HomeMy WebLinkAboutINSPECTION SUMMARY - 17-00285 - 398 Pioneer Rd - Rocky Ridge Apartments - Bldg 1 - 4 plexPermit
Inspection
Summary
Permit Status of (Open) as of Report Date: 04/03/2019 11:17 am
Permit Details Permit Number: 17-00285
398 Pioneer Rd - Rocky Ridge Apartments - Bldg 1 - 4 plex
398 Pioneer Rd
Multi-Family Residential
Permit Issued Date: 02/23/2018
Permit Inspection Statistics
39Total Inspections Completed:
27Total Inspections Passed:
Inspection Pass Rate: 69.23%
Permit Inspection History *Refer to Individual Inspection Report for more Details
10/03/2018PARTPASSJoel GrayPublic Works Final Inspection
Fire hydrants near buildings 15 and 11 are too low. Hydrant bottom must be
between 3 and 9" above finished grade. Some storz adapters not installed yet.
Inspector Comments:
10/09/2018PassJoel GrayPublic Works Final Inspection
12/05/2018PassQuinton OwensPlanning and Zoning Final Inspection
Landscaping is completed for building 1.
P&Z approved for occupancy
Inspector Comments:
Building Inspection Type
07/18/2017PassTed DyeCommercial Footing Inspection
07/26/2017PassTed DyeFoundation Inspection
08/23/2017PassTed DyeCommercial Insulation Inspection
09/25/2017FailTed DyeSheeting
Sheeting that missed being nailed to the studs has been marked with green
paint.
Inspector Comments:
10/03/2017PassQuinton OwensSheeting
Sheathing corrections have been made at marked locations.Inspector Comments:
10/29/2017FailTed DyeCommercial Framing/Structure Inspection
10/30/2017FailTed DyeCommercial Framing/Structure Inspection
10/31/2017PassTed DyeCommercial Insulation Inspection
11/03/2017FailTed DyeCommercial Sheetrock/Drywall Inspection
11/06/2017PassTed DyeCommercial Sheetrock/Drywall Inspection
Both main level units require solid metal cover over clean outs in rated walls to
protect penetrations.
Inspector Comments:
Site address shall be provided and easily visible from street. Building and unit
numbers are posted.
Inspector Comments:
Vent termination covers between buildings shall be metal with damper and cover
opening downward.
Inspector Comments:
02/08/2018FailQuinton OwensCommercial Building Final
1102 missing living rm sprinkler escutcheon - also in 1202 hall closet.Inspector Comments:
Page 1 of 3
(Continued)
Permit Details Permit Number: 17-00285
398 Pioneer Rd - Rocky Ridge Apartments - Bldg 1 - 4 plex
398 Pioneer Rd
Multi-Family Residential
Permit Status of (Open) as of Report Date: 04/03/2019 11:17 am
Permit
Inspection
Summary
02/16/2018PassQuinton OwensCommercial Framing/Structure Inspection
02/16/2018FailQuinton OwensCommercial Building Final
* North main level unit fire rating at clean out under bathroom sink in rated party
wall is not completed.
* Metal clean out cover installed on south unit party wall - approved
Inspector Comments:
* Metal cleanout cover under bathroom sink in north unit required to protect
penetration. (completed per Ted)
* Site address is not posted (Minumum 4" tall numbers or larger if needed -
easily visible from street)
Inspector Comments:
02/26/2018FailQuinton OwensCommercial Building Final
Temporary occupancy approved. Post temporary address sign immediately if
waiting for permanent signage to completed.
Inspector Comments:
10/04/2018PassQuinton OwensCommercial Building Final
Electrical Inspection Type
10/25/2017PassBret StoddardCommercial Electrical Rough-in
11/27/2017PassBret StoddardCommercial Electrical Rough-in
01/16/2018PassBret StoddardResidential Electrical Service Inspection
02/01/2018PassBret StoddardResidential Electrical Final Inspection
Fire Inspection Type
10/24/2017PassDale PickeringFire Sprinkler Rough-in
01/29/2018FailBret StoddardFire Alarm Final Inspection
01/30/2018PassDale PickeringFire Sprinkler Final Inspection
01/30/2018PassBret StoddardFire Alarm Final Inspection
10/01/2018PassDale PickeringFire Department Inspection
10/09/2018PassDale PickeringFire Department Final Inspection
Mechanical Inspection Type
10/27/2017FailDon AllenHVAC Rough-in
10/30/2017PassDon AllenHVAC Rough-in
Good to cover the mechanical rough inInspector Comments:
02/26/2018PassDon AllenHVAC Final Inspection
Page 2 of 3
(Continued)
Permit Details Permit Number: 17-00285
398 Pioneer Rd - Rocky Ridge Apartments - Bldg 1 - 4 plex
398 Pioneer Rd
Multi-Family Residential
Permit Status of (Open) as of Report Date: 04/03/2019 11:17 am
Permit
Inspection
Summary
Planning & Zoning
03/07/2018PARTPASSQuinton OwensPlanning and Zoning Final Inspection
P&Z Final approved for temporary occupancy
* Landscaping to be done as soon as weather permits
* PUD requirements will be verified.
Inspector Comments:
Plumbing Inspection Type
08/24/2017PassDon AllenPlumbing Underground Inspection
09/19/2017PassDon AllenPlumbing Water
6 inch main water line held test good to coverInspector Comments:
10/20/2017PassDon AllenPlumbing Sewer
10/27/2017FailDon AllenPlumbing Rough-in
10/30/2017PassDon AllenPlumbing Rough-in
Good to cover the plumbing rough in on building 1Inspector Comments:
12/15/2017PassDon AllenPlumbing Water
Good to cover the water lineInspector Comments:
02/26/2018PassDon AllenPlumbing Final Inspection
Page 3 of 3