Loading...
HomeMy WebLinkAboutINSPECTION REPORT ELECTRICAL - 14-00291 - BYU-I Underground Duct Bank - ElectricalCommunity Development Department Phone (208)359-3020 Inspection Hotline: (208)372-2344 INSPECTION REPORT Inspection Type Building Type Inspection ELECTRICAL BLD-ELEC ELEC-UNGD Permit Number: Address: 488 S 2nd E Project: 14-00291 BYU-I Underground Duct Bank - Electrical Inspection Date 9/4/2014 Inspection Result: PASS D ESCRIPTIO N CO MMEN TS STATUS Labeling and listing-installation of materials and equipment, direct burial, etc. 90.7, 110.3(B) COMPLETED Stub up approved for protection against physical damage sch. 80 PVC, RMC, IMC, RTRC-XW or equivalent 300.5(D)(4) COMPLETED Ferrous metal equipment must have corrosion protection, elbows wrapped, etc. 300.6(A) COMPLETED Backfill material must not contain large rocks, cinders, paving materials, etc. 300.5(F) COMPLETED Approved for backfill To place red concrete from Kimball building 35' out to transformer and 1/1/2" to vault. COMPLETED Inspector: Bret Stoddard