Permit Status of (Open) as of Report Date: 03/06/2019 11:23 am
Permit Details Permit Number: 12-00072
Brighton Townhomes Recreation Building
242 W 6th S
Building - Commercial
Permit Issued Date: 05/30/2014
Permit Inspection Statistics
21Total Inspections Completed:
17Total Inspections Passed:
Inspection Pass Rate: 80.95%
Permit Inspection History *Refer to Individual Inspection Report for more Details
Building Inspection Type
04/04/2012PassQuinton OwensFooting Inspection
Rebar clean, supported and meets clearance requirement.Inspector Comments:
04/06/2012PassQuinton OwensFoundation Inspection
horz rebar 2' o.c.
vert rebar ~18" o.c.
Inspector Comments:
4/19/12 QO: Sheeting - missed nailing under front window north side of door;
next to front door to storage room; south wall in bathroom.
-need stud over joint on south wall.
Inspector Comments:
05/09/2012PassQuinton OwensFraming/Structure Inspection
5/9/12 QO: firewall - 5/8" type x on exterior of back wall complete.Inspector Comments:
06/22/2012FailPLL ADMINFraming/Structure Inspection
-Trusses not braced per truss details.
-Could not get into crawl space.
-Crawl space access NOT per code (size)
-Could not check sheathing for nailing on hard downs.
As per Jon Berry.
Inspector Comments:
06/27/2012PassQuinton OwensFraming/Structure Inspection
Framing items completed
crawl space NOT inspected (need ladder)
Action required: -crawl space inspection fro framing.
-weep holes in masonry per IBC.
Inspector Comments:
06/29/2012PassQuinton OwensInsulation Inspection
Windows and doors sealed
u-factor = .34
Blown ins in exterior walls.
Empire model DVD42FP30N
Action required: Clear insulation form behind fireplace unless 0" clearance is
allowed.
Inspector Comments:
Page 1 of 3
(Continued)
Permit Details Permit Number: 12-00072
Brighton Townhomes Recreation Building
242 W 6th S
Building - Commercial
Permit Status of (Open) as of Report Date: 03/06/2019 11:23 am
Permit
Inspection
Summary
07/03/2012PassQuinton OwensSheetrock/Drywall Inspection
Ok to tape drywall.
Add screws to a couple missed locations. (indicated over phone).
Inspector Comments:
08/22/2012FailQuinton OwensBuilding Final
-Grab bar correction in bathroom
-sign by stove "for warming only."
-Crawl space insulation needed at SW and NW corners, and at foundation corner
between study rm and main area.
(at floor joist)
Inspector Comments:
08/23/2012PassQuinton OwensSidewalk Inspection
08/27/2012PassQuinton OwensBuilding Final
Temp approval
call when sign for stove is ready. Will check insl. in craw space as well
(no ladder right now).
Inspector Comments:
Electrical Inspection Type
02/23/2012PassBret StoddardCommercial Electrical Rough-in
approved for cover.Inspector Comments:
05/23/2012PassBret StoddardCOM & MFR Electrical Service Inspection
Service approved to be energized for permanent power.Inspector Comments:
07/18/2012PassBret StoddardCOM & MFR Electrical Service Inspection
approved to remain energized for permanent power.
Changed panel for higher AIC rated breaker.
Inspector Comments:
08/03/2012PassBret StoddardCOM, COM-A, COM-R, and COM-T Electrical Final Inspection
Approved for a final and C.O.Inspector Comments:
Fire Inspection Type
10/17/2012PassQuinton OwensFire Department Final Inspection
Fire extinguishers √
Emergency lights √
Exit signs √
OK
Inspector Comments:
Page 2 of 3
(Continued)
Permit Details Permit Number: 12-00072
Brighton Townhomes Recreation Building
242 W 6th S
Building - Commercial
Permit Status of (Open) as of Report Date: 03/06/2019 11:23 am
Permit
Inspection
Summary
Mechanical Inspection Type
06/22/2012PassPLL ADMINHVAC Rough-in
HVAC and gas line looked good EXCEPT crawl space NOT checked.
As per Jon Berry.
Inspector Comments:
08/22/2012FailQuinton OwensHVAC Final Inspection
-Grab bar correction in bathroom
-sign by stove "for warming only."
-Crawl space insulation needed at SW and NW corners, and at foundation corner
between study rm and main area.
(at floor joist)
Inspector Comments:
08/27/2012PassQuinton OwensHVAC Final Inspection
Plumbing Inspection Type
04/24/2012FailDon AllenPlumbing Rough-in
Need to put clean out under the kitchen sink extended out 3" clean out.Inspector Comments:
05/03/2012PassDon AllenPlumbing Rough-in
09/07/2012PassDon AllenPlumbing Final Inspection
All good for C/OInspector Comments: