HomeMy WebLinkAboutINSPECTION SUMMARY - 16-00266 - 1360 S 12 W - Motel 6Permit
Inspection
Summary
Permit Status of (Open) as of Report Date: 05/29/2019 11:43 am
Permit Details Permit Number: 16-00266
1360 S 12 W - Motel 6
1360 S 12 W
Building - Commercial
Permit Issued Date:
Permit Inspection Statistics
40Total Inspections Completed:
28Total Inspections Passed:
Inspection Pass Rate: 70.00%
Permit Inspection History *Refer to Individual Inspection Report for more Details
04/20/2017PARTPASSJoel GrayPublic Works Final Inspection
Items needing addressed:
1.Swales on south and west sides not completed. (To be completed by June 1)
2.Swale in center of parking lot filled with gravel and shorter than proposed
resulting in less storage volume. Resolved on site 8 ft depth to allow for rock fill.)
3.Setbacks not followed on 12th West.
4.Street sign damaged. (car slid off road)
5.Has agreement for road widening and sidewalks been signed by both parties?
6.What is black pipe on East end for? (French drain to be installed by June 1)
7.Trash enclosure detail is for 2 dumpsters not 1.( Try 1 but acknowledge
possible need for 2 and will increase if necessary)
8.Gravel on North side? (May not happen)
9.Right of way needs to be deeded to City on 2000 S and 12th W. and 15 ft
utility easements along perimeter of parcel.
Inspector Comments:
10/11/2017PassNatalie PowellPlanning and Zoning Final Inspection
Building Inspection Type
05/03/2016FailQuinton OwensCommercial Footing Inspection
05/04/2016PassQuinton OwensCommercial Footing Inspection
Ufer installed in SE corner.Inspector Comments:
05/05/2016PassTed DyeFoundation Inspection
West halfInspector Comments:
Ufer ground rebar added inside foundation wall (ufer bar in footing ended up
outside foundation wall).
Inspector Comments:
05/06/2016PassQuinton OwensFoundation Inspection
Inspection for East half of building foundation.Inspector Comments:
05/17/2016PassQuinton OwensCommercial Insulation Inspection
Foundation insulationInspector Comments:
06/10/2016PassQuinton OwensCommercial Footing Inspection
Partial footing:
Slab with interior footings under corridor only.
Inspector Comments:
Page 1 of 4
(Continued)
Permit Details Permit Number: 16-00266
1360 S 12 W - Motel 6
1360 S 12 W
Building - Commercial
Permit Status of (Open) as of Report Date: 05/29/2019 11:43 am
Permit
Inspection
Summary
06/16/2016PassTed DyeFoundation Inspection
Shearwall footing/foundation on east end of building, last floor pour.Inspector Comments:
08/26/2016PassQuinton OwensCommercial Sheetrock/Drywall Inspection
Pre-rock behind tubs only for rated walls.Inspector Comments:
09/22/2016FailTed DyeCommercial Framing/Structure Inspection
09/22/2016FailTed DyeSheeting
Those spots that missed having the sheeting nailed to the studs is marked with
green paint, some inside and some outside.
Inspector Comments:
09/29/2016PassTed DyeSheeting
Corrections made.
OK to cover exterior
Inspector Comments:
10/26/2016PassTed DyeCommercial Framing/Structure Inspection
Truss and draft stop inspections only.
All other framing inspection items to be inspected at a later date.
Draft stops were good.
Inspector Comments:
11/02/2016FailTed DyeResidential Framing/Structure Inspection
In the wall framing section that failed, the measurement for the wall separating
the differant flight of stairs , should have read " from the front of the tread
measured vertically 42" to the top of the wall".
Inspector Comments:
11/28/2016FailQuinton OwensCommercial Insulation Inspection
11/23/16: Penetrations in top & bottom plates in non-rated walls are sealed with
"fire block" foam and are not fire rated as instructed previously. Only the two
walls inside sleeping units require fire caulking at top and bottom plate
penetrations upstairs and top plates on first floor.
Exterior walls and corridor are approved for cover. Call for inspection of fire
caulking.
Inspector Comments:
12/12/2016PARTPASSBret StoddardCommercial Sheetrock/Drywall Inspection
12/16/2016PassQuinton OwensCommercial Sheetrock/Drywall Inspection
1st level only.Inspector Comments:
Fire rate penetrations in all separation walls where they occur. Plastic pipes have
intumescent fire caulk INSIDE 3/8" annular space between pipe and drywall.
Inspector Comments:
Self closing device required on doors to main laundry room.
Inspector Comments:
Fire rate PVC pipe penetrations in ceilings of storage rooms about halfway down
the corridor (caulk to be INSIDE 3/8" annular space).
Inspector Comments:
Parking lot to be marked as soon as weather permits. Handicap parking as per
IBC & A117.1-2009.
Inspector Comments:
Page 2 of 4
(Continued)
Permit Details Permit Number: 16-00266
1360 S 12 W - Motel 6
1360 S 12 W
Building - Commercial
Permit Status of (Open) as of Report Date: 05/29/2019 11:43 am
Permit
Inspection
Summary
Address numbers to be posted where easily seen from street.
Inspector Comments:
Exterior finishes shall be done at front entrance prior to public access.
Inspector Comments:
Fix smoke detector as identified with Ted on first floor.
Inspector Comments:
03/30/2017FailQuinton OwensCommercial Building Final
Vertical grab bars missing at water closets (required). Vertical grab bars at
non-roll in showers (pending decision).
Inspector Comments:
Electrical Inspection Type
10/13/2016PassBret StoddardCommercial Electrical Rough-in
10/18/2016PassBret StoddardCommercial Electrical Rough-in
10/20/2016PassBret StoddardCOM & MFR Electrical Service Inspection
03/29/2017PARTPASSBret StoddardCommerical Electrical Final Inspection
03/30/2017PassBret StoddardCommerical Electrical Final Inspection
Fire Inspection Type
09/21/2016FailDale PickeringFire Sprinkler Rough-in
10/18/2016PassBret StoddardFire Alarm Rough-in
03/29/2017FailBret StoddardFire Alarm Final Inspection
03/31/2017PassQuinton OwensFire Alarm Final Inspection
03/31/2017PassDale PickeringFire Sprinkler Hydro
Chief David Davis inspected on 3/31/2017. Passed.Inspector Comments:
04/18/2017PassDale PickeringFire Sprinkler Rough-in
04/18/2017PassDale PickeringFire Department Final Inspection
10/05/2017PassDale PickeringFire Department Final Inspection
Mechanical Inspection Type
10/06/2016PassDon AllenHVAC Rough-in
There was no mechanical contractor on the job. The exhaust fans in the
bathrooms and the cloths dryer vents was ran by somebody. The mechanical
rough in was approved by the building official. Might have to install damper see
building code
Inspector Comments:
04/17/2017PassDon AllenHVAC Final Inspection
Page 3 of 4
(Continued)
Permit Details Permit Number: 16-00266
1360 S 12 W - Motel 6
1360 S 12 W
Building - Commercial
Permit Status of (Open) as of Report Date: 05/29/2019 11:43 am
Permit
Inspection
Summary
Plumbing Inspection Type
05/27/2016PassDon AllenPlumbing Water
06/07/2016PassDon AllenPlumbing Underground Inspection
06/09/2016PassDon AllenPlumbing Sewer
08/12/2016PassDon AllenPlumbing Rough-in
The d w v looks good will need to see the pressure on the water lines when
finished
Inspector Comments:
03/29/2017PARTPASSDon AllenPlumbing Final Inspection
Need to support the water
need vent covers on combustion air in water heater room
screws need to be taken out of the dryer duct
Inspector Comments:
04/17/2017PassDon AllenPlumbing Final Inspection
Inspections Required
Sidewalk Inspection
Commercial Building Final
Public Works Final Inspection