HomeMy WebLinkAboutINSPECTION SUMMARY - 17-00097 - 415 W 6th S - Falls Pointe Apt - 42 UnitsPermit
Inspection
Summary
Permit Status of (Open) as of Report Date: 03/27/2019 10:04 am
Permit Details Permit Number: 17-00097
415 Flats (Falls Pointe) - 42 Units
415 W 6th S
Multi-Family Residential
Permit Issued Date: 04/11/2017
Permit Inspection Statistics
73Total Inspections Completed:
34Total Inspections Passed:
Inspection Pass Rate: 46.58%
Permit Inspection History *Refer to Individual Inspection Report for more Details
01/03/2018PARTPASSJoel GrayPublic Works Final Inspection
1. Fire hydrant raised.
2. Water valves raised to final grade when landscaping completed.
3. Retention basin finished in spring.
4. Dumpster enclosure is 8" too narrow.
5. Existing driveway low back curb replaced with new high back curb.
Inspector Comments:
01/05/2018FailQuinton OwensPlanning and Zoning Final Inspection
Landscaping is not completed.
Approved only for temporary occupancy with landscaping requirements to be
inspected when done (no later than June 1,2018)
Inspector Comments:
06/19/2018PassQuinton OwensPlanning and Zoning Final Inspection
Landscaping will be completed by June 1, 2018Inspector Comments:
06/20/2018PassJoel GrayPublic Works Final Inspection
Building Inspection Type
05/02/2017PARTPASSTed DyeCommercial Footing Inspection
West half of footings inspected only.Inspector Comments:
05/04/2017PARTPASSQuinton OwensCommercial Footing Inspection
East side continuous footing onlyInspector Comments:
05/09/2017PARTPASSTed DyeFoundation Inspection
West,South and East wall complete.
North wall has an opening in center of wall to allow for trucks to pass through.
OK to pour those areas that have been formed.
Inspector Comments:
05/31/2017PassTed DyeCommercial Footing Inspection
06/02/2017PassTed DyeCommercial Footing Inspection
Interior footings on east side.Inspector Comments:
06/06/2017PassTed DyeCommercial Footing Inspection
Footing inspected; Center footing.Inspector Comments:
Page 1 of 5
(Continued)
Permit Details Permit Number: 17-00097
415 Flats (Falls Pointe) - 42 Units
415 W 6th S
Multi-Family Residential
Permit Status of (Open) as of Report Date: 03/27/2019 10:04 am
Permit
Inspection
Summary
06/09/2017PassTed DyeCommercial Footing Inspection
items inspected; Remainder of interior footings on the north end(Appox. 10'per
footing).
Exterior spot footings for columns.
Columns
Inspector Comments:
06/13/2017PassTed DyeCommercial Footing Inspection
08/25/2017FailQuinton OwensSheeting
SHEETING INSPECTION ON THE NORTH, EAST, AND SOUTH WALLS ONLY.
WEST WALL IS NOT READY
* A few locations are missing nailing (marked with pink paint on the outside at
main level and inside on the upper levels)
Inspector Comments:
09/13/2017FailTed DyeSheeting
Inspected the back side sheeting on levels 2 and 3
Those spots that missed having the sheeting nailed to the studs is marked with a
black marker.
The locations is marked on the door to the unit
Inspector Comments:
10/05/2017PARTPASSQuinton OwensCommercial Framing/Structure Inspection
Attic trusses only and top and bottom plate penetrations on 3rd level only.
* approved to hang ceiling on 3rd level
Inspector Comments:
10/05/2017PARTPASSQuinton OwensCommercial Insulation Inspection
Inspection in attic only prior to hanging top floor ceiling.
* approved to hang 3rd level ceiling only - attic insulation markers are needed.
Inspector Comments:
10/09/2017PARTPASSTed DyeCommercial Insulation Inspection
3rd Floor insulation inspection completed.Inspector Comments:
10/12/2017PARTPASSQuinton OwensSheeting
Roof sheeting only on building section east of breezeway.Inspector Comments:
10/16/2017PassTed DyeCommercial Framing/Structure Inspection
10/20/2017PARTPASSTed DyeCommercial Insulation Inspection
10/20/2017PARTPASSTed DyeCommercial Sheetrock/Drywall Inspection
Units 301, 302, 303, 304, 305, 306,307, 308 and 315 are approved to tape.Inspector Comments:
10/23/2017FailTed DyeCommercial Sheetrock/Drywall Inspection
10/24/2017PARTPASSTed DyeCommercial Sheetrock/Drywall Inspection
11/01/2017PARTPASSTed DyeCommercial Sheetrock/Drywall Inspection
11/03/2017PassJoel GraySidewalk Inspection
11/03/2017FailTed DyeCommercial Sheetrock/Drywall Inspection
11/06/2017PARTPASSTed DyeCommercial Insulation Inspection
Page 2 of 5
(Continued)
Permit Details Permit Number: 17-00097
415 Flats (Falls Pointe) - 42 Units
415 W 6th S
Multi-Family Residential
Permit Status of (Open) as of Report Date: 03/27/2019 10:04 am
Permit
Inspection
Summary
11/08/2017PARTPASSTed DyeCommercial Insulation Inspection
11/09/2017PARTPASSTed DyeCommercial Sheetrock/Drywall Inspection
11/09/2017PassTed DyeCommercial Insulation Inspection
11/13/2017FailTed DyeCommercial Sheetrock/Drywall Inspection
101 ApprovedInspector Comments:
11/16/2017PassTed DyeCommercial Insulation Inspection
Inspection included 1st floor hall and south stair tower.Inspector Comments:
11/16/2017PARTPASSTed DyeCommercial Sheetrock/Drywall Inspection
Rooms 106 and 112 have not been competed.Inspector Comments:
11/17/2017PassTed DyeCommercial Sheetrock/Drywall Inspection
12/01/2017PARTPASSTed DyeCommercial Framing/Structure Inspection
12/14/2017PARTPASSQuinton OwensCommercial Sheetrock/Drywall Inspection
First level corridor only:
* Rated ceiling approved for cover.
Inspector Comments:
01/03/2018FailTed DyeResidential Building Final
Units 201-215 and 301-315 Need to have the water lines coming from the water
heater and penetrating the corricor separation wall, Fire caulked.
Unit 201; The smoke detectors are not communicating with one another.
Call for a reinspection when items have been corrected.
Inspector Comments:
2nd and 3rd floors have passed and are ready to occupy.
!st floor to done at a later date
Stairs wells have been completed and serve as access to upper levels,(2nd and
3rd).
Inspector Comments:
01/04/2018PARTPASSTed DyeResidential Building Final
Landscaping to be done in the spring(buy the 1st of June).
Mail boxes are in the construction zone on level One. There must be a reprenitive
of Headwater present when the post person and the tenants deliver and get their
mail.
The parking lot will need to be done in the spring when weather allows.
Inspector Comments:
01/12/2018PARTPASSTed DyeCommercial Building Final
06/21/2018PassTed DyeCommercial Building Final
Page 3 of 5
(Continued)
Permit Details Permit Number: 17-00097
415 Flats (Falls Pointe) - 42 Units
415 W 6th S
Multi-Family Residential
Permit Status of (Open) as of Report Date: 03/27/2019 10:04 am
Permit
Inspection
Summary
Electrical Inspection Type
10/04/2017PARTPASSBret StoddardCommercial Electrical Rough-in
11/01/2017PARTPASSBret StoddardCommercial Electrical Rough-in
11/02/2017PARTPASSBret StoddardResidential Electrical Rough-in
11/16/2017PassBret StoddardCOM & MFR Electrical Service Inspection
11/16/2017PARTPASSBret StoddardCommercial Electrical Rough-in
12/13/2017PARTPASSBret StoddardCommercial Electrical Rough-in
12/21/2017FailBret StoddardCommerical Electrical Final Inspection
12/21/2017PassBret StoddardResidential Electrical Final Inspection
01/03/2018FailBret StoddardResidential Electrical Final Inspection
01/04/2018PARTPASSBret StoddardResidential Electrical Final Inspection
01/11/2018PassBret StoddardCommerical Electrical Final Inspection
Fire Inspection Type
10/09/2017PassDale PickeringFire Sprinkler Rough-in
12/11/2017PassDale PickeringFire Sprinkler Rough-in
12/11/2017FailDale PickeringFire Sprinkler Hydro
01/04/2018PARTPASSDale PickeringFire Sprinkler Final Inspection
1st floor needs sprinkler trims, system calculations.Inspector Comments:
01/04/2018PARTPASSDale PickeringFire Department Final Inspection
01/04/2018PassBret StoddardFire Alarm Final Inspection
01/09/2018PassDale PickeringFire Sprinkler Hydro
06/19/2018PARTPASSJoel GrayFire Underground Inspection
06/20/2018PassDale PickeringFire Sprinkler Final Inspection
Previously given only a part pass. Please indicate full approval status.Inspector Comments:
06/20/2018PassDale PickeringFire Department Final Inspection
Previously given only a part pass. Please indicate full approval status.Inspector Comments:
06/20/2018PassFireInspector UserFire Underground Inspection
Page 4 of 5
(Continued)
Permit Details Permit Number: 17-00097
415 Flats (Falls Pointe) - 42 Units
415 W 6th S
Multi-Family Residential
Permit Status of (Open) as of Report Date: 03/27/2019 10:04 am
Permit
Inspection
Summary
Mechanical Inspection Type
09/26/2017PassDon AllenHVAC Rough-in
10/20/2017PassDon AllenHVAC Rough-in
12/28/2017PassDon AllenHVAC Final Inspection
Good for the C/O on the 1st 2nd and 3rd floor.Inspector Comments:
01/09/2018PassDon AllenHVAC Final Inspection
Plumbing Inspection Type
05/22/2017PassDon AllenPlumbing Underground Inspection
Good to cover the plumbing undergroundInspector Comments:
06/08/2017PassDon AllenPlumbing Water
Good to cover the water line. Will need to see the pressure teat on the fire lineInspector Comments:
09/26/2017PassDon AllenPlumbing Rough-in
11/06/2017PassDon AllenPlumbing Rough-in
Good to cover the plumbing rough in on all floorsInspector Comments:
12/01/2017PassDon AllenPlumbing Rough-in
12/29/2017PassDon AllenPlumbing Final Inspection
01/09/2018PassDon AllenPlumbing Final Inspection
Page 5 of 5