Permit Status of (Open) as of Report Date: 03/12/2019 10:27 am
Permit Details Permit Number: 13-00036
15 Madison Professional Park - Madison Women's Clinic Remodel
15 Madison Professional Park
Commercial Remodel
Permit Issued Date: 06/12/2013
Permit Inspection Statistics
10Total Inspections Completed:
8Total Inspections Passed:
Inspection Pass Rate: 80.00%
Permit Inspection History *Refer to Individual Inspection Report for more Details
06/12/2013FailBret StoddardElectrical Rough-in
Patient care areas are required to be wired with a metallic raceway system for
the exam, procedure, etc. for all new wiring added, call for a re-inspect when
ready.
Inspector Comments:
06/13/2013PassBret StoddardElectrical Rough-in
Approved for cover in the west portion remodel upstairs on the north end-exam
rooms(2), procedure room, nurses station and bathroom-as Per Jane Shaw.
Inspector Comments:
06/14/2013FailQuinton OwensSheetrock/Drywall Inspection
6/12,QO: Main floor framing approved by front entry.Inspector Comments:
07/26/2013PassQuinton OwensFraming/Structure Inspection
7/26,QO: North end Framing (main floor) approved.Inspector Comments:
09/24/2013PassDon AllenPlumbing Rough-in
09/25/2013PassBret StoddardElectrical Final Inspection
Approved for a final-remodeled portions.Inspector Comments:
09/26/2013PassQuinton OwensBuilding Final
Furnace: seal round gas pipe at furnace.
Action Required: see above, email quintono@rexburg.org
Side note: Exhaust fan added upstairs (where does it terminate?)
Inspector Comments:
6/14, QO: Failed drywall inspection for NW section of main floor (SE room not
hung at time of inspection).
Inspector Comments:
09/26/2013PassQuinton OwensSheetrock/Drywall Inspection
9/26,QO: no fire separation required. No inspection requested for north end
drywall. Approved without inspection.
Inspector Comments:
03/24/2015PassDon AllenHVAC Final Inspection
GOOD FOR THE C/OInspector Comments:
Plumbing Inspection Type
09/24/2013PassDon AllenPlumbing Final Inspection
all good for C/O.Inspector Comments: