HomeMy WebLinkAboutINSPECTION SUMMARY - 16-00568 - 167 W Main St - Medicine Shoppe - RemodelPermit
Inspection
Summary
Permit Status of (Open) as of Report Date: 05/22/2019 9:02 am
Permit Details Permit Number: 16-00568
167 W Main St - Medicine Shoppe - Remodel
167 W Main St
Commercial Remodel
Permit Issued Date: 09/01/2016
Permit Inspection Statistics
7Total Inspections Completed:
6Total Inspections Passed:
Inspection Pass Rate: 85.71%
Permit Inspection History *Refer to Individual Inspection Report for more Details
Building Inspection Type
No Framing inspection requested or done. Only non-structural partition walls
were framed as part of remodel. However, framing inspections are required even
for no-structural walls. Approved to continue with finishing drywall, but no
approval is given on framing. Be sure to always check with inspector before
covering and avoid possibly removing drywall to allow for inspection.
Inspector Comments:
10/10/2016PassQuinton OwensCommercial Sheetrock/Drywall Inspection
No mechanical or plumbing inspections done. Approved to proceed on drywall
ONLY if these either do not apply (plumbing?) or are being done after
drywall (mech?).
Inspector Comments:
Ceiling grid is missing perimeter wires tied to grid 8" max. from wall on all sides
(Seismic D zone requirement). Attaching clip to wall with screw(s) is optional.
Inspector Comments:
12/15/2016FailQuinton OwensCommercial Building Final
Fire rate penetrations behind drinking fountain and in SW corner at top of wall in
mechanical room.
Inspector Comments:
12/21/2016PassQuinton OwensCommercial Building Final
Electrical Inspection Type
10/04/2016PassBret StoddardCommercial Electrical Rough-in
12/15/2016PassBret StoddardElectrical Final Inspection COM-A,R,T
Mechanical Inspection Type
12/16/2016PassDon AllenHVAC Final Inspection
Good for the C/OInspector Comments:
Plumbing Inspection Type
12/16/2016PassDon AllenPlumbing Final Inspection
Good for the C/OInspector Comments: