Loading...
HomeMy WebLinkAboutHYDRAULIC CALCULATIONS - 17-00123 - 555 W Mikan Dr - Eden Apartments Bldg 4 - 42 Units Project Name : 17-228 Drawing No. : Project Location: City: CALCULATION SUMMARY Design Areas Design Area Name Min. Density Area of Application Occupancy Calculated Heads Min. Pressure Hose Streams Total Water Pressure @ Source Margin To Source (gpm/ft²)(ft²)#(psi)(gpm)(gpm)(psi)(psi) Min. Flow (gpm) Calc. Mode (Model) 1 RES 1200 160.7 Required 70.2 0.05 20 3 100 12.416.7Demand (HW) Date 4/9/2018 Page 1Copyright © 2002-2012 Tyco Fire Protection Products File: D:\Dropbox (Phoenix Fire)\Phoenix Fire - Design\Current Jobs\2017\17-228 Eden Apts - Rexburg\17-228 FP 42-PLEX.dwg Design Remote Area Name Remote Area Location Occupancy Classification Density (gpm/ft²) Area of Application (ft²) Coverage per Sprinkler (ft²) Number of Calculated Sprinklers In-Rack Demand (gpm) Special Heads Hose Streams (gpm) Total Water Required (incl. Hose Streams) (gpm) Required Pressure at Source (psi) Type of System Volume - Entire System (gal) 1 RES 0.05 1200 400 3 0 100 160.7 70.2 Wet 91.2 gal Water Supply Information Date Location Source HYDRAULIC CALCULATIONS for 02/05/2018 ON-SITE83 SRC Project Name : 17-228 Contract No. : Project Location: City: Date: 4/9/2018 Name of Contractor: Address: Phone Number: Name of Designer: DAMION SNODGRASS Authority Having Jurisdiction: City: E-mail: Job Information Contractor Information Notes Date 4/9/2018 Page 2Copyright © 2002-2012 Tyco Fire Protection Products File: D:\Dropbox (Phoenix Fire)\Phoenix Fire - Design\Current Jobs\2017\17-228 Eden Apts - Rexburg\17-228 FP 42-PLEX.dwg Job : 17-228 Diagram for Design Area : 1 (Optimized Hydraulic Simplified) Node Labels: Pipe Labels: Off Off Date 4/9/2018 Page 3Copyright © 2002-2012 Tyco Fire Protection Products File: D:\Dropbox (Phoenix Fire)\Phoenix Fire - Design\Current Jobs\2017\17-228 Eden Apts - Rexburg\17-228 FP 42-PLEX.dwg Job : 17-228 Hydraulic Analysis for : 1 Water Supply Parameters Calculation Info Calculation Mode Hydraulic Model Fluid Name Fluid Weight, (lb/ft³) Fluid Dynamic Viscosity, (lb·s/ft²) Demand Hazen-Williams Water @ 60F (15.6C) N/A for Hazen-Williams calculation. N/A for Hazen-Williams calculation. Supply 1 : SRC Flow (gpm)Pressure (psi) 0 83 1400 62 Node at Source Static Pressure (psi) Residual Pressure (psi) Flow (gpm) Available Pressure (psi) Total Demand (gpm) Required Pressure (psi) Supply Analysis SRC 83 62 1400 82.9 160.7 70.2 Inside Hose Flow / Standpipe Demand (gpm) Outside Hose Flow (gpm) Additional Outside Hose Flow (gpm) Other (custom defined) Hose Flow (gpm) Total Hose Flow (gpm) 100 100 Hoses Ovehead Sprinkler Flow (gpm) InRack Sprinkler Flow (gpm) Other (custom defined) Sprinkler Flow (gpm) Total Sprinkler Flow (gpm) 60.7 0 0 60.7 Required Margin of Safety (psi) SRC - Pressure (psi) SRC - Flow (gpm) Demand w/o System Pump(s) 0 70.2 60.7 N/A Sprinklers Other Date 4/9/2018 Page 4Copyright © 2002-2012 Tyco Fire Protection Products File: D:\Dropbox (Phoenix Fire)\Phoenix Fire - Design\Current Jobs\2017\17-228 Eden Apts - Rexburg\17-228 FP 42-PLEX.dwg Job : 17-228 Hydraulic Analysis for : 1 Date 4/9/2018 Page 5 Copyright © 2002-2012 Tyco Fire Protection Products File: D:\Dropbox (Phoenix Fire)\Phoenix Fire - Design\Current Jobs\2017\17-228 Eden Apts - Rexburg\17-228 FP 42-PLEX.dwg Job : 17-228 Hydraulic Analysis for : 1 Pressure (psi)Label Graph Labels Flow (gpm) ValuesDescription 0S1 83Supply point #1 - Static 1400S2 62Supply point #2 - Residual 0D1 15.5Elevation Pressure 60.7D2 70.2System Demand 160.7D3 70.2System Demand + Add.Out.Hose Pressure (psi) Curve Name Curve Intersections & Safety Margins Flow (gpm) Safety MarginIntersection Pressure (psi)@ Flow (gpm) 67.9Supply82.9 12.4 160.7 Open Heads Head Ref. DensityDensity K-Factor PressureFlowPressure (gpm/ft²)(gpm/ft²)(gpm/psi½)(psi)(gpm)(psi) Flow (gpm) Coverage (ft²) Required Calculated Head Type S101 4.9 0.05 20 16.7 0.05 16.720400Overhead Sprinkler S102 4.9 0.05 20 16.7 0.05 16.720400Overhead Sprinkler S103 4.9 0.05 20 16.7 0.052 17.820.7400Overhead Sprinkler Date 4/9/2018 Page 6Copyright © 2002-2012 Tyco Fire Protection Products File: D:\Dropbox (Phoenix Fire)\Phoenix Fire - Design\Current Jobs\2017\17-228 Eden Apts - Rexburg\17-228 FP 42-PLEX.dwg Job : 17-228 Node Data Hydraulic Calculations / Fluid Delivery Time Analysis Node# Elev ft Type Hgroup K-Fact. Open/Closed gpm/psi½ Discharge Overdischarge gpm gpm Coverage Density ft² gpm/ft² Tot. Pres. Elev. Pres. psi psi Req. Pres. Req. Discharge psi gpm S102 30.75 Overhead Sprinkler HEAD 4.9 Open 20 0 400 0.05 16.7 -15.5 16.7 20 S101 30.75 Overhead Sprinkler HEAD 4.9 Open 20 0.0 400 0.05 16.7 -15.5 16.7 20 S103 30.75 Overhead Sprinkler HEAD 4.9 Open 20.7 0.7 400 0.052 17.8 -15.5 16.7 20 543 31.17 Node NODE 16.8 -15.7 001 31.17 Node NODE 17.2 -15.7 003 31.17 Node NODE 17.6 -15.7 004 31.17 Node NODE 17.8 -15.7 542 31.17 Node NODE 18 -15.7 005 31.17 Node NODE 18.4 -15.7 299-O 6.17 Node NODE 58.8 -4.8 299-I 5.06 Node NODE 64.8 -4.4 300 1 Node NODE 67.6 -2.6 SRC -5 Supply SUPPLY -60.7 70.2 0 Date 4/9/2018 Page 7Copyright © 2002-2012 Tyco Fire Protection Products File: D:\Dropbox (Phoenix Fire)\Phoenix Fire - Design\Current Jobs\2017\17-228 Eden Apts - Rexburg\17-228 FP 42-PLEX.dwg Hydraulic CalculationsJob : 17-228 PIPE INFORMATION Node 1 Node 2 Elev 1 Elev 2 (ft) K-Factor 1 K-Factor 2 (gpm/psi½) Flow added (q) Total flow (Q) (gpm) Nominal ID Actual ID (in) Fittings quantity x (name) = length (ft) L F T (ft) C Factor Pf per ft (psi) total (Pt) elev (Pe) frict (Pf) (psi) NOTES 1Path No: S102 543 30.75 31.17 4.9 20 20 1 1.049 1x(us.90)=2 0.42 2 2.42 120 0.1297 16.7 -0.2 0.3 543 004 31.17 31.17 0 20 1 1.101 1x(BM.Tee-Br)=5 10.42 5 15.42 150 0.0678 16.8 0 1 004 005 31.17 31.17 20 40 1.25 1.394 1x(BM.Tee-Run)=1 6.8 1 7.8 150 0.0776 17.8 0 0.6 005 299-O 31.17 6.17 20.7 60.7 1.25 1.394 16x(BM.Tee-Run)=16 1x(coupling)=1.59 1x(BM.90)=6 2x(BM.Tee-Br)=12 140.57 35.59 176.16 150 0.1679 18.4 10.8 29.6 299-O 299-I 6.17 5.06 0 60.7 1.25 0 1.11 0 1.11 0 4.9522 58.8 0.5 5.5 Ames2000B *** 299-I 300 5.06 1 0 60.7 1.25 1.394 1x(coupling)=1.59 4.06 1.59 5.64 150 0.1679 64.8 1.8 0.9 300 SRC 1 -5 0 60.7 4 4.24 1x(us.90)=19.43 106 19.43 125.43 150 0.0007 67.6 2.6 0.1 SRC 70.2 2Path No: S101 001 30.75 31.17 4.9 20 20 1 1.049 1x(us.Tee-Br)=5 0.42 5 5.42 120 0.1299 16.7 -0.2 0.7 001 003 31.17 31.17 0 20 1 1.101 1x(BM.90)=5 0.86 5 5.86 150 0.0679 17.2 0 0.4 003 004 31.17 31.17 0 20 1.25 1.394 1x(BM.Tee-Run)=1 9.2 1 10.2 150 0.0215 17.6 0 0.2 004 17.8 3Path No: S103 542 30.75 31.17 4.9 20.7 20.7 1 1.049 1x(us.90)=2 0.42 2 2.42 120 0.1379 17.8 -0.2 0.3 542 005 31.17 31.17 0 20.7 1 1.101 1x(BM.Tee-Br)=5 1.69 5 6.69 150 0.0721 18 0 0.5 005 18.4 Date 4/9/2018 Page 8Copyright © 2002-2012 Tyco Fire Protection Products File: D:\Dropbox (Phoenix Fire)\Phoenix Fire - Design\Current Jobs\2017\17-228 Eden Apts - Rexburg\17-228 FP 42-PLEX.dwg Hydraulic CalculationsJob : 17-228 PIPE INFORMATION Node 1 Node 2 Elev 1 Elev 2 (ft) K-Factor 1 K-Factor 2 (gpm/psi½) Flow added (q) Total flow (Q) (gpm) Nominal ID Actual ID (in) Fittings quantity x (name) = length (ft) L F T (ft) C Factor Pf per ft (psi) total (Pt) elev (Pe) frict (Pf) (psi) NOTES * Pressures are balanced to a high degree of accuracy. Values may vary by 0.1 psi due to display rounding. *** Device pressure loss (gain in the case of pumps) is calculated from the device’s curve. If the device curve is printed with this report, it will appear below. The length of the device as shown in the table above comes from the CAD drawing. The friction loss per unit of length is calculated based upon the length and the curve-based loss/gain value. Internal ID and C Factor values are irrelevant as the device is not represented as an addition to any pipe, but is an individual item whose loss/gain is based solely on the curve data. * Maximum Velocity of 12.76 ft/s occurs in the following pipe(s): (299-O-005), (300-299-I) Date 4/9/2018 Page 9Copyright © 2002-2012 Tyco Fire Protection Products File: D:\Dropbox (Phoenix Fire)\Phoenix Fire - Design\Current Jobs\2017\17-228 Eden Apts - Rexburg\17-228 FP 42-PLEX.dwg Device GraphsJob : 17-228 Date 4/9/2018 Page 10Copyright © 2002-2012 Tyco Fire Protection Products File: D:\Dropbox (Phoenix Fire)\Phoenix Fire - Design\Current Jobs\2017\17-228 Eden Apts - Rexburg\17-228 FP 42-PLEX.dwg 02.05.18 – Flowed by Clint Charles Stat – 83 Residual – 62 Pitot - 55 Pitot – 55 4130 Airport Road Phone: 208-468-9115 Nampa, Idaho 83687 Fax: 208-461-9117 5226 S 45 W Phone: 208-313-7153 Idaho Falls, Idaho 83402 Fax: 208-461-9117 02.08.18 Project: Eden Apartments Madison fire Department 26 N. Center St. Rexburg, ID 83440 Attn: Dale Pickering RE: Fire Department Connection Dale, Please pre-approve Fire Department connection locations at the above mentioned project. Please see attached detail of proposed locations. If these locations are unacceptable, please specify desired locations and return with this report. If you have any further questions and/or concerns, please feel free to call. Sincerely, Don Weland Phoenix Fire Protection