HomeMy WebLinkAboutRESCHECK - 17-00208 - 656 Hillside Dr - New SFRCGenerated by REScheck-Web Software
�J( Compliance Certificate
Project
Energy Code:
2012 IECC
Location:
Rexburg, Idaho
Construction Type:
Single-family
Project Type:
New Construction
Conditioned Floor Area:
5,975 ft2
Glazing Area
13%
Climate Zone:
6 (8693 HDD)
Permit Date:
Permit Number:
Construction Site:
Owner/Agent:
Designer/Contractor:
Compliance: Passes using UA trade-off
Compliance: 14.2% Better Than Code Maximum UA: 599 Your UA: 514
The % Better or Worse Than Code Index reflects how close to compliance the house Is based on code trade-off rules.
It DOES NOT provide an estimate of energy use or cost relative to a minimum -code home.
Envelope Assemblies
Ceiling: Flat or Scissor Truss 5,975 19.0 50.0 0.014 84
Wall: Wood Frame, 161n. o.c. 3,150 21.0 0.0 0.057 151
Window: Vinyl Frame, 2 Pane w/ Low -E 400 0.350 140
Door: Solid 96 0.300 29
Basement: Solid Concrete or Masonry 3,150 13.0 13.0 0.035 110
Wall height: 9.0'
Depth below grade: 6.0'
Insulation depth: 9.0'
Compliance Statement., The proposed building design described here is consistent with the building plans, specifications, and other
calculations submitted with the permit application. The proposed building has been designed to meet the 2012 IECC requirements in
REScheck Version 5.5.0 and to comply with the mandatory requirements listed in the REScheck Inspection Checklist.
Project Title: Report date: 04/21/17
Data filename: Page 1 of 8
CREScheck Software Version 5.5.0
�J( Inspection Checklist
Energy Code: 2012 IECC
Requirements: 0.0% were addressed directly in the REScheck software
Text in the "Comments/Assumptions" column is provided by the user in the REScheck Requirements screen. For each
requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception
is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided.
Section
#
Pre-Inspection/Plan Review
Plans Verifled
Value
Fleld Verified
Value
CompliesT Comments/Assumptions
& Re .ID
103.1,
Construction drawings and
❑Complies
103.2
documentation demonstrate
❑Does Not
[PRI]1
energy code compliance for the
❑Not Observable
,10
building envelope.
❑Not Applicable
103.1,
-Construction drawings and
❑Complies
103.2,
documentation demonstrate
''❑Does Not
403.7
energy code compliance for
❑Not Observable
[PR3]1
lighting and mechanical systems.
❑Not Applicable
.Q,
Systems serving multiple
dwelling units must demonstrate
compliance with the IECC
Commercial Provisions.
302.1,
Heating and cooling equipment is
Heating:
Heating:
❑Complies
403.6
sized per ACOA Manual S based
Btu/hr
Btu/hr
❑Does Not
[PR2]2
on loads calculated per ACCA
Cooling:
Cooling:
❑Not Observable
Manual J or other methods
Btu/hr _
Btu/hr_
❑Not Applicable
approved by the code official.
Additional Comments/Assumptions:
11 High Impact (Tier 1)2 Medium Impact (Tier 2) 3 1 Low Impact (Tier 3)
Project Title: Report date: 04/21/17
Data filename: Page 2 of 8
Section
#
Foundation Inspection
Plans Verified
Value
Field Verified
Value
Compliest
Comments/Assumptions
& Req.ID
402.1.1
Conditioned basement wall R-_
R- ❑Complies
see the Envelope Assemblies
[FO411
insulation R -value. Where interior R-
R- ❑Does Not
.table for values.
40
in is used, verification
❑Not Observable
may need to occur during
Insulation Inspection. Not
❑Not Applicable
required in warm -humid locations
in Climate Zone 3.
303.2
Conditioned basement wall
.❑complies
(FO511
Insulation Installed per
❑Does Not
manufacturer's instructions.
❑Not Observable
❑Not Applicable
402.2.8
Conditioned basement wall ft
ft ❑Compiles
see the Envelope Assemblies
[FO611
insulation depth of burial or
❑Does Not
table for values.
distance from top of wall.
❑Not Observable
❑Not Applicable
303.2.1
A protective covering is installed
❑Complies
[FO11]1
to protect exposed exterior
❑Does Not
insulation and extends a
'❑Not Observable
minimum of 6 in. below grade.
❑Not Applicable
403.8
Snow- and Ice -melting system
❑complies
[F01212
controls installed.
❑Does Not
�'-
❑Not Observable
❑Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1) -`;: Medium Impact (Tier 2) 3 1 Low Impact (Tier 3)
Project Title: Report date: 04/21/17
Data filename: Page 3 of 8
Section
#
& Re .ID
Framing / Rough -In Inspection
plans Verified
Value
Field Verified
Value
Complies?
Comments/Assumptions
402.1.1,
402.3.4
Door U -factor.
U- U- —
❑Complles
See the Envelope Assemblies
[FR1]1
❑Does Not
table for values.
:$.
❑Not Observable
❑Not Applicable
402.1.1,.
402.3.1,
aU-factor (area -weighted
averag
average),
e).
U- U-_
❑Complles
See the Envelope Assemblies
402.3.3,
-
❑Does Not
table for values.
402.3.6,
❑Not Observable
402.5
❑Not Applicable
PP
[FR211
d
303.1,3
U -factors of fenestration products
❑Complies
[FR411
are determined in accordance
❑Does Not
with the NFRC test procedure or
taken from the default table.
❑Not Observable
❑Not Applicable
402.4.1.1
Air barrier and thermal barrier
❑Complies
[FR2311 installed
per manufacturer's
❑Does Not
instructions.
❑Not Observable
❑Not Applicable
402.4.3 Fenestration that is not site built
❑Complies
[FR20] is listed and labeled as meeting
❑Does Not
AAMA/WDMA/CSA 101/1.5.2/A440
or has infiltration rates per NFRC
❑Not Observable
400 that do not exceed code
❑Not Applicable
limits.
402.4.4 IC
-rated recessed lighting fixtures
❑Complies
[FR16] sealed at housing/interior finish
❑Does Not
AP and labeled to indicate 252.0 cfm
leakage at 75 Pa.
❑Not Observable
❑Not Applicable
403.2.1 Supply ducts in attics are
1
R-R-- ❑Complies
[FR12] insulated to aAll other ducts
R- R❑Does Not
-
Ur in
unconditioneded spaces or
—
outside the building envelope are
❑Not Observable
insulated to 2-11-6.
❑Not Applicable
403.2.2 All joints and seams of air ducts,
❑Complies
FR1311 air
handlers, and filter boxes are
-.❑Does Not
.sealed.
`..❑Not
Observable
❑Not Applicable
403.2.3 Building
cavities are not used as
❑Complies
[F111511 ducts
or plenums.
❑Does Not
❑Not Observable
❑Not Applicable
403.3HVAC piping conveying fluids
R-- R-- ❑Complles
[FR17]1 above 105 QF or chilled fluids
❑Does
Not
VV below 55 QF are Insulated to a:R-
3.
❑Not Observable
❑Not Applicable
403.3.1 Protection of insulation on HVAC
❑Complies
[FR24]1 piping.
❑Does Not
❑Not Observable
. ❑Not Applicable
403.4.2 Hot water pipes are insulated to
R- R- ❑Complies
[FR1811 Z-11-3.0Does
Not
J
❑Not Observable
❑Not Applicable
1 High Impact (Tier 1) 2'. Medium Impact (Tier 2) 3 Low Impact (Tier 3)
Project Title:
Data filename: Report date: 04/21/17
Page 4 of 8
# Framin / Rou h -in Ins ection plans Verified Field Verified
,,, 9 g p Value Value Complies? Comments/Assumptions
403.5 Automatic or gravity dampers are
[FR19]2 installed on all outdoor air
,Nr intakes and exhausts.
Additional Comments/Assumptions:
❑Does Not
❑Not Observable
❑Not Applicable
1 I High Impact (Tier 1) 2 Medium Impact (Tier 2) 1 3 1 Low Impact (Tier 3)
Project Title: Report date: 04/21/17
Data filename: Page 5 of 8
--W—
Insulation Ins ection
P
Plans Verified
Value
Field Verified
Value
Complies.
Comments/Assumptions
& Req. ID
303.1
All installed insulation is labeled
❑Complles
[IN13]2
or the installed R -values
❑Does Not
provided.
❑Not Observable
❑Not Applicable
402.1.1,
Wall insulation R -value. If this is a
R-
R-
❑Complies See the Envelope Assemblies
402.2.5,
mass wall with at least Y2 of the
❑ Wood
❑ Wood
❑Does Not table for values.
402.2.6
[IN3]1
wall insulation on the wall
exterior, the exterior insulation
❑ Mass
❑ Mass
❑Not Observable
;y)
requirement applies (FR10).
❑ Steel
❑ Steel
❑Not Applicable
303.2
Wall insulation is installed per
❑Complies
[IN4)1
,manufacturer's instructions.
❑Does Not
❑Not Observable
❑Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1) ,: Medium Impact (Tier 2) 3 Low Impact (Tier 3)
Project Title: Report date: 04/21/17
Data filename: Page 6 of 8
Section
#
Final inspection Provisions
Plans Verified
Value
Field Verified
Value
Complies?
Comments /Assumptions
& Re .ID
402.1.1,
Ceiling insulation R -value.
R-
R-_ ❑Complies see the Envelope Assemblies
402.2.1,
❑ Wood
❑ Wood ❑Does Not table for values.
402'2'2'
402.2.6
❑ Steel
E] Steel ❑Not Observable
[Fill'
❑Not Applicable
303.1.1.1,
Ceiling insulation installed per
❑compiles
303.2
manufacturer's instructions.
❑Does Not
[FI2]1
Blown insulation marked every
300 W.
❑Not Observable
________
❑Not Applicable
402 2.3
Vented attics with air permeable
❑Complies
[F[22]2
insulation include baffle adjacent
❑Does Not
to soffit and eave vents that
extends over Insulation.
❑Not Observable
❑Not Applicable
402.2.4
Attic access hatch and door
R-_
R-_ ❑Complies
[FI3]1
insulation aR-value of the
❑Does Not
adjacent assembly.
❑Not Observable
❑Not Applicable
402.4.1.2
Blower door test @ 50 Pa. <=5
ACH 50 =_
ACH 50 = ❑complies
[FI17]1
ach in Climate Zones 1-2, and
- ❑Does Not
0
<=3 ach in Climate Zones 3-8.
❑Not Observable
❑Not Applicable
403.2.2
Duct tightness test result of <=4
cfm/100
cfm/100 ❑complies
[FI4]1
cfm/100 ft2 across the system or
ftz
ft2 ❑Does Not
<=3 cfm/100 ft2 without air
handler @ 25 Pa. For rough -in
❑Not Observable
tests, verification may need to
❑Not Applicable
occur during Framing Inspection.
403.2.2.1 .Air
handler leakage designated
❑Complies
[FI2411
by manufacturer at <=2% of
❑Does Not
design air flow.
❑Not Observable
❑Not Applicable
403.1.1
Programmable thermostats
❑Complies
[FI9]1
installed on forced air furnaces.
❑Does Not
IV
❑Not Observable
❑Not Applicable
403.1.2
-----—---_.
Heat pump thermostat Installed
_._. -------...-----
❑Complies
[FI10]2
on heat pumps.
❑Does Not
Ul
❑Not Observable
❑Not Applicable
403.4.1
Circulating service hot water
❑Complies
[FI11]2
systems have automatic or
❑Does Not
u
accessible manual controls.
❑Not Observable
_
❑Not Applicable
403.5.1
All mechanical ventilation system
❑Complies
[FI25]2
fans not part of tested and listed
❑Does Not
HVAC equipment meet efficacy
and air flow limits.
❑Not Observable
❑Not Applicable
404.1
75% of lamps in permanent
❑Complies
[FI611
fixtures or 75% of permanent
❑Does Not
V, ',fixtures
have high efficacy lamps.
Does not apply to low -voltage
❑Not Observable
'..lighting.
❑Not Applicable
1 I High Impact (Tier 1) 2 1 Medium Impact (Tier 2) 3 1 Low Impact (Tier 3)
Project Title: Report date: 04/21/17
Data filename: Page 7 of 8
--
#
Final Inspection Provisions
Plans Verified
Value
Field Verified
Value
Complies?
Comments/Assumptions
& Reg.ID
404.1.1
Fuel gas lighting systems have
❑complies
[FI2313
no continuous pilot light.
❑Does Not
❑Not Observable
❑Not Applicable
401.3
Compliance certificate posted.
❑Compiles
[FI712
- ❑Does Not
❑Not Observable
❑Not Applicable
3033
Manufacturer manuals for
- ❑Complies
[FI18]3
mechanical and water heating
❑Does Not
systems have been provided.
❑Not Observable
❑Not Applicable
Additional Comments/Assumptions:
1 I High Impact (Tier 1) 1 2 1 Medium Impact (Tier 2) -3; Low Impact (Tier 3)
Project Title: Report date: 04/21/17
Data filename: Page 8 of 8
fz2012 IECC Energy
Efficiency Certificate
Insulation Rating R -Value
Above -Grade Wall 21.00
Below -Grade Wall 26.00
Floor 0.00
Ceiling / Roof 65.00
Ductwork (unconditioned spaces):
Glass & Door Rating U -Factor SHGG
Window 0.35
Door 0.30
Heating System:
Cooling System:
Water Heater:
Name: Date:
Comments