HomeMy WebLinkAboutREVIEW REPORT REVISIONS - 17-00373 - 720 Cornelison Ave - Juniper Sands Apartments - Bldg #3 - 56 UnitsReview
Report
Current Building Review Status: REVISIONS
Application Number: 17-00371Permit Details
Application Received Date: 07/06/2017
Multi-Family Residential
Application Approved Date:
Application Approved Status: APPROVED
07/06/2017
Juniper Sands Apartments - Building #1
Status of Plan Reviews Completed
07/11/2017Electrical Review REVISIONS
07/12/2017Plumbing Review COMPLETED
07/12/2017HVAC Review COMPLETED
07/13/2017Fire Department Review - Site Plan COMPLETED
07/21/2017Planning and Zoning Review - Site Plan REVISIONS
07/26/2017Building Review REVISIONS
Permit Review Status
Plan Reviews Still in Progress
Public Works Review - Site Plan
Electrical Review
Planning and Zoning Review - Site Plan
Building Review
DESCRIPTION COMMENTS STA TUS
*Please respond to "REVISIONS" status items, with appropriate comment/documentation as needed!
Rated doors and windows meet the requirements
of IBC Section 716
REVISIONSDoors at stair enclosures shall be 90 min
(revision needed for stair enclosure to be 2 hour
- connects 4 stories)
*Revisions Response :
fireblocking and draftstopping meet the
requirements of IBC Section 718
REVISIONS* Identify draft stopping in attic as required by
718.4.2 or per exceptions.
* Fire blocking approval will be based on
inspection.
*Revisions Response :
Exit Enclosures meet the requirements of IBC
Section 1022
REVISIONS* Barrier required in exit enclosure at stairs
descending below the exit discharge level.
* Exit enclosure connecting 4 stories shall be 2
hour fire rated.
* Required stair signage per 1022.9 is not
identified on plans. Recommended for review
and approval before installation.
* Wall type 7 shows both sides fire rated, even
for exterior walls, but 3/4 hour fire protection
rated openings are not identified (1022.7)
*Revisions Response :
Reviewed By: Quinton Owens
Review Date: 07/26/2017
Plan Review Details
quinton.owens@rexburg.org
Building Review Status: REVISIONS
Page 1 of 2
Approval of plans does not constitue approval of variance from code
Building Review (Continued)
D ESCRIPTIO N CO MMEN TS STATUS
All Accessible Routes meet the requirements of
IBC Section 1104
REVISIONSAll passage doors in type A units require 3'0"
doors.
*Revisions Response :
Building complies with IECC (IBC, 1301)REVISIONSBuilding needs to meet prescriptive thermal
envelope requirements or submit energy
compliance report.
*Revisions Response :
Glass and Glazing meets the requirements of IBC
Chapter 24
REVISIONSGlazing less than 36" above landing and within
60" horizontally of the bottom tread of stairs
and windows less than 60" above adjacent
stairs are hazardous locations and shall be
tempered.
*Revisions Response :
Site Grading meets the requirements of IBC
Section 1804.3
Grade shall slope away from building for
drainage per 1804.3
COMPLETED
Fire barriers meet the requirements of IBC
Section 707
Fire riser room and stair enclosure walls are
constructed as fire barriers - fire rating extends
up to roof or floor deck above regardless of
ceiling rating.
COMPLETED
Penetrations meet the requirements of IBC
Section 714
No fire stop penetration details provided. Fire
rating of walls and horizontal assemblies shall
be maintained at all penetrations.
COMPLETED
Dwelling Units meet the requirements of IBC
Section 1107
3 type A required, 2 one bedroom unit & 1 two
bedroom provided.
All other ground floor units are type B
COMPLETED
Toilets, Bathing Fac., Sinks, Kit. and Drink. Fount.
meet IBC Sec. 1109
Note: In type A units, Floor & wall finish to be
done with removable cabinet allowed under
kitchen sink for wheelchair forward approach
(not identified on plans).
COMPLETED
Page 2 of 2
Approval of plans does not constitue approval of variance from code