area under stairs. Ceiling radiation dampers missing in vents
penetrating rated ceiling in rooms off of fire truck bay. Finish fire rating ceiling
penetrations in shop room. Fire door frames are not labeled as per 716.5.7.4
(laundry room door frame has no label).
Note: Exhaust vent cap missing on roof of ambulance bay.
Inspector Comments:
10/20/2015FailQuinton OwensCommercial Building Final
Fire rated glazing for rated doors is on order. Suppose to arrive in a week. Call
for re-inspect as soon as they are installed.
OK for 2 week temporary C.O.
Inspector Comments:
10/20/2015PassQuinton OwensCommercial Sheetrock/Drywall Inspection
Gap between rated ceiling and south block wall and around column penetration
between restroom and hall has been fire caulked.
Inspector Comments:
10/20/2015PassQuinton OwensCommercial Framing/Structure Inspection
11/06/2015FailQuinton OwensCommercial Building Final
Missed fire rated glazing in west door going into fire truck bay.Inspector Comments:
01/29/2016PassQuinton OwensCommercial Building Final
No re-inspection called in.
Inspected on later visit to fire station. Fire rating installed in west door to south
garage done.
Inspector Comments:
Page 3 of 4
(Continued)
Permit Details Permit Number: 14-00370
26 N Center St - Madison Fire Station - Addition & Remodel
26 N Center St
Commercial Addition
Permit Status of (Open) as of Report Date: 06/26/2019 3:27 pm
Permit
Inspection
Summary
Electrical Inspection Type
05/13/2015PassBret StoddardCOM-A, COM-R, COM-T Electrical Rough-in
05/26/2015PassBret StoddardCOM-A, COM-R, COM-T Electrical Rough-in
06/25/2015PassBret StoddardCOM-A, COM-R, COM-T Electrical Rough-in
08/04/2015PassBret StoddardCOM-A, COM-R, COM-T Electrical Rough-in
09/15/2015FailBret StoddardCOM, COM-A, COM-R, and COM-T Electrical Final Inspection
10/05/2015FailBret StoddardCOM, COM-A, COM-R, and COM-T Electrical Final Inspection
02/05/2016PassBret StoddardCOM, COM-A, COM-R, and COM-T Electrical Final Inspection
Fire Inspection Type
06/08/2015PassDale PickeringFire Sprinkler Rough-in
Rough-in for 2nd floor only, PassInspector Comments:
06/25/2015PassDale PickeringFire Sprinkler Rough-in
09/03/2015PassDale PickeringFire Sprinkler Final Inspection
09/15/2015FailBret StoddardFire Alarm Final Inspection
10/05/2015PassBret StoddardFire Alarm Final Inspection
Mechanical Inspection Type
05/21/2015FailDon AllenHVAC Rough-in
need to finish the roughinInspector Comments:
09/25/2015PassDon AllenHVAC Final Inspection
good for the c/oInspector Comments:
Plumbing Inspection Type
11/25/2014PassDon AllenPlumbing Underground Inspection
05/06/2015PassDon AllenPlumbing Rough-in
THE PLUMBING ROUGHIN ON THE 2ND FLOOR PASSED TEST AND CAN BE
COVERED
Inspector Comments:
05/21/2015PassDon AllenPlumbing Rough-in
09/25/2015PassDon AllenPlumbing Final Inspection
good for the c/oInspector Comments:
Page 4 of 4