HomeMy WebLinkAboutFS PLANS - 19-00161 - 425 S 3rd W - Sugar City Bldg 4 - FA/FS InstallF R E F R E 7 4 7 3 F R E D R W D R W S 1 0 1 S 1 0 2 S103 03 7 6 0 7 This system as shown oncompany print nodatedforatcontract nois designed to discharge at a rate ofa maximum area ofwhen supplied with water at a rate ofOccupancy classification:Commodity classification:Maximum storage height:Storage arrangement:Number of heads flowing:System Type:Maximum velocity:Flow from In-Rack sprinklers:Flow from Overhead sprinklers:Flow from Inside Hoses:Flow from Outside Hoses:Other fixed flows:Total flow in system piping:Additional flow at/beyond source:Total of all flows:Calculation results for Design Areagpm/ft² (L/min/m²) of floor area over -Surplus Pressure at Source:Pressure Required at Source:Pressure Available at Source:atat the base of the riser.Hose stream allowance ofis included in the above.12ND FLOOR PHOENIX FIRE PROTECTION08/01/2018SOUTH FORK VILLA425 S 3RD W18-2300.05428 ft²68.2 gpm56.9 psiLIGHT 3Wet15.02 ft/s0 gpm68.2 gpm0 gpm0 gpm0 gpm68.2 gpm100 gpm168.2 gpm 56.9 psi69.8 psi12.9 psiDesign Area Density:Calculations usingMethodOccupancy Classification:Design AreaSystemAdditional Outside Hose:Design Area Size:Notes:1Wet2ND FLOOR DemandHazen-WilliamsLIGHT 0.05100428 M A N U F A C T U R E D T R U S S E S N T S F D C D E T A I L