HomeMy WebLinkAboutRESCHECK - 19-00142 - 576 E 5th S - New SFRCNJ/'REScheck Software Version 4.6.5
Compliance Certificate
Project SHAWN & HILARY JENSEN'S RESIDENCE
Energy Code:
2012 IECC
Location:
Rexburg, Idaho
Construction Type:
Single-family
Project Type:
New Construction
Conditioned Floor Area:
3,675 ft2
Glazing Area
10%
Climate Zone:
6 (8693 HDD)
Permit Date:
20
Permit Number:
Construction Site: Owner/Agent: Designer/Contractor:
576 EAST 5TH SOUTH
REXBURG,ID 83440
Compliance: Passes using UA trade-off
Compliance: 5.7% Better Than Code Maximum UA: 383 Your UA: 361
The % Better or Worse Than Code Index reflects how close to compliance the house is based on code trade-off rules.
It DOES NOT provide an estimate of energy use or cost relative to a minimum -code home.
Envelope Assemblies
Ceiling 1: Raised or Energy Truss
Wall 1: Wood Frame, 16" o.c.
Window 1: Vinyl/Fiberglass Frame:Double Pane with Low -E
Door 1: Glass
Wall 2: Wood Frame, 16" o.c.
Window 2: Vinyl/Fiberglass Frame:Double Pane with Low -E
Door 2: Solid
Wall 3: Wood Frame, 16" D.C.
Window 3: Vinyl/Fiberglass Frame:Double Pane with Low -E
Door 3: Solid
Wall 4: Wood Frame, 16" D.C.
Window 4: Vinyl/Fiberglass Frame:Double Pane with Low -E
Crawl 1: Solid Concrete or Masonry
Wall height: 3.0'
Depth below grade: 2.5'
Insulation depth: 3.0'
Project Title: SHAWN & HILARY JENSEN'S RESIDENCE
Data filename: JAREScheck FOR SHAWN AND HILARY JENSEN.rck
3,675
49.0
0.0
0.020
74
642
22.0
0.0
0.056
30
80
0.250
20
20
0.250
5
755
22.0
0.0
0.056
39
20
0.250
5
44
0.250
11
1,000
22.0
0.0
0.056
42
205
0.250
51
44
0.250
11
1,000
22.0
0.0
0.056
55
15
0.250
4
150
0.0
6.0
0.112
14
Report date: 03/21/19
Pagel of 9
Compliance Statement: The proposed building design described here is consistent with the building plans, specifications, and other
calculations submitted with the permit application. The proposed building has been designed to meet the 2012 IECC requirements in
REScheck Version 4.6.5 and to comply with the mandatory requirem " s h d in the REScheck Inspection Checklist.
CZV acv, q \ anSQ •� — D c,r VL .t' 1.
Name -Title �r Z 'Zs✓
Si aturre/ Daye
Project Title: SHAWN & HILARY JENSEN'S RESIDENCE Report date: 03/21/19
Data filename: J:REScheck FOR SHAWN AND HILARY JENSEN.rck Page 2 of 9
CREScheck Software Version 4.6.5
�(j Inspection Checklist
Energy Code: 2012 IECC
Requirements: 100.0% were addressed directly in the REScheck software
Text in the "Comments/Assumptions" column is provided by the user in the REScheck Requirements screen. For each
requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception
is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided.
Section
_
#
Pre-Inspection/Plan Review
& Req ID I_
103.1,
Construction drawings and
103.2
documentation demonstrate
[PRI]1
energy code compliance for the
lighting and mechanical systems.
building envelope.
103.1,
103.2,
403.7
[PR3]1
302.1,
403.6
[PR2]2
Plans Verified I Field Verified
ValueValue I Complies? Comments/Assumptions
Complies Requirement will be met.
E]Does Not
❑Not Observable Location on plans/spec: A-
303
- - - - -- --- - - -
Construction drawings and
_.--- - --
Not Applicable
- -- - -
documentation demonstrate
❑Complies
E]Does Not
Requirement will be met.
energy code compliance for
lighting and mechanical systems.
❑Not Observable
Location on plans/spec: M -
Systems serving multiple
Not Applicable
101
dwelling units must demonstrate
compliance with the IECC
Commercial Provisions.
Heating and cooling equipment is
sized per ACCA Manual S based
Heating.
Btu/hr
Heating: ❑Complies
Btu/hr
Requirement will be met.
on loads calculated per ACCA
Not
Manual J or other methods
Cooling;Does
Btu/hr
CoBt �hrg; ❑Not Observable
ation on plans/spec: M-
approved by the code official.
❑Not Applicable
1Loc
01
Additinnal
-.....1-......
I, High Impact (Tier 1) _2 Medium Impact (Tier 2)
-_ - -- - ; 3 . Low Impact (Tier 3) i
Project Title: SHAWN & HILARY JENSEN'S RESIDENCE
Data filename: JAREScheck FOR SHAWN AND HILARY JENSEN.rck
Report date: 03/21/19
Page 3 of 9
#
Foundation Inspection rians veririeo
Value
Field Verified li
Co mpes? Comments/Assumptions
'
& Req.ID
Value
(
p tions
402.2.10
[F07] i
-- ----------------------
Unvented crawl space wall R-
insulation R -value.
_- —
R- ❑Complies
-- —..— __-------
See the Envelope Assemblies
R-
R- ❑Does Not
table for values.
❑Not Observable
❑Not Applicable
3.2
[F08]1
Unvented crawl space wall
insulation installed per
_._
❑Complies
Requirement will be met.
A'
manufacturer's instructions.
❑Does Not
ONot Observable
Location on plans/spec: A-
__
ONot Applicable
301
2.2.10
[F09]1
Unvented crawl space continuous[]C
vapor retarder installed over
— — — --
omplies
-- _- --
Requirement will be met.
exposed earth, joints overlapped
❑Does Not
by 6 in. and sealed, extending at
ONot Observable
Location on plans/spec: A -
least 6 in. up and attached to the
ONot Applicable
303
wall.
402.2.9
[FO10]1
Unvented crawls wall
pace insulation depth of burial Or in•
_ -
in. OComplies
See the Envelope Assemblies
distance from top of wall.
ODoes Not
table for values.
�
ONot Observable
- - —
— — -_---- — —
ONot Applicable
3.2.1
[FO11]2
A protective covering is installed
to protect exposed exterior
— - — —
❑Complies
— -- o
Exceptidon: null.
insulation and extends a
ODoes Not
minimum of 6 in. below grade.
ONot Observable
- --
— --- --
ONot Applicable
3.8
[FO12]2
Snow- and ice -melting system—
controls installed.
— — — — -
OComplies
-
Exception: null.
[]Does Not
ONot Observable
[]Not Applicable
1 i High Impact (Tier 1) _. L2 Medium Impact (Tier 2) ) _ -
- — -- —_ 3 � Low Impact (Tier 3)
Project Title: SHAWN & HILARY)ENSEN'S RESIDENCE
Data filename: ):\REScheck FOR SHAWN AND HILARY)ENSEN.rck Report date: 03 4 of 9
Page 4 of 9
Section
#
Framing / Rough -In Inspection
Plans Verified Field Verified
& Req.ID
--
— ---
Value Value Complies?
Comments/Assumptions
02.1.1,
402.3.4
-
Door LI -factor.
_ -- ----
U ❑Complies
See the Envelope Assemblies
[FR1]1
ODoes Not
table for values.
❑Not Observable
'402.1-1,
Glazing U -factor (area -weighted
El Not Applicable
U __
402.3.1,
402.3.3,
average).
U ❑Complies
ODoes Not
See the Envelope Assemblies
table for values.
402.3.6,
i 402.5
❑Not Observable
1
[]Not Applicable
3
r
U -factors of fenestration products
are determined in accordance
❑Complies
Requirement will be met.
with the NFRC test procedure or
❑Does Not
taken from the default table.
❑Not Observable
Location on plans/spec: A-
402.4.1.1 Air barrier and thermal barrier
_ ❑Not Applicable
-� - - - -
601
[FR23]1
installed per manufacturer's
❑Complies
❑Does
Requirement will be met.
instructions.
Not
❑Not Observable Location on plans/spec: A-
--
402.4 .3
Fenestration that is not site built
❑Not Applicable
3
[FR20]1
is listed and labeled as meeting
AAMA
❑Com Plies
ODoes
Requirement will be meta
/WDMA/CSA 101/I.S.2/A440
Not
or has infiltration rates per NFRC
❑Not Observable
400 that do not exceed code
limits.
ONot Applicable
402.4.4
[FR16]2
IC -rated recessed lighting fixtures
sealed at housing/interior finish
❑Complies
Requirement will be met.
J
and labeled to indicate s2.0 cfm
❑Does Not
leakage at 75 Pa.
❑Not Observable
Location on plans/spec: E -
403.2.1
_ _- -- -----_____
Supply ducts in attics are _
R
_ __ _ __ __-. ❑Not Applicable
- - _. _ _ __.__ __ - _ _ -__
101
- --
[FR12]1
insulated to >_R-8. All other ducts
R ❑Complies
- - - _
Requirement will be met.
in unconditioned spaces or R-
R- ODoes Not
outside the building envelope are
ONot Observable
Location on plans/spec: M -
insulated to _>R-6,
❑Not Applicable
101
403.2.2
All joints and seams of air ducts,
[FR13]1
air handlers, and filter boxes are
❑Complies
_ _
Requirement will be met.
sealed.
❑Does Not
ONot Observable
Location on plans/spec: M-
_.
403.2 3
------------ - - - - - -
Building cavities are not used as
- - ------ _ ❑Not Applicable
- - - - - - - - ------------
101
[FR15)3
ducts or plenums.
❑Complies
_. _ _ ___-_
Requirement will be met.
0Does Not
❑Not Observable
Location on plans/spec: M-
403.3
HVAC piping conveying fluids R_
_ ❑Not Applicable
101
[FR17]1
above 105 QF or chilled fluids
_
❑Com lies
R p
Exception: null.
below 55 QF are insulated to >_R-
❑Does Not
3.
❑Not Observable
403.31
_ - -- - - - -
Protection of insulation on HVAC
- - -ONot Applicable
[FR24]1
piping.
[]Complies
❑Does Not
Requirement will be met.
❑Not Observable
Location on plans/spec: M-
403.4.2
Hot water pipes are insulated to R
_ ❑Not Applicable
- --
101
[FR18]2
>_R-3.
R- ❑Complies
❑Does Not
Requirement will be met.
ONot Observable
Location on plans/spec. M -
[]Not Applicable
101
1 High Impact (Tier 1) 2 Medium Impact (Tier 2) 3 1 Low Impact (Tier 3) i
Project Title: SHAWN & HILARY JENSEN'S RESIDENCE
Data filename: J:\REScheck FOR SHAWN AND HILARY JENSEN.rck Report date: 03/21/19
Page 5 of 9
# !Framing /Rough-In Inspection Plans Verified Field Verified
& Req.ID I Value Value Complies? Comments/Assumptions
_-- — _ __
403.5 Automatic or gravity dampers are _ —" G
(FR19)1 installed on all outdoor air ❑Complies Requirement will be met.
intakes and exhausts. E]Does Not
Location on plans/spec: M-
❑Not Observable 101
_ ❑Not Applicable
Additional Comments/Assumptions:
Ll I High Impact (Tier 10 2 Medium Impact (Tier 2) 3 Low Impact (Tier 3)
Project Title: SHAWN & HILARY JENSEN'S RESIDENCE
Data filename: JAREScheck FOR SHAWN AND HILARY JENSEN.rck Report date: 03/21/19
Page 6 of 9
Section
# Insulation Inspection
& Req.ID
Plans Verified
ValueValue
; Field Verified
Complies?
i Comments/Assumptions
303.1 All installed insulation is labeled—
[IN13]2 or the installed R -values
❑Complies
Requirement will be met.
e, provided.
❑Does Not
❑Not Observable
402.1.1, Wall insulation R -value. If this is a
R-
❑Not Applicable
402.2.5, mass wall with at least 1/2 of the
402.2.6 wall insulation on the wall
❑ Wood
R-
❑ Wood
❑Complies
❑Does Not
See the Envelope Assemblies
table for values.
[IN311 exterior, the exterior insulation
❑ Mass
❑ Mass
❑Not Observable
requirement applies (FR10).
❑ Steel
❑ Steel
❑Not Applicable
303.2 Wall insulation is installed per
[IN4)1 manufacturer's instructions. ❑Complies Requirement will be met.
❑Does Not
❑Not Observable Location on plans/spec: A-
�
Additional Comments/Assumptions: ❑Not Applicable
1 High Impact (Tier 1) 2 Medium Impact (_Tier 2) 3 ;Low Impact (Tier 3)
- -- - -
— — — _ _
Project Title: SHAWN & HILARY JENSEN'S RESIDENCE
Data filename: J:\REScheck FOR SHAWN AND HILARY JENSEN.rck Report date: 03/21/19
Page 7 of 9
Section
Final Inspection Provisions
& Req.ID
402.1.1, Ceiling insulation R -value.
402.2.1,
402.2.2,
402.2.6
[Fill'
a,
Plans Verified ' Field Verified
Value Value Complies?
R- R- - -❑Complies
❑ Wood ❑ Wood ❑Does Not
❑ Steel ❑ Steel
❑Not Observable
❑Not Applicable
Comments/Assumptions
See the Envelope Assemblies
table for values.
1.1.1,
303.2
Ceiling insulation installed per
manufacturer's instructions.
❑Complies
❑Does Not
Requirement will be met
[FI2]'
Blown insulation marked every
300 ftZ.
❑Not Observable
Location on plans/spec: A-
❑Not Observable
❑Not Applicable
303
402.2.3
s [FI22]2
Vented attics with air permeable
insulation include baffle adjacent
❑Complies
❑Does Not
Requirement will be met.
I
to soffit and eave vents that
extends over insulation.
❑Not Observable
Location on plans/spec: C -
— -- --
--- --- --- -- - - ---_ __-- ____. _
❑Not Applicable
101
14 02.2.4
[FI3]'
Attic access hatch and door R-
insulation >_R -value of the
R- ❑Complies
Requirement will be met.
adjacent assembly.
❑Does Not
Location on plans/spec: S-
EObservable
❑Not Applicable
104
4.1.2
[FI17]'
Blower door test @ 50 Pa. <=5 ACH 50 =
ach in Climate Zones 1-2, and
ACH 50 = ❑Complies
Requirement will be met.
<=3 ach in Climate Zones 3-8.
❑Does Not
❑Not Observable
Location on plans/spec: M -
❑Not Applicable
101
403.2.2
[FI4]'
Duct tightness test result of <=4 cfm/100
cfm/100 ft2 across the system or ft2
cfm/100 ❑Complies
ft2
Requirement will be met.
<=3 cfm/100 ft2 without air
handler @ 25 Pa. For rough -in
❑Does Not
❑Not Observable
Location on plans/spec: M -
tests, verification may need to
❑Not Applicable
101
-
occur during Framing Inspection.
3.2.2.1
[FI24]'
Air handler leakage designated
by manufacturer at <=2% of
❑Complies
Requirement will be met.
design air flow.
❑Does Not
❑Not Observable
Location on plans/spec: M -
-- - - -----
--- --
❑Not Applicable
101
403 .1
(FI9] z
Programmable thermostats
installed on forced air furnaces.
--
❑Complies
- - -- - - - - - - --
Requirement will be met.
❑Does Not
❑Not Observable
Location on plans/spec: M -
❑Not Applicable
101
3.1.2
[FI10]2
Heat pump thermostat installed-
on heat pumps.
- - - -
❑Complies
x - .-
Exception: null.
❑Does Not
M
403.4.1 Circulating service hot water
[FIll]2 systems have automatic or
accessible manual controls.
403.5.1 All mechanical ventilation system
[FI25]2 fans not part of tested and listed
HVAC equipment meet efficacy
and air flow limits.
4U4.1 i51/o of lamps in permanent
[F16]' fixtures or 75% of permanent
fixtures have high efficacy lamps.
- Does not apply to low -voltage
lighting.
❑Not Observable
❑Not Applicable
❑Complies
Exception: null.
❑Does Not
❑Not Observable
❑Not Applicable
❑Complies
❑Does Not
Exception: null.
❑Not Observable
❑Not Applicable
❑Complies
Requirement will be met.
❑Does Not
❑Not Observable
Location on plans/spec: E- j
❑Not Applicable
101
1 ,High Impact (Tier 1) 2 Medwm Impact (Tier 2) 3 Low Impact (Tier 3)
Project Title: SHAWN & HILARY JENSEN'S RESIDENCE Report date: 03/21/19
Data filename: J:\REScheck FOR SHAWN AND HILARY JENSEN.rck Page 8 of 9
2012 IECC Energy
Efficiency Certificate
Above -Grade Wall
22.00
Below -Grade Wall
6.00
Floor
0.00
Ceiling / Roof
49.00
Ductwork (unconditioned spaces):
,Glass & Door Rating
Window
0.25
Door
0.25
.: Cooling
Heating System:
Cooling System:
Water Heater:_ t
Name:
Date:
_
Comments