HomeMy WebLinkAboutINSPECTION SUMMARY - 16-00521 - 220 Ricks Ave - Freddy'sPermit
Inspection
Summary
Permit Status of (Open) as of Report Date: 05/21/2019 11:58 am
Permit Details Permit Number: 16-00521
220 Ricks Ave - Freddy's
220 Ricks Ave
Building - Commercial
Permit Issued Date: 09/29/2016
Permit Inspection Statistics
39Total Inspections Completed:
25Total Inspections Passed:
Inspection Pass Rate: 64.10%
Permit Inspection History *Refer to Individual Inspection Report for more Details
05/31/2017FailNatalie PowellPlanning and Zoning Final Inspection
05/31/2017FailJoel GrayPublic Works Final Inspection
ADA requirements for cross slope are not met at each approach location. (Cross
slope exceeds 2%). Sidewalk inspection prior to placement was not completed.
Inspector Comments:
12/19/2017PassNatalie PowellPlanning and Zoning Final Inspection
Building Inspection Type
10/17/2016PassQuinton OwensCommercial Footing Inspection
10/21/2016PassQuinton OwensFoundation Inspection
Foundation walls. Piers per detail 12/S8.1 do not have #5 vertical rebar.
Correction was made by adding 2 additional #4 bars per engineer. Submit RFI
documentation.
Inspector Comments:
10/31/2016PassTed DyeCommercial Footing Inspection
Footing inspected; Center spot footing, 2 footings for columns on east side of
main building and footings in north-east corner.
Inspector Comments:
11/02/2016PassTed DyeCommercial Footing Inspection
11/30/2016PassTed DyeCommercial Framing/Structure Inspection
Cricket framing and hold downs inspected ONLY.
All other framing will be done at a later date.
Inspector Comments:
11/30/2016PassTed DyeSheeting
Roof Sheeting inspection only.Inspector Comments:
12/13/2016FailQuinton OwensSheeting
Multiple locations found missing nails just on north wall or nail spacing too far.
Request was made on site to postpone rest of inspection so framers can double
check their work before re-inspection.
Inspector Comments:
12/21/2016FailTed DyeSheeting
Those spots that the sheeting missed being nailed to the
studs have been marked with pink paint.
Finish nailing then call for a reinspection.
Inspector Comments:
Page 1 of 3
(Continued)
Permit Details Permit Number: 16-00521
220 Ricks Ave - Freddy's
220 Ricks Ave
Building - Commercial
Permit Status of (Open) as of Report Date: 05/21/2019 11:58 am
Permit
Inspection
Summary
12/21/2016PassTed DyeCommercial Framing/Structure Inspection
Check furdowns for fire blocking.
We will check for the fire blocking when the insulation inspection is done.
Inspector Comments:
12/27/2016PassTed DyeSheeting
Door and window perimeters not sealed yet.
Multiple narrow stud cavities not insulated on north, east, and south walls.
Inspector Comments:
12/27/2016FailQuinton OwensCommercial Insulation Inspection
Be sure there is enough grab bar backing up to 54" from corner on side wall and
42" from corner on back wall in restrooms.
Inspector Comments:
Insulation added to empty cavities in exterior walls.Inspector Comments:
12/29/2016PARTPASSQuinton OwensCommercial Insulation Inspection
Window & door perimeters not yet sealed. Call for inspection when ready.Inspector Comments:
01/04/2017PassTed DyeCommercial Sheetrock/Drywall Inspection
02/09/2017PassQuinton OwensSuspending Ceiling Inspection
Ceiling grid installation is approved, but mechanical is not completed. Electrical
inspection is scheduled and must also be approved.
Inspector Comments:
02/17/2017FailQuinton OwensCommercial Building Final
Approved for Temporary C.O. Egress & Life safety items inspected to allow
employee training. Work is still in progress and full inspection will be needed
before opening.
Inspector Comments:
02/24/2017FailQuinton OwensCommercial Building Final
Approved for temporary C.O. onlyInspector Comments:
05/31/2017FailJoel GraySidewalk Inspection
12/19/2017PassJoel GraySidewalk Inspection
Electrical Inspection Type
11/01/2016PassBret StoddardElectrical Underground Inspection
12/21/2016PARTPASSBret StoddardCommercial Electrical Rough-in
01/20/2017PassBret StoddardCOM & MFR Electrical Service Inspection
02/10/2017PassBret StoddardCommercial Electrical Rough-in
02/16/2017PARTPASSBret StoddardCommerical Electrical Final Inspection
02/23/2017PassBret StoddardCommerical Electrical Final Inspection
Page 2 of 3
(Continued)
Permit Details Permit Number: 16-00521
220 Ricks Ave - Freddy's
220 Ricks Ave
Building - Commercial
Permit Status of (Open) as of Report Date: 05/21/2019 11:58 am
Permit
Inspection
Summary
Fire Inspection Type
02/21/2017PassDale PickeringFire Department Inspection
Commercial Hood Inspection. Inspection verified proper function of 3 hoods
(fryer,grill, grill) with manual activation by fusible link and pull station. All
functions including gas and electrical shunt, make up air, auto ventilation, hood
ventilation operated properly. DP
Inspector Comments:
07/10/2017PassDale PickeringFire Department Final Inspection
Mechanical Inspection Type
12/21/2016PassDon AllenHVAC Rough-in
01/17/2017FailDon AllenHVAC Rough-in
02/06/2017FailDon AllenHVAC Rough-in
Need to finish sealing the duct workInspector Comments:
02/14/2017PARTPASSQuinton OwensHVAC Rough-in
Supply vent still to be added to office (after ceiling grid adjustment). Connect
return air vents. Other supply vents in kitchen area are ready to install grills and
the repair needed at bottom of grease duct was completed.
Inspector Comments:
02/17/2017PassDon AllenHVAC Rough-in
Good for the Temp C/OInspector Comments:
02/24/2017PassDon AllenHVAC Final Inspection
Plumbing Inspection Type
10/24/2016PassDon AllenPlumbing Sewer
Good to cover the sewer lineInspector Comments:
10/28/2016PassDon AllenPlumbing Underground Inspection
Good to cover the plumbing underground
When draining the underground it backed up in to the test manhole. Need to find
out why it wont drain and fix before the final.
Inspector Comments:
12/21/2016PassDon AllenPlumbing Rough-in
02/13/2017PassDon AllenPlumbing Final Inspection
Good for the C/OInspector Comments:
Inspections Required
Public Works Final Inspection
Page 3 of 3