HomeMy WebLinkAboutR3531 4.4K HSWModel F1Res Series Glass Bulb Residential Sprinklers For NFPA 13, NFPA 13R, and NFPA 13D Applications Features • cULus Listed Residential Sprinklers • Available in pendent and horizontal sidewall orientations • Decorative finishes available, including recessed escutch- eons and conical concealed cover plates Product Description Model F1Res Series sprinklers are residential sprinklers with a 3 mm glass bulb operating element. A variety of K-Factors as well as recessed and conical concealed options are available as detailed in this Bulletin. The F1Res Series sprinklers are specially engineered for fast thermal response to meet the requirements of UL 1626. They are intended for installation in accordance with NFPA 13, 13R, and 13D. Application The Model F1Res Series sprinklers cULus Listed Residential sprinklers are intended for use in accordance with NFPA 13, NFPA 13R, or NFPA 13D. The Model F1Res residential sprin- klers are cULus Listed for use in residential occupancies and residential portions of any occupancy, where permitted by NFPA 13, NFPA 13R, or NFPA 13D. For NFPA 13R and NFPA 13D applications, the design flow and pressure shall not be less than the minimum flow and pressure specified in the Listed Bulletin 135 October 2018 www.reliablesprinkler.com Residential Sprinkler Summary Sprinkler Model Sprinkler Identification Number (SIN) Orientation K-Factor gpm/psi1/2 (lpm/bar1/2) Thread Size NPT or ISO7-1 Installation Options Max. Coverage Area ft x ft (m x m) F1Res30 R3511 Pendent 3.0 (43)1/2 Pendent or Recessed 16 x16 (4.9 x 4.9) F1Res49 R3516 Pendent 4.9 (71)1/2 Pendent or Recessed 20 x 20 (6.1 x 6.1) F1Res58 R3513 Pendent 5.8 (84)1/2 Pendent or Recessed 20 x 20 (6.1 x 6.1) F1Res76 R7618 Pendent 7.6 (109)3/4 Pendent or Recessed 20 x 20 (6.1 x 6.1) F1Res30 CCP R3511 Pendent 3.0 (43)1/2 Conical Concealed or Recessed 14 x 14 (4.3 x 4.3) F1Res49 CCP R3516 Pendent 4.9 (71)1/2 Conical Concealed or Recessed 20 x 20 (6.1 x 6.1) F1Res58 CCP R3513 Pendent 5.8 (84)1/2 Conical Concealed or Recessed 20 x 20 (6.1 x 6.1) F1Res76 CCP R7618 Pendent 7.6 (109)3/4 Conical Concealed or Recessed 20 x 20 (6.1 x 6.1) F1Res44 HSW R3531 Horizontal Sidewall 4.4 (63)1/2 Recessed 16 x 20 (4.9 x 6.1) F1Res44 SWC R3531 Horizontal Sidewall 4.4 (63)1/2 Conical Concealed 16 x 20 (4.9 x 6.1) F1Res58 HSW R3533 Horizontal Sidewall 5.8 (84)1/2 Recessed 16 x 20 (4.9 x 6.1) F1Res 58 HSWX RA3533 Horizontal Sidewall 5.8 (84)1/2 Recessed 14 x 26 (4.3 x 7.9) Table A Design Criteria tables in this Bulletin. For NFPA 13 applications, the design density shall be a minimum of 0.1 gpm/sf (4.1 mm/ min), but in no case shall the flow and pressure be less than the minimum flow and pressure specified in the Listed Design Criteria tables in this bulletin. Model F1Res Series sprinklers are listed for use in wet systems only. cULus Listed Model F1Res30 Residential Pendent Sprinkler Components and Installation Dimensions Figure 1 * Model FV escutcheons are not for use in positively pressurized ceiling plenums. Technical Specifications Style: Pendent and Recessed Pendent Threads: 1/2” NPT or ISO7-1R1/2 Nominal K-Factor: 3.0 (43 metric) Max. Working Pressure: 175 psi (12 bar) Material Specifications Thermal Sensor: 3 mm glass bulb Sprinkler Frame: Brass Alloy Button: Copper Alloy Sealing Assembly: Nickel Alloy with PTFE Load Screw: Bronze Alloy Deflector: Bronze Alloy Finishes (See Table N) Temperature Ratings 155°F (68°C) 175°F (79°C) Recessed Escutcheons F2 Recessed FV Recessed* Sprinkler Wrenches Model W2 Model GFR2 (Recessed) Model F1Res30 Residential Pendent Sprinkler & Models F2 & FV Escutcheon SIN R3511 Bulletin 135 October 2018 Page 2 of 15 www.reliablesprinkler.com Minimum Flow and Residual Pressure in Wet Pipe Systems(1) Maximum Coverage Area(2) ft. x ft.(m x m) Flow gpm (l/min) Pressure psi (bar) Deflector to Ceiling Distance 12 x 12 (3.7 x 3.7)8 (30)7.0 (0.48) 1 to 4 inches (25 to 100 mm) 14 x 14 (4.3 x 4.3)10 (38)11.0 (0.76) 15 x 15 (4.6 x 4.6)12 (45)16.0 (1.1) 16 x 16 (4.9 x 4.9)13 (49)18.8 (1.3) Table BModel F1Res30 Residential Pendent Sprinkler Hydraulic Design Criteria Notes: 1. For NFPA 13 installations the flow per sprinkler must be the greater of: (1) the flow listed in the table above or (2) the flow required to achieve a minimum design density of 0.1 gpm/sq ft over the design area of the sprinkler. 2. For coverage area dimensions less than those listed above, use the minimum required flow for the next larger max. coverage area listed. Model F1Res49 Residential Pendent Sprinkler Components and Installation Dimensions Figure 2 Model F1Res49 Residential Sprinkler & Models F1, F2, & FV Escutcheons SIN R3516 Technical Specifications Style: Pendent and Recessed Pendent Threads: 1/2” NPT or ISO7-1R1/2 Nominal K-Factor: 4.9 (71 metric) Max. Working Pressure: 175 psi (12 bar) Material Specifications Thermal Sensor: 3 mm glass-bulb Sprinkler Frame: Brass Alloy Button: Copper Alloy Sealing Assembly: Nickel Alloy with PTFE Load Screw: Bronze Alloy Deflector: Bronze Alloy Finishes (See Table N) Temperature Ratings 155°F (68°C) 175°F (79°C) Recessed Escutcheons F1 Recessed F2 Recessed FV Recessed* Sprinkler Wrenches Model W2 Model GFR2 (Recessed) Bulletin 135 October 2018 Page 3 of 15 www.reliablesprinkler.com Minimum Flow and Residual Pressure in Wet Pipe Systems(1) Maximum Coverage Area(2) ft. x ft. (m x m) Flow gpm (l/min) Pressure psi (bar) Deflector to Ceiling Distance 12 x 12 (3.7 x 3.7)13 (49)7.0 (0.48) 1 to 4 inches (25 to 100 mm) 14 x 14 (4.3 x 4.3)13 (49)7.0 (0.48) 16 x 16 (4.9 x 4.9)13 (49)7.0 (0.48) 18 x 18 (5.5 x 5.5)17 (64)12.0 (0.83) 20 x 20 (6.1 x 6.1)20 (76)16.7 (1.15) 12 x 12 (3.7 x 3.7)15 (57)9.4 (0.65) 4 to 8 inches (100 to 200 mm) 14 x 14 (4.3 x 4.3)16 (61)10.7 (0.74) 16 x 16 (4.9 x 4.9)17 (64)12.0 (0.83) 18 x 18 (5.5 x 5.5)19 (72)15.0 (1.03) 20 x 20 (6.1 x 6.1)22 (83)20.2 (1.39) Model F1Res49 Residential Pendent Sprinkler Hydraulic Design Criteria Table C Notes: 1. For NFPA 13 installations the flow per sprinkler must be the greater of: (1) the flow listed in the table above or (2) the flow required to achieve a minimum design density of 0.1 gpm/sq ft over the design area of the sprinkler. 2. For coverage area dimensions less than those listed above, use the minimum required flow for the next larger max. coverage area listed. * Model FV escutcheons are not for use in positively pressurized ceiling plenums. Model F1Res58 Residential Pendent Sprinkler & F1, F2, & FV Recessed Escutcheons SIN R3513 Technical Specifications Style: Pendent and Recessed Pendent Threads: 1/2” NPT or ISO7-1R1/2 Nominal K-Factor: 5.8 (84 metric) Max. Working Pressure: 175 psi (12 bar) Material Specifications Thermal Sensor: 3 mm glass bulb Sprinkler Frame: Brass Alloy Button: Copper Alloy Sealing Assembly: Nickel Alloy with PTFE Load Screw: Bronze Alloy Deflector: Bronze Alloy Finishes (See Table N) Temperature Ratings 155°F (68°C) 175°F (79°C) Recessed Escutcheons F1 Recessed F2 Recessed FV Recessed* Sprinkler Wrenches Model W2 Model GFR2 (Recessed) * Model FV escutcheons are not for use in positively pressurized ceiling plenums. Model F1Res58 Residential Pendent Sprinkler Components and Installation Dimensions Figure 3 Bulletin 135 October 2018 Page 4 of 15 www.reliablesprinkler.com Minimum Flow and Residual Pressure in Wet Pipe Systems(1) Maximum Coverage Area(2) ft. x ft. (m x m) Flow gpm (l/min) Pressure psi (bar) Deflector to Ceiling Distance 16 x 16 (4.9 x 4.9)16 (61)7.6 (0.52) 1 to 4 inches (25 to 100 mm)18 x 18 (5.5 x 5.5)19 (72)10.8 (0.75) 20 x 20 (6.1 x 6.1)22 (83)14.4 (1.0) Model F1Res58 Residential Pendent Sprinkler Hydraulic Design Criteria Table D Notes: 1. For NFPA 13 installations the flow per sprinkler must be the greater of: (1) the flow listed in the table above or (2) the flow required to achieve a minimum design density of 0.1 gpm/sq ft over the design area of the sprinkler. 2. For coverage area dimensions less than those listed above, use the minimum required flow for the next larger max. coverage area listed. Model F1Res76 Residential Pendent Sprinkler & F1, F2, & FV Escutcheons SIN R7618 Technical Specifications Style: Pendent and Recessed Pendent Threads: 3/4” NPT or ISO7-1R3/4 Nominal K-Factor: 7.6 (109 metric) Max. Working Pressure: 175 psi (12 bar) Material Specifications Thermal Sensor: 3 mm glass bulb Sprinkler Frame: Brass Alloy Button: Copper Alloy Sealing Assembly: Nickel Alloy with PTFE Load Screw: Bronze Alloy Deflector: Bronze Alloy Finishes (See Table N) Temperature Ratings 155°F (68°C) 175°F (79°C) Recessed Escutcheons F1 Recessed F2 Recessed FV Recessed* Sprinkler Wrenches Model W2 Model GFR2 (Recessed) Model F1Res76 Residential Pendent Sprinkler Components and Installation Dimensions Figure 4 * Model FV escutcheons are not for use in positively pressurized ceiling plenums. Bulletin 135 October 2018 Page 5 of 15 www.reliablesprinkler.com Minimum Flow and Residual Pressure in Wet Pipe Systems(1) Maximum Coverage Area(2) ft. x ft. (m x m) Flow gpm (l/min) Pressure psi (bar) Deflector to Ceiling Distance 18 x 18 (5.5 x 5.5)21 (80)7.6 (0.52)1 to 4 inches (25 to 100 mm)20 x 20 (6.1 x 6.1)23 (87)9.2 (0.63) Model F1Res76 Residential Pendent Sprinkler Hydraulic Design Criteria Table E Notes: 1. For NFPA 13 installations the flow per sprinkler must be the greater of: (1) the flow listed in the table above or (2) the flow required to achieve a minimum design density of 0.1 gpm/sq ft over the design area of the sprinkler. 2. For coverage area dimensions less than those listed above, use the minimum required flow for the next larger max. coverage area listed. Model F1Res30 CCP Conical Concealed Pendent & Model FP Recessed Escutcheon Pendent Sprinkler SIN R3511 Technical Specifications Style: Conical Concealed Pendent and Recessed Pendent Threads: 1/2” NPT or ISO7-1R1/2 Nominal K-Factor: 3.0 (43 metric) Max. Working Pressure: 175 psi (12 bar) Material Specifications Thermal Sensor: 3 mm glass bulb Sprinkler Frame: Brass Alloy Button: Copper Alloy Sealing Assembly: Nickel Alloy with PTFE Load Screw: Bronze Alloy Deflector: Bronze Alloy Finishes (See Table N) Temperature Ratings 155°F (68°C) Recessed Escutcheons/Cover Plates CCP Conical Concealed Plate 135°F (57°C)* FP Recessed* Sprinkler Wrenches Model GFR2 Model F1Res30 CCP and FP Recessed Pendent Sprinkler Installation Dimensions Figure 5 *Note: Model FP escutcheons and CCP cover plates are not listed for use in positively pressurized ceiling plenums. Bulletin 135 October 2018 Page 6 of 15 www.reliablesprinkler.com Minimum Flow and Residual Pressure in Wet Pipe Systems(1) Maximum Coverage Area(2) ft. x ft. (m x m) Flow gpm (l/min) Pressure psi (bar)Deflector to Ceiling Distance 12 x 12 (3.7 x 3.7)8 (30)7.0 (0.48)1/2 to 1 inch (13 to 25 mm)14 x 14 (4.3 x 4.3)11 (38)13.4 (0.92) Model F1Res30 CCP Pendent & FP Recessed Pendent Sprinkler Hydraulic Design Criteria Table F Notes: 1. For NFPA 13 installations the flow per sprinkler must be the greater of: (1) the flow listed in the table above or (2) the flow required to achieve a minimum design density of 0.1 gpm/sq ft over the design area of the sprinkler. 2. For coverage area dimensions less than those listed above, use the minimum required flow for the next larger max. coverage area listed. 3. The sprinkler must be installed into a ceiling with the listed cover plate installed. Model F1Res49 CCP Conical Concealed Pendent & Model FP Recessed Escutcheon Pendent Sprinkler SIN R3516 Technical Specifications Style: Conical Concealed Pendent and Recessed Pendent Threads: 1/2” NPT or ISO7-1R1/2 Nominal K-Factor: 4.9 (71 metric) Max. Working Pressure: 175 psi (12 bar) Material Specifications Thermal Sensor: 3 mm glass bulb Sprinkler Frame: Brass Alloy Button: Copper Alloy Sealing Assembly: Nickel Alloy with PTFE Load Screw: Bronze Alloy Deflector: Bronze Alloy Finishes (See Table N) Temperature Ratings 155°F (68°C) Recessed Escutcheons/Cover Plates CCP Conical Concealed Plate 135°F (57°C)* FP Recessed* Sprinkler Wrenches Model GFR2 Model F1Res49 CCP & FP Recessed Pendent Sprinkler Installation Dimensions Figure 6 Minimum Flow and Residual Pressure in Wet Pipe Systems(1) Maximum Coverage Area(2) ft. x ft. (m x m) Flow gpm (l/min) Pressure psi (bar)Deflector to Ceiling Distance 14 x 14 (4.3 x 4.3)13 (49)7.0 (0.48) 1/2 to 1 inch (13 to 25 mm) 16 x 16 (4.9 x 4.9)14 (53)8.2 (0.57) 18 x 18 (5.5 x 5.5)18 (68)13.5 (0.93) 20 x 20 (6.1 x 6.1)20 (76)16.7 (1.15) Model F1Res49 CCP Pendent and FP Recessed Pendent Hydraulic Design Criteria Table G Notes: 1. For NFPA 13 installations the flow per sprinkler must be the greater of: (1) the flow listed in the table above or (2) the flow required to achieve a minimum design density of 0.1 gpm/sq ft over the design area of the sprinkler. 2. For coverage area dimensions less than those listed above, use the minimum required flow for the next larger max. coverage area listed. 3. The sprinkler must be installed into a ceiling with the listed cover plate installed. *Note: Model FP escutcheons and CCP cover plates are not for use in positively pressurized ceiling plenums. Bulletin 135 October 2018 Page 7 of 15 www.reliablesprinkler.com Model F1Res58 CCP Conical Concealed Pendent & Model FP Recessed Escutcheon Pendent Sprinkler SIN R3513 Technical Specifications Style: Conical Concealed Pendent and Recessed Pendent Threads: 1/2” NPT or ISO7-1R1/2 Nominal K-Factor: 5.8 (84 metric) Max. Working Pressure: 175 psi (12 bar) Material Specifications Thermal Sensor: 3 mm glass bulb Sprinkler Frame: Brass Alloy Button: Copper Alloy Sealing Assembly: Nickel Alloy with PTFE Load Screw: Bronze Alloy Deflector: Bronze Alloy Finishes (See Table N) Temperature Ratings 155°F (68°C) Recessed Escutcheons/Cover Plates CCP Conical Concealed Plate 135°F (57°C)* FP Recessed* Sprinkler Wrenches Model GFR2 (Recessed) Figure 7Model F1Res58 CCP and FP Recessed Pendent Sprinkler Installation Dimensions Minimum Flow and Residual Pressure in Wet Pipe Systems(1) Maximum Coverage Area(2) ft. x ft. (m x m) Flow gpm (l/min) Pressure psi (bar)Deflector to Ceiling Distance 16 x 16 (4.9 x 4.9)16 (61)7.6 (0.52) 1/2 to 1 inch (13 to 25 mm)18 x 18 (5.5 x 5.5)19 (72)10.8 (0.75) 20 x 20 (6.1 x 6.1)22 (83)14.4 (1.0) Model F1Res58 CCP Pendent & FP Recessed Pendent Hydraulic Design Criteria Table H *Note: Model FP escutcheons and CCP cover plates are not for use in positively pressurized ceiling plenums. Notes: 1. For NFPA 13 installations the flow per sprinkler must be the greater of: (1) the flow listed in the table above or (2) the flow required to achieve a minimum design density of 0.1 gpm/sq ft over the design area of the sprinkler. 2. For coverage area dimensions less than those listed above, use the minimum required flow for the next larger max. coverage area listed. 3. The sprinkler must be installed into a ceiling with the listed cover plate installed. Bulletin 135 October 2018 Page 8 of 15 www.reliablesprinkler.com Figure 8Model F1Res76 CCP and FP Recessed Pendent Sprinkler Installation Dimensions Model F1Res76 CCP Conical Concealed Pendent and Model FP Recessed Escutcheon Pendent Sprinkler SIN R7618 Technical Specifications Style: Conical Concealed Pendent and Recessed Pendent Threads: 3/4” NPT or ISO7-1R3/4 Nominal K-Factor: 7.6 (109 metric) Max. Working Pressure: 175 psi (12 bar) Material Specifications Thermal Sensor: 3 mm glass bulb Sprinkler Frame: Brass Alloy Button: Copper Alloy Sealing Assembly: Nickel Alloy with PTFE Load Screw: Bronze Alloy Deflector: Bronze Alloy Finishes (See Table N) Temperature Ratings 155°F (68°C) Recessed Escutcheons/Cover Plates CCP Conical Concealed Plate 135°F (57°C)* FP Recessed* Sprinkler Wrenches Model GFR2 (Recessed) Minimum Flow and Residual Pressure in Wet Pipe Systems(1) Maximum Coverage Area(2) ft. x ft. (m x m) Flow gpm (l/min) Pressure psi (bar)Deflector to Ceiling Distance 16 x 16 (4.9 x 4.9)21 (80)7.6 (0.52) 1/2 to 1 inch (13 to 25 mm)18 x 18 (5.5 x 5.5)22 (83)8.4 (0.58) 20 x 20 (6.1 x 6.1)25 (95)10.8 (0.75) Model F1Res76 CCP Pendent & FP Recessed Pendent Hydraulic Design Criteria Table I *Note: Model FP escutcheons and CCP cover plates are not for use in positively pressurized ceiling plenums. Notes: 1. For NFPA 13 installations the flow per sprinkler must be the greater of: (1) the flow listed in the table above or (2) the flow required to achieve a minimum design density of 0.1 gpm/sq ft over the design area of the sprinkler. 2. For coverage area dimensions less than those listed above, use the minimum required flow for the next larger max. coverage area listed. 3. The sprinkler must be installed into a ceiling with the listed cover plate installed. Bulletin 135 October 2018 Page 9 of 15 www.reliablesprinkler.com Model F1Res44 Horizontal Sidewall Sprinkler & Models FV & F2 Recessed Escutcheon SIN R3531 Technical Specifications Style: Sidewall and Recessed Sidewall Threads: 1/2” NPT or ISO7-1R1/2 Nominal K-Factor: 4.4 (63 metric) Max. Working Pressure: 175 psi (12 bar) Material Specifications Thermal Sensor: 3 mm glass bulb Sprinkler Frame: Brass Alloy Button: Copper Alloy Sealing Assembly: Nickel Alloy with PTFE Load Screw: Bronze Alloy Deflector: Bronze Alloy Finishes (See Table N) Temperature Ratings 155°F (68°C) 175°F (79°C) Recessed Escutcheons F2 Recessed FV Recessed Sprinkler Wrenches Model W2 Model GFR2 (Recessed) Minimum Flow and Residual Pressure in Wet Pipe Systems(1) Maximum Coverage Area(2) ft. x ft. (m x m) Flow gpm (l/min) Pressure psi (bar) Deflector to Ceiling Distance 12 x 12 (3.7 x 3.7)12 (45)7.5 (0.52) 4 to 6 inches (100 to 150 mm) 14 x 14 (4.3 x 4.3)14 (53)10.2 (0.70) 15 x 15 (4.6 x 4.6) 15 (57)11.6 (0.80) 16 x 16 (4.9 x 4.9)16 (61)13.3 (0.92) 16 x 18 (4.9 x 5.5)18 (68)16.8 (1.16) 16 x 20 (4.9 x 6.1)23 (87)27.4 (1.89) 18 x 18 (5.5 x 5.5)19 (72)18.7 (1.29) 12 x 12 (3.7 x 3.7)14 (53)10.2 (0.7) 6 to 12 inches (150 to 300 mm) 14 x 14 (4.3 x 4.3)16 (61)13.2 (0.91) 15 x 15 (4.6 x 4.6)16 (61)13.2 (0.91) 16 x 16 (4.9 x 4.9)17 (64)15.0 (1.03) 16 x 18 (4.9 x 5.5)20 (76)20.7 (1.43) 16 x 20 (4.9 x 6.1)23 (87)27.4 (1.89) Model F1Res44 Horizontal Sidewall Sprinkler Hydraulic Design Criteria Table J Notes: 1. For NFPA 13 installations the flow per sprinkler must be the greater of: (1) the flow listed in the table above or (2) the flow required to achieve a minimum design density of 0.1 gpm/sq ft over the design area of the sprinkler. 2. For coverage area dimensions less than those listed above, use the minimum required flow for the next larger max. coverage area listed. Model F1Res44 Horizontal Sidewall Sprinkler Installation Dimensions Figure 9 Bulletin 135 October 2018 Page 10 of 15 www.reliablesprinkler.com Note: (1) Not for installation where the maximum ceiling temperature exceeds 100°F due to cover plate temperature rating. (2) 135°F SWC Conical Concealed Plate for 155°F (68°C) sprinklers (3) 135°F SWC-2 (Slotted) Conical Concealed Plate for 175°F (79°C) sprinklers Minimum Flow and Residual Pressure in Wet Pipe Systems(1) Maximum Coverage Area(2) ft. x ft. (m x m) Ordinary Temperature Rating 155°F (68°C) Intermediate Temperature Rating 175°F (79°C)Deflector to Ceiling DistanceFlow gpm (l/min) Pressure psi (bar) Flow gpm (l/min) Pressure psi (bar) 12 x 12 (3.7 x 3.7)13 (49)8.7 (0.60)14 (53)10.2 (0.7) 4 to 6 inches (100 to 150 mm) 14 x 14 (4.3 x 4.3)14 (53)10.2 (0.7)14 (53)10.2 (0.7) 15 x 15 (4.6 x 4.6)16 (61)13.2 (0.91)– –– – 16 x 16 (4.9 x 4.9)17 (64)15.0 (1.03)– –– – 16 x 18 (5.5 x 5.5)19 (72)18.7 (1.31)– –– – 16 x 20 (4.9 x 6.1)23 (87)27.4 (1.89)– –– – 12 x 12 (3.7 x 3.7)14 (53)10.2 (0.7)– –– – 6 to 12 inches (150 to 300 mm) 14 x 14 (4.3 x 4.3)15 (57)11.7 (0.81)– –– – 15 x 15 (4.6 x 4.6)17 (64)15.0 (1.03)– –– – 16 x 16 (4.9 x 4.9)18 (68)16.8 (1.16)– –– – 16 x 18 (4.9 x 5.5)20 (76)20.7 (1.43)– –– – Model F1Res44 SWC Conical Concealed Horizontal Sidewall Sprinkler Hydraulic Design Criteria Table K Notes: 1. For NFPA 13 installations the flow per sprinkler must be the greater of: (1) the flow listed in the table above or (2) the flow required to achieve a minimum design density of 0.1 gpm/sq ft over the design area of the sprinkler. 2. For coverage area dimensions less than those listed above, use the minimum required flow for the next larger max. coverage area listed. SWC SWC-2 Bulletin 135 October 2018 Page 11 of 15 www.reliablesprinkler.com Model F1Res44 SWC Conical Concealed Horizontal Sidewall Sprinkler SIN R3531 Technical Specifications Style: Conical Concealed Sidewall Threads: 1/2” NPT or ISO 7-1 R1/2 Nominal K-Factor: 4.4 (63 metric) Max. Working Pressure: 175 psi (12 bar) Material Specifications Thermal Sensor: 3 mm glass-bulb Sprinkler Frame: Brass Alloy Button: Copper Alloy Sealing Assembly: Nickel Alloy with PTFE Load Screw: Bronze Alloy Deflector: Bronze Alloy Finishes (See Table N) Temperature Ratings 155°F (68°C) 175°F (79°C) (1) Cover Plates SWC Conical Concealed Plate(2) SWC-2 (Slotted) Conical Concealed Plate(3) Sprinkler Wrenches Model GFR2 Model F1Res44 SWC Conical Concealed Horizontal Sidewall Sprinkler and Installation Dimensions Figure 10 Model F1Res58 Horizontal Sidewall Sprinkler & Models F2 & FV Recessed Escutcheon SIN R3533 Technical Specifications Style: Sidewall and Recessed Sidewall Threads: 1/2” NPT or ISO7-1R1/2 Nominal K-Factor: 5.8 (84 metric) Max. Working Pressure: 175 psi (12 bar) Material Specifications Thermal Sensor: 3 mm glass bulb Sprinkler Frame: Brass Alloy Button: Copper Alloy Sealing Assembly: Nickel Alloy with PTFE Load Screw: Bronze Alloy Deflector: Bronze Alloy Finishes (See Table N) Temperature Ratings 155°F (68°C) 175°F (79°C) Recessed Escutcheons F2 Recessed FV Recessed Sprinkler Wrenches Model W2 Model GFR2 (Recessed) Minimum Flow and Residual Pressure in Wet Pipe Systems(1) Maximum Coverage Area(2) ft. x ft. (m x m) Flow gpm (l/min) Pressure psi (bar) Deflector to Ceiling Distance 12 x 12 (3.7 x 3.7)16 (61)7.6 (0.52) 4 to 6 inches (100 to 150 mm) 14 x 14 (4.3 x 4.3)18 (68)9.7 (0.66) 15 x 15 (4.6 x 4.6)19 (72)10.7 (0.74) 16 x 16 (4.9 x 4.9)21 (80)13.2 (0.91) 16 x 18 (5.5 x 5.5)25 (95)18.6 (1.28) 16 x 20 (4.9 x 6.1)29 (110)25.0 (1.72) 12 x 12 (3.7 x 3.7)22 (83)14.4 (1.0) 6 to 12 inches (150 to 300 mm) 14 x 14 (4.3 x 4.3)22 (83)14.4 (1.0) 15 x 15 (4.6 x 4.6)24 (91)17.1 (1.18) 16 x 16 (4.9 x 4.9)26 (98)20.1 (1.39) 16 x 18 (4.9 x 5.5)31 (117)28.6 (1.97) Model F1Res58 Horizontal Sidewall Sprinkler Hydraulic Design Criteria Table L Notes: 1. For NFPA 13 installations the flow per sprinkler must be the greater of: (1) the flow listed in the table above or (2) the flow required to achieve a minimum design density of 0.1 gpm/sq ft over the design area of the sprinkler. 2. For coverage area dimensions less than those listed above, use the minimum required flow for the next larger max. coverage area listed. Model F1Res58 Residential Horizontal Sidewall Sprinkler Installation Dimensions Figure 11 Bulletin 135 October 2018 Page 12 of 15 www.reliablesprinkler.com Model F1Res58 HSWX Horizontal Sidewall Sprinkler & Models F2 & FV Recessed Escutcheon SIN RA3533 Technical Specifications Style: Sidewall and Recessed Sidewall Threads: 1/2” NPT or ISO7-1R1/2 Nominal K-Factor: 5.8 (84 metric) Max. Working Pressure: 175 psi (12 bar) Material Specifications Thermal Sensor: 3 mm glass bulb Sprinkler Frame: Brass Alloy Button: Copper Alloy Sealing Assembly: Nickel Alloy with PTFE Load Screw: Bronze Alloy Deflector: Bronze Alloy Finishes (See Table N) Temperature Ratings 155°F (68°C) 175°F (79°C) Recessed Escutcheons F2 Recessed FV Recessed Sprinkler Wrenches Model W2 Model GFR2 (Recessed) Minimum Flow and Residual Pressure in Wet Pipe Systems(1) Maximum Coverage Area(2) ft. x ft. (m x m) Flow gpm (l/min) Pressure psi (bar) Deflector to Ceiling Distance 18 x 20 (5.5 x 6.1)30 (114)26.8 (1.85) 4 to 6 inches (100 to 150 mm) 20 x 20 (6.1 x 6.1)30 (114)26.8 (1.85) 16 x 22 (4.9 x 6.7)33 (125)32.4 (2.23) 16 x 24 (4.9 x 7.3)38 (144)42.9 (2.96) 14 x 26 (4.3 x 7.9)42 (160)52.4 (3.63) 18 x 20 (5.5 x 6.1)35 (133)36.4 (2.51) 6 to 12 inches (150 to 300 mm) 16 x 22 (4.9 x 6.7)38 (144)42.9 (2.96) 16 x 24 (4.9 x 7.3)42 (160)52.4 (3.61) 14 x 26 (4.3 x 7.9)46 (174)62.9 (4.34) Model F1Res58 HSWX Horizontal Sidewall Sprinkler Hydraulic Design Criteria Table M Notes: 1. For NFPA 13 installations the flow per sprinkler must be the greater of: (1) the flow listed in the table above or (2) the flow required to achieve a minimum design density of 0.1 gpm/sq ft over the design area of the sprinkler. 2. For coverage area dimensions less than those listed above, use the minimum required flow for the next larger max. coverage area listed. Model F1Res58 HSWX Residential Horizontal Sidewall Sprinkler Installation Dimensions Figure 12 Bulletin 135 October 2018 Page 13 of 15 www.reliablesprinkler.com Installation Models F1Res sprinklers are to be installed as shown in this bulletin. Model F1, F2, FV, and FP recessed escutcheons are the only recessed escutcheons to be used with Model F1Res sprinklers. Not all F1Res sprinklers may be used with all recessed escutcheons offered. Confirm listing of escutch- eon type for use with individual sprinklers. Use of any other recessed escutcheon will void all approvals and warranties. For installing Model F1Res sprinklers, use only the Model W2 sprinkler Wrench; for installing Models F1Res Recessed Pendent, Sidewall, Conical Concealed Pendent (CCP), and Sidewall Concealed (SWC and SWC–2) sprinklers use only the Model GFR2 sprinkler wrench. Use of wrenches other than those specified may damage these sprinklers. Model GFR2 Model W2 Installation of F1Res sprinklers in a wall or ceiling will require a hole diameter of 2-1/4” (57 mm) for F1 or F2 recessed escutcheons; or 2-5/8” (67 mm) for FP recessed escutcheons, CCP, SWC, and SWC–2 cover plates. Install F1Res HSW sprinklers with a ceiling to deflector dis- tance that complies with the hydraulic design criteria tables in this bulletin. The flow arrow on deflector must point away from near wall and “Top” marking must face the ceiling. A ‘leak tight” sprinkler joint can be obtained with the following torque: • 1/2” NPT and ISO7-1R1/2: 8-18 ft-lbs (11 – 24 N-m) • 3/4” NPT and ISO7-1R3/4: 14-20 ft-lbs (19 – 27 N-m) Do not tighten sprinklers over maximum recommended torque. This may cause leakage or impairment of the sprinklers. Do not install any glass bulb sprinklers where the bulb is cracked or there is a loss of liquid from the bulb. Glass bulb sprinklers have orange bulb protectors to mini- mize bulb damage during shipping, handling and installation. Remove this protection at the time the sprinkler system is placed in service. Removal of the protectors before this time may leave the bulb vulnerable to damage. RASCO wrenches are designed to install sprinklers when protectors are in place. Remove protectors by undoing the clasp by hand. Do not use tools to remove the protectors. Maintenance Reliable Model F1Res Sprinklers should be inspected and the sprinkler system maintained in accordance with NFPA 25, 13, 13D, and 13R, as well as the requirements of any Authorities Having Jurisdiction. Prior to installation, sprinklers should remain in the original cartons and packaging until used. This will minimize the potential for damage to sprinklers that could cause improper operation or non-operation. Do not clean sprinklers with soap and water, ammonia liquid or any other cleaning fluids. Remove dust by gentle vacuum- ing without touching the sprinkler. Replace any sprinkler which has been painted (other than factory applied). Properly installed CCP, SWC, and SWC–2 cover plates will have an air gap that is required for proper operation, do not seal the gap or paint the cover plates. Table N Standard Finishes Special Application Finishes Sprinkler(1)F1, F2. FV, FP(3), Escutcheons CCP, SWC (Conical) Cover Plates (1)Sprinkler (1)F1, F2. FV, FP(3), Escutcheons CCP, SWC (Conical) Cover Plates (1) Bronze Brass --Bright Brass Bright Brass Bright Brass Chrome Plated Chrome Plated Chrome Plated Dull Chrome Dull Chrome Dull Chrome White Polyester (2) White Polyester White Paint Black Polyester (2) Black Polyester Black Paint ------Custom Color Polyester Custom Color Polyester Custom Color Paint ------Electroless Nickel PTFE (2)---- Notes: (1) Paint or any other coating applied over the factory finish will void all approvals and warranties. (2) cULus Listed Corrosion Resistant. (3) The Model FP escutcheon assembly consists of an unfinished galvanized cup with a finished escutcheon ring. Finishes Bulletin 135 October 2018 Page 14 of 15 www.reliablesprinkler.com P / N 9 9 9 9 9 7 0 2 3 5 Replace any sprinkler which has been damaged, where cracks are observed in the glass bulb, or when liquid has been lost from the glass bulb. A stock of spare sprinklers should be maintained to allow quick replacement of damaged or operated sprinklers. Failure to properly maintain sprinklers may result in inadver- tent operation or non-operation during a fire event. Listings & Approvals Listed by Underwriters Laboratories Inc. and UL Certified for Canada (cULus) Guarantee For Reliable Automatic Sprinkler Company guarantee, terms, and conditions, visit www.reliablesprinkler.com. Patents For patents applicable to products contained in this technical bulletin, please visit www.r-s.co Ordering Information Specify the following when ordering: Sprinkler • Model (See Table A) • Temperature Rating • Threads (NPT or ISO7-1) • Finish (See Table N) Escutcheon or Cover Plate • Model • Finish (See Table N) Sprinkler Wrench • Model W2 (Pendent and HSW) • GFR2 (Recessed and Concealed) Bulletin 135 October 2018 Page 15 of 15 www.reliablesprinkler.com