HomeMy WebLinkAboutPLANS - 19-00085 - 279 Rodney Dr - Solar PanelsSHEET INDEX PV1 - COVER SHEET PV2 - PROPERTY PLAN PV3 - SITE PLAN PV4 - EQUIPMENT & ATTACHMENT DETAIL PV5 - ELECTRICAL SINGLE LINE DIAGRAM PV6 - ELECTRICAL CALCULATIONS & ELECTRICAL NOTES PV7 - MAIN BREAKER DERATE CALCS. (IF NEEDED) PV8 - LABELS & LOCATIONS PV9 - STRING & SE OPTIMIZER PV10 - CUSTOM DIRECTORY PLACARD(IF NEEDED - NEC 690.56(B)) GENERAL NOTES SITE SPECIFICATIONS OCCUPANCY - R3 CONSTRUCTION - V-B ZONING: RESIDENTIAL SCOPE OF WORK INSTALLATION OF UTILITY INTERACTIVE PHOTOVOLTAIC SOLAR SYSTEM 5.7 kW DC PHOTOVOLTAIC SOLAR ARRAY ROOF TYPE: Comp Shingle MODULES: (19) Trinasolar 300 TSM-DD05A.08(II) INVERTER(S): Enphase IQ7-60-2-US,---- RACKING: Unirac Sunframe Microrail Mounting & Racking System AERIAL VIEW SITE NOTES / OSHA REGULATION 1. A LADDER SHALL BE IN PLACE FOR INSPECTION IN COMPLIANCE WITH OSHA REGULATIONS. 2. THE PV MODULES ARE CONSIDERED NON-COMBUSTIBLE AND THIS SYSTEM IS AN UTILITY INTERACTIVE SYSTEM WITH NO STORAGE BATTERIES. 3. THE SOLAR PV INSTALLATION SHALL NOT OBSTRUCT ANY PLUMBING, MECHANICAL, OR BUILDING ROOF VENTS. 4. ROOF COVERINGS SHALL BE DESIGNED, INSTALLED, AND MAINTAINED IN ACCORDANCE WITH THIS CODE AND THE APPROVED MANUFACTURER'S INSTRUCTIONS SUCH THAT THE ROOF COVERING SHALL SERVE TO PROTECT THE BUILDING OR STRUCTURE. SOLAR CONTRACTOR 1. MODULE CERTIFICATIONS WILL INCLUDE UL1703, IEC61646, IEC61730. 2. IF APPLICABLE, MODULE GROUNDING LUGS MUST BE INSTALLED AT THE MARKED GROUNDING LUG HOLES PER THE MANUFACTURERS' INSTALLATION REQUIREMENTS. 3. AS INDICATED BY DESIGN, OTHER NRTL LISTED MODULE GROUNDING DEVICES MAY BE USED IN PLACE OF STANDARD GROUNDING LUGS AS SHOWN IN MANUFACTURER DOCUMENTATION AND APPROVED BY THE AHJ. 4. CONDUIT AND WIRE SPECIFICATIONS ARE BASED ON MINIMUM CODE REQUIREMENTS AND ARE NOT MEANT TO LIMIT UP-SIZING AS REQUIRED BY FIELD CONDITIONS. 5. CONDUIT POINT OF PENETRATION FROM EXTERIOR TO INTERIOR TO BE INSTALLED AND SEALED WITH A SUITABLE SEALING COMPOUND. 6. DC WIRING LIMITED TO MODULE FOOTPRINT W/ ENPHASE AC SYSTEM. 7. ENPHASE WIRING SYSTEMS SHALL BE LOCATED AND SECURED UNDER THE ARRAY W/ SUITABLE WIRING CLIPS. 8. MAX DC VOLTAGE CALCULATED USING MANUFACTURER PROVIDED TEMP COEFFICIENT FOR VOC UNLESS NOT AVAILABLE. 9. ALL INVERTERS, MOTOR GENERATORS, PHOTOVOLTAIC MODULES, PHOTOVOLTAIC PANELS, AC PHOTOVOLTAIC MODULES, DC COMBINERS, DC-TO-DC CONVERTERS,SOURCE CIRCUIT COMBINERS, AND CHARGE CONTROLLERS INTENDED FOR USE IN A PHOTOVOLTAIC POWER SYSTEM WILL BE IDENTIFIED AND LISTED FOR THE APPLICATION PER 690.4 (B). 10. ALL SIGNAGE TO BE PLACED IN ACCORDANCE WITH LOCAL BUILDING CODE. EQUIPMENT LOCATIONS 1. PROPER ACCESS AND WORKING CLEARANCE AROUND EXISTING AND PROPOSED ELECTRICAL EQUIPMENT WILL BE PROVIDED AS PER SECTION [NEC 110.26]. 2. EQUIPMENT INSTALLED IN DIRECT SUNLIGHT MUST BE RATED FOR EXPECTED OPERATING TEMPERATURE AS SPECIFIED BY [NEC 690.31 (A)-(B)] AND [NEC TABLE 310.15 (B)]. 3. ADDITIONAL AC DISCONNECTS SHALL BE PROVIDED WHERE THE INVERTER IS NOT ADJACENT TO THE UTILITY AC DISCONNECT, OR NOT WITHIN SIGHT OF THE UTILITY AC DISCONNECT. 4. ALL EQUIPMENT SHALL BE INSTALLED ACCESSIBLE TO QUALIFIED PERSONNEL ACCORDING TO NEC APPLICABLE CODES. 5. ALL COMPONENTS ARE LISTED FOR THEIR PURPOSE AND RATED FOR OUTDOOR USAGE WHEN APPROPRIATE. DATE DRAWING BY PROJECT NUMBER SHEET NAME PAGE NUMBER REVISION 1220 S. 630 E STE. 430 AMERICAN FORK, UT 84003 800-377-4480 WWW.BLUERAVENSOLAR.COM CONFIDENTIAL - THE INFORMATION HEREIN CONTAINED SHALL NOT BE USED FOR THE BENEFIT OF ANYONE EXCEPT BLUERAVENSOLAR NOR SHALL IT BE DISCLOSED IN WHOLE OR IN PART TO OTHERS OUTSIDE RECIPIENTS ORGANIZATION, EXCEPT IN CONNEC TION WITH THE SALE AND USE OF THE RESPECTIVE EQUIPMENT, WITHOUT THE WRITTEN PERMISSION OF BLUERAVENSOLAR LLC. PV1 COVER SHEET Marcelo Correa 59370955 February 19, 2019 0 SI T E I N F O R M A T I O N : Sh a w n a S m i t h 27 9 R o d n e y D r . RE X B U R G , I d a h o 8 3 4 4 0 DC S Y S T E M S I Z E : 5 . 7 k W D C CONTRACTOR: BRS FIELD OPS 385.498.6700 PV INSTALLATION PROFESSIONAL Scott Gurney # PV-011719-015866 NABCEP CERTIFIED CODES AND STANDARDS 1. ALL WORK SHALL COMPLY WITH 2017 NATIONAL ELECTRIC CODE (NEC), 2015 INTERNATIONAL RESIDENTIAL CODE (IRC), 2015 INTERNATIONAL BUILDING CODE (IBC), 2015 INTERNATIONAL PLUMBING CODE (IPC), AND ALL STATE AND LOCAL BUILDING, ELECTRICAL, AND PLUMBING CODES. 2. DRAWINGS HAVE BEEN DETAILED ACCORDING TO UL LISTING REQUIREMENTS. DESIGN CRITERIA ASCE 7 WIND SPEED: 115 MPH GROUND SNOW LOAD: 50 PSF EXPOSURE CATEGORY: C SEISMIC DESIGN CATEGORY: D N D C A C D C A C D C A C D C A C D C A C D C A C D C A C D C A C D C A C D C A C D C A C D C A C D C A C D C A C D C A C D C A C D C A C D C A C D C A C 27 9 R o d n e y D r . DC SYSTEM SIZE: 5.7 kW DC ROOF TYPE: Comp Shingle (19) Trinasolar 300 TSM-DD05A.08(II) Enphase IQ7-60-2-US,----INVERTER 8'16' SCALE: 1/16" = 1'-0" 0' 32'4' LEGEND AC M INVERTER & DC DISCONNECTINV AC DISCONNECT UTILITY METER / SERVICE PANEL PV REVENUE METER JB JUNCTION BOX PROPERTY LINE FIRE SETBACK EMT CONDUIT RUN (TO BE DETERMINED IN FIELD) PV WIRE STRING PV SUB (E) SUBPANEL LC (N) LOAD CENTER C COMBINER BOX DATE DRAWING BY PROJECT NUMBER SHEET NAME PAGE NUMBER REVISION 1220 S. 630 E STE. 430 AMERICAN FORK, UT 84003 800-377-4480 WWW.BLUERAVENSOLAR.COM CONFIDENTIAL - THE INFORMATION HEREIN CONTAINED SHALL NOT BE USED FOR THE BENEFIT OF ANYONE EXCEPT BLUERAVENSOLAR NOR SHALL IT BE DISCLOSED IN WHOLE OR IN PART TO OTHERS OUTSIDE RECIPIENTS ORGANIZATION, EXCEPT IN CONNEC TION WITH THE SALE AND USE OF THE RESPECTIVE EQUIPMENT, WITHOUT THE WRITTEN PERMISSION OF BLUERAVENSOLAR LLC. PV2 PROPERTY PLAN 0 Marcelo Correa 59370955 February 19, 2019 SI T E I N F O R M A T I O N : Sh a w n a S m i t h 27 9 R o d n e y D r . RE X B U R G , I d a h o 8 3 4 4 0 DC S Y S T E M S I Z E : 5 . 7 k W D C CONTRACTOR: BRS FIELD OPS 385.498.6700 PV INSTALLATION PROFESSIONAL Scott Gurney # PV-011719-015866 NABCEP CERTIFIED FR O N T O F H O M E MP1 # OF MODULES: 19 AZIMUTH:269° PITCH:18° TSRF:80% AREA: 883 SQ. FT 75'-11" 124'-11" N D C A C D C A C D C A C D C A C D C A C D C A C D C A C D C A C D C A C D C A C D C A C D C A C D C A C D C A C D C A C D C A C D C A C D C A C D C A C 4'8' SCALE: 1/8" = 1'-0" 0' 2'16' LEGEND AC M INVERTER & DC DISCONNECTINV AC DISCONNECT UTILITY METER / SERVICE PANEL PV REVENUE METER JB JUNCTION BOX PROPERTY LINE FIRE SETBACK EMT CONDUIT RUN (TO BE DETERMINED IN FIELD) PV WIRE STRING PV SUB (E) SUBPANEL LC (N) LOAD CENTER C COMBINER BOX DC SYSTEM SIZE: 5.7 kW DC ROOF TYPE: Comp Shingle (19) Trinasolar 300 TSM-DD05A.08(II) Enphase IQ7-60-2-US,----INVERTER DATE DRAWING BY PROJECT NUMBER SHEET NAME PAGE NUMBER REVISION 1220 S. 630 E STE. 430 AMERICAN FORK, UT 84003 800-377-4480 WWW.BLUERAVENSOLAR.COM CONFIDENTIAL - THE INFORMATION HEREIN CONTAINED SHALL NOT BE USED FOR THE BENEFIT OF ANYONE EXCEPT BLUERAVENSOLAR NOR SHALL IT BE DISCLOSED IN WHOLE OR IN PART TO OTHERS OUTSIDE RECIPIENTS ORGANIZATION, EXCEPT IN CONNEC TION WITH THE SALE AND USE OF THE RESPECTIVE EQUIPMENT, WITHOUT THE WRITTEN PERMISSION OF BLUERAVENSOLAR LLC. Marcelo Correa 59370955 February 19, 2019 SI T E I N F O R M A T I O N : Sh a w n a S m i t h 27 9 R o d n e y D r . RE X B U R G , I d a h o 8 3 4 4 0 DC S Y S T E M S I Z E : 5 . 7 k W D C CONTRACTOR: BRS FIELD OPS 385.498.6700 PV INSTALLATION PROFESSIONAL Scott Gurney # PV-011719-015866 NABCEP CERTIFIED PV3 SITE PLAN 0 FR O N T O F H O M E MP1 # OF MODULES: 19 AZIMUTH:269° PITCH:18° TSRF:80% AREA: 883 SQ. FT 3' 3' 14'-4" 61'-7" Sealed For Existing Roof & Attachment Only Digitally signed by John Calvert Date: 2019.02.20 11:10:44 -06'00' MODULE WIDTH H PV4 ARRAY DETAIL, FRONT VIEW Scale: 3/8" = 1'-0" MODULE WIDTH 48" MAX.1'-11" MAX. 18 ° 48" MAX.1'-11" MAX. ARRAY DETAIL, SIDE VIEW Scale: 3/8" = 1'-0" LANDSCAPE PORTRAIT LANDSCAPE PORTRAIT Unirac Sunframe Microrail TRIM RAILPV MODULE (BEHIND TRIM RAIL) G PV4 Unirac Sunframe Microrail FRAME SFM Raised Seal Flashing RACKING ATTACHMENTS TO BE STAGGERED BY SHIFTING EACH SUBSEQUENT ROW OF ATTACHMENTS ONE RAFTER OVER. (E) ROOF MEMBRANE UNIRAC SLIDERS AND TRIMRAIL ROOF ATTACHMENTS PV MODULE (E) BUILDING STRUCTURE DE T A I L , B O T T O M S T A N D O F F Sc a l e : 3 " = 1 ' - 0 " G Trinasolar 300 TSM-DD05A.08(II) 5/16" STAINLESS STEEL LAG BOLT WITH 2-1/2" MIN. EMBEDMENT AND FLAT WASHER 2.5" Unirac Sunframe Microrail UNIRAC TRIMRAIL 2.5" MIN. EMBED.FLASHING (E) ROOF MEMBRANE UNIRAC SLIDERS PV MODULE (E) BUILDING STRUCTURE Trinasolar 300 TSM-DD05A.08(II) 5/16" STAINLESS STEEL LAG BOLT WITH 2-1/2" MIN. EMBEDMENT AND FLAT WASHER 2.5" Unirac Sunframe Microrail FLASHING DE T A I L , M I D D L E / T O P S T A N D O F F Sc a l e : 3 " = 1 ' - 0 " H 2.5" MIN. EMBED. ROOF TYPE: Comp Shingle ROOF FRAMING TYPE: Manufactured Truss RAFTER OR TOP CHORD(TRUSS) 2x4 @ 24"O.C. CEILING JOIST OR BOTTOM CHORD(TRUSS) 2x4 @ 24"O.C. PV ARRAY INFORMATION PV MODULE COUNT: 19 MODULES # OF ATTACHMENT POINTS: 41 ARRAY AREA: Module Count x 17.51ft² = 332.7ft² ROOF AREA: 1767.0ft² % OF ARRAY/ROOF: 17.9% ARRAY WEIGHT: Module Count x 50lbs = 950.0lbs DISTRIBUTED LOAD: Array Weight ÷ Array Area = 2.86 lbs/ft² POINT LOAD: Array Weight ÷ Attachments = 23.2lbs/attachment DATE DRAWING BY PROJECT NUMBER SHEET NAME PAGE NUMBER REVISION 1220 S. 630 E STE. 430 AMERICAN FORK, UT 84003 800-377-4480 WWW.BLUERAVENSOLAR.COM CONFIDENTIAL - THE INFORMATION HEREIN CONTAINED SHALL NOT BE USED FOR THE BENEFIT OF ANYONE EXCEPT BLUERAVENSOLAR NOR SHALL IT BE DISCLOSED IN WHOLE OR IN PART TO OTHERS OUTSIDE RECIPIENTS ORGANIZATION, EXCEPT IN CONNEC TION WITH THE SALE AND USE OF THE RESPECTIVE EQUIPMENT, WITHOUT THE WRITTEN PERMISSION OF BLUERAVENSOLAR LLC. Marcelo Correa 59370955 February 19, 2019 SI T E I N F O R M A T I O N : Sh a w n a S m i t h 27 9 R o d n e y D r . RE X B U R G , I d a h o 8 3 4 4 0 DC S Y S T E M S I Z E : 5 . 7 k W D C CONTRACTOR: BRS FIELD OPS 385.498.6700 PV INSTALLATION PROFESSIONAL Scott Gurney # PV-011719-015866 NABCEP CERTIFIED PV4 EQUIP. DETAIL 0 GROUND SNOW LOAD: 50 PSF EXPOSURE CATEGORY: C SEISMIC DESIGN CATEGORY: D STRUCTURAL DESIGN CRITERIA ASCE 7-10 WIND SPEED: 115 MPH Sealed For Existing Roof & Attachment Only Digitally signed by John Calvert Date: 2019.02.20 11:10:34 -06'00' (E) LOADS N G SUPPLY SIDE CONNECTION PER NEC 230.46, NEC 230.79(D), NEC 705.12(A) N EGC L2 L1 (E)100A / 2P L2 L1 (E)100A MAIN SERVICE PANEL (E)100A / 2P MAIN BREAKER 15 (E) GROUNDING ELECTRODE INTERCONNECTION NOTES 1. GROUND FAULT PROTECTION IN ACCORDANCE WITH [NEC 215.9] & [NEC 230.95] 2. ALL EQUIPMENT TO BE RATED FOR BACKFEEDING. 3. SUPPLY SIDE INTERCONNECTION ACCORDING TO [NEC705.12(A)] WITH SERVICE ENTRANCE CONDUCTORS IN ACCORDANCE WITH [NEC 240.21(B)] DISCONNECT NOTES 1. DISCONNECTING SWITCHES SHALL BE WIRED SUCH THAT WHEN THE SWITCH IS OPENED THE CONDUCTORS REMAINING LIVE ARE CONNECTED TO THE TERMINALS MARKED “LINE SIDE” (TYPICALLY THE UPPER TERMINALS) 2. AC DISCONNECT MUST BE ACCESSIBLE TO QUALIFIED UTILITY PERSONNEL, BE LOCKABLE, AND BE A VISIBLE-BREAK SWITCH 3. DC CURRENT CONDUCTORS ARE TO REMAIN OUTSIDE OF BUILDING PRIOR TO EITHER A FUSEABLE SOURCE CIRCUIT N EGC 25A FUSES CLASS R PV AC DISCONNECT FUSED, 100kAIC - R LOCKABLE, VISIBLE OPEN 30A, 240V, 2-POLE 120/240 VAC 60HZ TO UTILITY GRID (E) N G G L2 L1 (N)20A/2P 21 L1 L2 G 21 JUNCTION BOX L1 L2 G (1) CIRCUIT OF 9 MODULES (N)20A/2P L2 L1 L1 L2 G JUNCTION BOX (OPTIONAL IF UF-B CABLE USED FOR ENTIRE HOMERUN) L1 L2 G 3 G JUNCTION BOX (1) CIRCUIT OF 10 MODULES +- +-++ --++ -- +- +-++ --++ -- (19) Trinasolar 300 TSM-DD05A.08(II) UL 1703 COMPLIANT (19) Enphase IQ7-60-2-US MICRO INVERTERS UL 1741 COMPLIANT 7 MODULES MAX FOR ALL SUB-BRANCH CIRCUIT(S) TO COMPLY WITH VRISE CALCS Enphase IQ Combiner 3 X-IQ-AM1-240-3 (SOLAR LOADS ONLY) DATE DRAWING BY PROJECT NUMBER SHEET NAME PAGE NUMBER REVISION 1220 S. 630 E STE. 430 AMERICAN FORK, UT 84003 800-377-4480 WWW.BLUERAVENSOLAR.COM CONFIDENTIAL - THE INFORMATION HEREIN CONTAINED SHALL NOT BE USED FOR THE BENEFIT OF ANYONE EXCEPT BLUERAVENSOLAR NOR SHALL IT BE DISCLOSED IN WHOLE OR IN PART TO OTHERS OUTSIDE RECIPIENTS ORGANIZATION, EXCEPT IN CONNEC TION WITH THE SALE AND USE OF THE RESPECTIVE EQUIPMENT, WITHOUT THE WRITTEN PERMISSION OF BLUERAVENSOLAR LLC. Marcelo Correa 59370955 February 19, 2019 SI T E I N F O R M A T I O N : Sh a w n a S m i t h 27 9 R o d n e y D r . RE X B U R G , I d a h o 8 3 4 4 0 DC S Y S T E M S I Z E : 5 . 7 k W D C CONTRACTOR: BRS FIELD OPS 385.498.6700 PV INSTALLATION PROFESSIONAL Scott Gurney # PV-011719-015866 NABCEP CERTIFIED PV5 ELEC. 3 LINE DIAG. 0 ALL CONDUIT TO BE RAN AT LEAST 7/8" ABOVE ROOF SURFACE WHERE EXPOSED TO SUNLIGHT. DATE DRAWING BY PROJECT NUMBER SHEET NAME PAGE NUMBER REVISION 1220 S. 630 E STE. 430 AMERICAN FORK, UT 84003 800-377-4480 WWW.BLUERAVENSOLAR.COM CONFIDENTIAL - THE INFORMATION HEREIN CONTAINED SHALL NOT BE USED FOR THE BENEFIT OF ANYONE EXCEPT BLUERAVENSOLAR NOR SHALL IT BE DISCLOSED IN WHOLE OR IN PART TO OTHERS OUTSIDE RECIPIENTS ORGANIZATION, EXCEPT IN CONNEC TION WITH THE SALE AND USE OF THE RESPECTIVE EQUIPMENT, WITHOUT THE WRITTEN PERMISSION OF BLUERAVENSOLAR LLC. Marcelo Correa 59370955 February 19, 2019 SI T E I N F O R M A T I O N : Sh a w n a S m i t h 27 9 R o d n e y D r . RE X B U R G , I d a h o 8 3 4 4 0 DC S Y S T E M S I Z E : 5 . 7 k W D C CONTRACTOR: BRS FIELD OPS 385.498.6700 PV INSTALLATION PROFESSIONAL Scott Gurney # PV-011719-015866 NABCEP CERTIFIED PV6 ELEC. CALCS. 0 GROUNDING NOTES 1. A GROUNDING ELECTRODE SYSTEM IN ACCORDANCE WITH [NEC 690-47] AND [NEC 250-50] THROUGH [NEC 250-60] SHALL BE PROVIDED. PER NEC, GROUNDING ELECTRODE SYSTEM OF EXISTING BUILDING MAY BE USED AND BONDED TO AT THE SERVICE ENTRANCE. IF EXISTING SYSTEM IS INACCESSIBLE, OR INADEQUATE, OR IS ONLY METALLIC WATER PIPING, A SUPPLEMENTAL GROUNDING ELECTRODE WILL BE USED AT THE INVERTER LOCATION CONSISTING OF A UL LISTED 8 FT GROUND ROD WITH ACORN CLAMP. 2. THE GROUNDING ELECTRODE CONDUCTOR SHALL BE PROTECTED FROM PHYSICAL DAMAGE BETWEEN THE GROUNDING ELECTRODE AND THE PANEL (OR INVERTER) IF SMALLER THAN #6 AWG COPPER WIRE PER NEC 250-64B. THE GROUNDING ELECTRODE CONDUCTOR WILL BE CONTINUOUS, EXCEPT FOR SPLICES OR JOINTS AT BUSBARS WITHIN LISTED EQUIPMENT PER [NEC 250.64C.]. 3. GROUNDING ELECTRODE CONDUCTORS SHALL BE NO LESS THAN #8 AWG AND NO GREATER THAN #6 AWG COPPER AND BONDED TO THE EXISTING GROUNDING ELECTRODE TO PROVIDE FOR A COMPLETE SYSTEM. 4. PV SYSTEM SHALL BE GROUNDED IN ACCORDANCE TO [NEC 250.21], [NEC TABLE 250.122], AND ALL METAL PARTS OR MODULE FRAMES ACCORDING TO [NEC 690.46]. 5. MODULE SOURCE CIRCUITS SHALL BE GROUNDED IN ACCORDANCE TO [NEC 690.42]. 6. THE GROUNDING CONNECTION TO A MODULE SHALL BE ARRANGED SUCH THAT THE REMOVAL OF A MODULE DOES NOT INTERRUPT A GROUNDED CONDUCTOR TO ANOTHER MODULE. 7. EACH MODULE WILL BE GROUNDED USING THE SUPPLIED CONNECTIONS POINTS IDENTIFIED IN THE MANUFACTURER'S INSTALLATION INSTRUCTIONS. 8. ENCLOSURES SHALL BE PROPERLY PREPARED WITH REMOVAL OF PAINT/FINISH AS APPROPRIATE WHEN GROUNDING EQUIPMENT WITH TERMINATION GROUNDING LUGS. 9. GROUNDING SYSTEM COMPONENTS SHALL BE LISTED FOR THEIR PURPOSE, AND GROUNDING DEVISES EXPOSED TO THE ELEMENTS SHALL BE RATED FOR DIRECT BURIAL. 10. GROUNDING AND BONDING CONDUCTORS SHALL BE COPPER, SOLID OR STRANDED, AND BARE WHEN EXPOSED. 11. EQUIPMENT GROUNDING CONDUCTORS SHALL BE SIZE ACCORDING TO [NEC 690.45] AND BE A MINIMUM OF #10AWG WHEN NOT EXPOSED TO DAMAGE (#6AWG SHALL BE USED WHEN EXPOSED TO DAMAGE). 12. GROUNDING AND BONDING CONDUCTORS, IF INSULATED, SHALL BE COLOR CODED GREEN (OR MARKED GREEN IF #4 AWG OR LARGER) 13. ALL CONDUIT BETWEEN THE UTILITY AC DISCONNECT AND THE POINT OF CONNECTION SHALL HAVE GROUNDED BUSHINGS AT BOTH ENDS. 14. SYSTEM GEC SIZED ACCORDING TO [NEC 690.47], [NEC TABLE 250.66], DC SYSTEM GEC SIZED ACCORDING TO [NEC 250.166], MINIMUM #8AWG WHEN INSULATED, #6AWG WHEN EXPOSED TO DAMAGE. 15. EXPOSED NON-CURRENT CARRYING METAL PARTS OF MODULE FRAMES, EQUIPMENTS, AND CONDUCTOR ENCLOSURES SHALL BE GROUNDED IN ACCORDANCE WITH 250.134 OR 250.136(A) REGARDLESS OF VOLTAGE. WIRING & CONDUIT NOTES 1. ALL CONDUIT SIZES AND TYPES, SHALL BE LISTED FOR ITS PURPOSE AND APPROVED FOR THE SITE APPLICATIONS 2. BOLTED CONNECTION REQUIRED IN DC DISCONNECTS ON THE WHITE GROUNDED CONDUCTOR (USE POLARIS BLOCK OR NEUTRAL BAR) 3. ANY CONNECTION ABOVE LIVE PARTS MUST BE WATERTIGHT. REDUCING WASHERS DISALLOWED ABOVE LIVE PARTS, MEYERS HUBS RECOMMENDED 4. UV RESISTANT CABLE TIES(NOT ZIP TIES) USED FOR PERMANENT WIRE MANAGEMENT OFF THE ROOF SURFACE IN ACCORDANCE WITH NEC 110.2,110.3(A-B). 300.4 5. SOLADECK JUNCTION BOXES MOUNTED FLUSH W/ROOF SURFACE TO BE USED FOR WIRE MANAGEMENT AND AS FLASHED ROOF PENETRATIONS FOR INTERIOR CONDUIT RUNS. 6. ALL PV CABLES AND HOMERUN WIRES BE TYPE USE-2, AND SINGLE-CONDUCTOR CABLE LISTED AND IDENTIFIED AS PV WIRE, TYPE TC-ER, OR EQUIVALENT; ROUTED TO SOURCE CIRCUIT COMBINER BOXES AS REQUIRED 7. ALL CONDUCTORS AND OCPD SIZES AND TYPES SPECIFIED ACCORDING TO [NEC 690.8] FOR MULTIPLE CONDUCTORS 8. ALL PV DC CONDUCTORS IN CONDUIT EXPOSED TO SUNLIGHT SHALL BE INSTALLED AT LEAST 7/8" ABOVE THE ROOF SURFACE AND DERATED ACCORDING TO [NEC TABLE 310.15 (B)(2)(a), NEC TABLE 310.15(B)(3)(a),& NEC 310.15(B)(3)(c)]. 9. EXPOSED ROOF PV DC CONDUCTORS SHALL BE USE-2, 90°C RATED, WET AND UV RESISTANT, AND UL LISTED RATED FOR 600V, UV RATED SPIRAL WRAP SHALL BE USED TO PROTECT WIRE FROM SHARP EDGES 10. PHASE AND NEUTRAL CONDUCTORS SHALL BE DUAL RATED THHN/THWN-2 INSULATED, 90°C RATED, WET AND UV RESISTANT, RATED FOR 600V 11. 4-WIRE DELTA CONNECTED SYSTEMS HAVE THE PHASE WITH THE HIGHER VOLTAGE TO GROUND MARKED ORANGE OR IDENTIFIED BY OTHER EFFECTIVE MEANS. 12. ALL SOURCE CIRCUITS SHALL HAVE INDIVIDUAL SOURCE CIRCUIT PROTECTION 13. VOLTAGE DROP LIMITED TO 2% FOR DC CIRCUITS AND 3% FOR AC CIRCUITS 14. NEGATIVE GROUNDED SYSTEMS DC CONDUCTORS SHALL BE COLOR CODED AS FOLLOWS: DC POSITIVE- RED (OR MARKED RED), DC NEGATIVE- GREY (OR MARKED GREY) 15. POSITIVE GROUNDED SYSTEMS DC CONDUCTORS COLOR CODED: DC POSITIVE- GREY (OR MARKED GREY), DC NEGATIVE- BLACK (OR MARKED BLACK) 16. AC CONDUCTORS >4AWG COLOR CODED OR MARKED: PHASE A OR L1- BLACK, PHASE B OR L2- RED, PHASE C OR L3- BLUE, NEUTRAL- WHITE/GRAY * USE-2 IS NOT INDOOR RATED BUT PV CABLE IS RATED THWN/THWN-2 AND MAY BE USED INSIDE ** USE-2 IS AVAILABLE AS UV WHITE 17. RIGID CONDUIT, IF INSTALLED, (AND/OR NIPPLES) MUST HAVE A PULL BUSHING TO PROTECT WIRES. 18. IF CONDUIT DETERMINED TO BE RAN THROUGH ATTIC IN FIELD THEN CONDUIT WILL BE EITHER EMT, FMC, OR MC CABLE IF DC CURRENT COMPLYING WITH NEC 690.31, NEC 250.118(10). DISCONNECTING MEANS SHALL COMPLY WITH 690.13 AND 690.15 19. CONDUIT RAN THROUGH ATTIC WILL BE AT LEAST 18" BELOW ROOF SURFACE COMPLYING WITH NEC 230.6(4) AND SECURED NO GREATER THAN 6' APART PER NEC 330.30(B). LABEL 12 PERMANENT DIRECTORY TO BE LOCATED AT SOLAR ARRAY RAPID SHUTDOWN SWITCH DENOTING THE LOCATION OF THE SERVICE EQUIPMENT LOCATION IF SOLAR ARRAY RAPID SHUT DOWN DISCONNECT SWITCH IS NOT GROUPED AND WITHIN LINE OF SITE OF MAIN SERVICE DISCONNECTING MEANS. [NEC 705.10] LABEL 13 PERMANENT DIRECTORY TO BE LOCATED AT MAIN SERVICE EQUIPMENT DENOTING THE LOCATION OF THE PV RAPID SHUTDOWN SYSTEM DISCONNECTING MEANS IF SOLAR ARRAY RAPID SHUT DOWN DISCONNECT SWITCH IS NOT GROUPED AND WITHIN LINE OF SITE OF MAIN SERVICE DISCONNECTING MEANS. [NEC 705.10, NEC 690.56(C)(1)] LABEL 11 PERMANENT DIRECTORY TO BE LOCATED AT MAIN SERVICE EQUIPMENT LOCATION IF ALL ELECTRICAL POWER SOURCE DISCONNECTING MEANS (SOLAR ARRAY RAPID SHUTDOWN SWITCH) ARE GROUPED AND IN LINE OF SITE OF MAIN SERVICE DISCONNECTING MEANS. [NEC 690.56(C) & NEC 705.10]. POWER TO THIS BUILDING IS ALSO SUPPLIED FROM A ROOF MOUNTED SOLAR ARRAY WITH A RAPID SHUTDOWN DISCONNECTING MEANS GROUPED AND LABELED WITHIN LINE OF SITE AND 10 FT OF THIS LOCATION. MAIN DISTRIBUTION UTILITY DISCONNECT(S) LABEL 3 AT POINT OF INTERCONNECTION, MARKED AT AC DISCONNECTING MEANS. [NEC 690.54, NEC 690.13 (B)] LABEL 4 AT POINT OF INTERCONNECTION FOR EQUIPMENT CONTAINING OVERCURRENT DEVICES IN CIRCUTS SUPPLYING POWER TO A BUSBAR OR CONDUCTOR SUPPLIED FORM MULTIPLE SOURCES, EACH SERVICE EQUIPMENT AND ALL ELECTRIC POWER PRODUCTION SOURCE LOCATIONS. [NEC 705.12(B)(3)] LABEL 5 PLACED ADJACENT TO THE BACK-FED BREAKER FROM THE INVERTER IF TIE IN CONSISTS OF LOAD SIDE CONNECTION TO BUSBAR. [NEC 705.12(B)(2)(3)(b)] 2 10 5 7 1 1 5 7 LABEL 7 AT DIRECT-CURRENT EXPOSED RACEWAYS, CABLE TRAYS, COVERS AND ENCLOSURES OF JUNCTION BOXES, AND OTHER WIRING METHODS; SPACED AT MAXIMUM 10FT SECTION OR WHERE SEPARATED BY ENCLOSURES, WALLS, PARTITIONS, CEILINGS, OR FLOORS. [NEC 690.31(G)(3&4)] LABEL 6 (ONLY IF 3 OR MORE SUPPLY SOURCES TO A BUSBAR) SIGN LOCATED AT LOAD CENTER IF IT CONTAINS 3 OR MORE POWER SOURCES. [NEC 705.12(B)(2)(3)(C)] LABEL 10 SIGN LOCATED AT RAPID SHUT DOWN DISCONNECT SWITCH [NEC 690.56(C)(3)]. LABEL 8 FOR PV SYSTEMS THAT SHUT DOWN THE ARRAY AND CONDUCTORS LEAVING THE ARRAY: SIGN TO BE LOCATED ON OR NO MORE THAN 3 FT AWAY FROM SERVICE DISCONNECTING MEANS TO WHICH THE PV SYSTEMS ARE CONNECTED AND SHALL INDICATE THE LOCATION OF ALL IDENTIFIED RAPID SHUTDOWN SWITCHES IF NOT AT THE SAME LOCATION. [NEC 690.56(C)(1)(A)] LABEL 9 FOR PV SYSTEMS THAT ONLY SHUT DOWN CONDUCTORS LEAVING THE ARRAY: SIGN TO BE LOCATED ON OR NO MORE THAN 3 FT AWAY FROM SERVICE DISCONNECTING MEANS TO WHICH THE PV SYSTEMS ARE CONNECTED AND SHALL INDICATE THE LOCATION OF ALL IDENTIFIED RAPID SHUTDOWN SWITCHES IF NOT AT THE SAME LOCATION. [NEC 690.56(C)(1)(B)] LABEL 1 FOR PV DISCONNECTING MEANS WHERE ALL TERMINALS OF THE DISCONNECTING MEANS MAY BE ENERGIZED IN THE OPEN POSITION. [NEC 690.13(B), NEC 705.22] LABEL 2 AT EACH DC DISCONNECTING MEANS, INCLUDING THE DC DISCONNECT AT THE INVERTER. [NEC 690.53, NEC 690.13(B)] LABELING NOTES: 1. LABELS CALLED OUT ACCORDING TO ALL COMMON CONFIGURATIONS. ELECTRICIAN TO DETERMINE EXACT REQUIREMENTS IN THE FIELD PER CURRENT NEC AND LOCAL CODES AND MAKE APPROPRIATE ADJUSTMENTS. 2. LABELING REQUIREMENTS BASED ON THE 2017 NATIONAL ELECTRIC CODE, OSHA STANDARD 19010.145, ANSI Z535. 3. MATERIAL BASED ON THE REQUIREMENTS OF THE AUTHORITY HAVING JURISDICTION. 4. LABELS TO BE OF SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENT INVOLVED [NEC 110.21] 5. LABELS TO BE A MINIMUM LETTER HEIGHT OF 3/8", WHITE ON RED BACKGROUND; REFLECTIVE, AND PERMANENTLY AFFIXED [IFC 605.11.1.1] *ELECTRICAL DIAGRAM SHOWN ABOVE IS FOR LABELING PURPOSES ONLY. NOT AN ACTUAL REPRESENATION OF EQUIPMENT AND CONNECTIONS TO BE INSTALLED. LABEL LOCATIONS PRESENTED MAY VERY DEPENDING ON TYPE OF INTERCONNECTION METHOD AND LOCATION PRESENTED ON PV5 OF 3 LINE DIAGRAM. PV5 LINE DIAGRAM TO REFLECT ACTUAL REPRESENTATION OF PROPOSED SCOPE OF WORK. JUNCTION BOX OR COMBINER BOX MAIN SERVICE PANEL AC DISCONNECT EXISTING SUB PANEL (IF WHERE POINT OF INTERCONNECTION IS MADE) PV COMBINER SUBPANEL - IF USED TO COMBINE PV OUTPUT CIRCUITS AC DC INVERTER (S) INTEGRATED DC DISCONNECT (ONLY IF PV INTERCONNECTION CONSISTS OF LOAD SIDE BREAKER) (ONLY IF PV INTERCONNECTION CONSISTS OF LOAD SIDE BREAKER) LABELING DIAGRAM FOR STRING INV. / DC OPTIMIZER INV.: AC JUNCTION BOX OR AC COMBINER BOX MAIN SERVICE PANEL AC DISCONNECT EXISTING SUB PANEL (IF WHERE POINT OF INTERCONNECTION IS MADE) PV COMBINER SUBPANEL - IF USED TO COMBINE PV OUTPUT CIRCUITS (ONLY IF PV INTERCONNECTION CONSISTS OF LOAD SIDE BREAKER) (ONLY IF PV INTERCONNECTION CONSISTS OF LOAD SIDE BREAKER) LABELING DIAGRAM FOR MICRO INV.: 8 3 5 6 1 1 5 11 1 11 13OR OR PLACARD 12 OR PLACARD 12 OR PLACARD 8 9 1 11 13OR OR PLACARD OR 10 WARNING 3 1 POWER TO THIS BUILDING IS ALSO SUPPLIED FROM ROOF MOUNTED SOLAR ARRAY. SOLAR ARRAY RAPID SHUTDOWN DISCONNECT IS LOCATED OUTSIDE NEXT TO UTILITY METER. WARNING POWER TO THIS BUILDING IS ALSO SUPPLIED FROM MAIN DISTRIBUTION UTILITY DISCONNECT LOCATED _______________________________ WARNING 3 4 IF BREAKER USED & 3 4 IF BREAKER USED & 1 3 3 4 IF BREAKER USED & 3 4 IF BREAKER USED & 4 6 11 1 3 4 DATE DRAWING BY PROJECT NUMBER SHEET NAME PAGE NUMBER REVISION 1220 S. 630 E STE. 430 AMERICAN FORK, UT 84003 800-377-4480 WWW.BLUERAVENSOLAR.COM CONFIDENTIAL - THE INFORMATION HEREIN CONTAINED SHALL NOT BE USED FOR THE BENEFIT OF ANYONE EXCEPT BLUERAVENSOLAR NOR SHALL IT BE DISCLOSED IN WHOLE OR IN PART TO OTHERS OUTSIDE RECIPIENTS ORGANIZATION, EXCEPT IN CONNEC TION WITH THE SALE AND USE OF THE RESPECTIVE EQUIPMENT, WITHOUT THE WRITTEN PERMISSION OF BLUERAVENSOLAR LLC. Marcelo Correa 59370955 February 19, 2019 SI T E I N F O R M A T I O N : Sh a w n a S m i t h 27 9 R o d n e y D r . RE X B U R G , I d a h o 8 3 4 4 0 DC S Y S T E M S I Z E : 5 . 7 k W D C CONTRACTOR: BRS FIELD OPS 385.498.6700 PV INSTALLATION PROFESSIONAL Scott Gurney # PV-011719-015866 NABCEP CERTIFIED PV8 LABELS 0 SHEET NAME PAGE NUMBER REVISION 1220 S. 630 E STE. 430 AMERICAN FORK, UT 84003 800-377-4480 WWW.BLUERAVENSOLAR.COM CONFIDENTIAL - THE INFORMATION HEREIN CONTAINED SHALL NOT BE USED FOR THE BENEFIT OF ANYONE EXCEPT BLUERAVENSOLAR NOR SHALL IT BE DISCLOSED IN WHOLE OR IN PART TO OTHERS OUTSIDE RECIPIENTS ORGANIZATION, EXCEPT IN CONNEC TION WITH THE SALE AND USE OF THE RESPECTIVE EQUIPMENT, WITHOUT THE WRITTEN PERMISSION OF BLUERAVENSOLAR LLC. '6 '$7$6+((7  PR O J E C T M A N A G E R : SC O T T G U R N E Y 38 5 - 4 9 8 - 4 4 0 1 CO N T R A C T O R : BL U E R A V E N S O L A R 80 0 . 3 7 7 . 4 4 8 0 SHEET NAME PAGE NUMBER REVISION 1220 S. 630 E STE. 430 AMERICAN FORK, UT 84003 800-377-4480 WWW.BLUERAVENSOLAR.COM CONFIDENTIAL - THE INFORMATION HEREIN CONTAINED SHALL NOT BE USED FOR THE BENEFIT OF ANYONE EXCEPT BLUERAVENSOLAR NOR SHALL IT BE DISCLOSED IN WHOLE OR IN PART TO OTHERS OUTSIDE RECIPIENTS ORGANIZATION, EXCEPT IN CONNEC TION WITH THE SALE AND USE OF THE RESPECTIVE EQUIPMENT, WITHOUT THE WRITTEN PERMISSION OF BLUERAVENSOLAR LLC. '6 '$7$6+((7  PR O J E C T M A N A G E R : SC O T T G U R N E Y 38 5 - 4 9 8 - 4 4 0 1 CO N T R A C T O R : BL U E R A V E N S O L A R 80 0 . 3 7 7 . 4 4 8 0 SHEET NAME PAGE NUMBER REVISION 1220 S. 630 E STE. 430 AMERICAN FORK, UT 84003 800-377-4480 WWW.BLUERAVENSOLAR.COM CONFIDENTIAL - THE INFORMATION HEREIN CONTAINED SHALL NOT BE USED FOR THE BENEFIT OF ANYONE EXCEPT BLUERAVENSOLAR NOR SHALL IT BE DISCLOSED IN WHOLE OR IN PART TO OTHERS OUTSIDE RECIPIENTS ORGANIZATION, EXCEPT IN CONNEC TION WITH THE SALE AND USE OF THE RESPECTIVE EQUIPMENT, WITHOUT THE WRITTEN PERMISSION OF BLUERAVENSOLAR LLC. '6 '$7$6+((7  PR O J E C T M A N A G E R : SC O T T G U R N E Y 38 5 - 4 9 8 - 4 4 0 1 CO N T R A C T O R : BL U E R A V E N S O L A R 80 0 . 3 7 7 . 4 4 8 0 SHEET NAME PAGE NUMBER REVISION 1220 S. 630 E STE. 430 AMERICAN FORK, UT 84003 800-377-4480 WWW.BLUERAVENSOLAR.COM CONFIDENTIAL - THE INFORMATION HEREIN CONTAINED SHALL NOT BE USED FOR THE BENEFIT OF ANYONE EXCEPT BLUERAVENSOLAR NOR SHALL IT BE DISCLOSED IN WHOLE OR IN PART TO OTHERS OUTSIDE RECIPIENTS ORGANIZATION, EXCEPT IN CONNEC TION WITH THE SALE AND USE OF THE RESPECTIVE EQUIPMENT, WITHOUT THE WRITTEN PERMISSION OF BLUERAVENSOLAR LLC. '6 '$7$6+((7  PR O J E C T M A N A G E R : SC O T T G U R N E Y 38 5 - 4 9 8 - 4 4 0 1 CO N T R A C T O R : BL U E R A V E N S O L A R 80 0 . 3 7 7 . 4 4 8 0 SHEET NAME PAGE NUMBER REVISION 1220 S. 630 E STE. 430 AMERICAN FORK, UT 84003 800-377-4480 WWW.BLUERAVENSOLAR.COM CONFIDENTIAL - THE INFORMATION HEREIN CONTAINED SHALL NOT BE USED FOR THE BENEFIT OF ANYONE EXCEPT BLUERAVENSOLAR NOR SHALL IT BE DISCLOSED IN WHOLE OR IN PART TO OTHERS OUTSIDE RECIPIENTS ORGANIZATION, EXCEPT IN CONNEC TION WITH THE SALE AND USE OF THE RESPECTIVE EQUIPMENT, WITHOUT THE WRITTEN PERMISSION OF BLUERAVENSOLAR LLC. '6 '$7$6+((7  PR O J E C T M A N A G E R : SC O T T G U R N E Y 38 5 - 4 9 8 - 4 4 0 1 CO N T R A C T O R : BL U E R A V E N S O L A R 80 0 . 3 7 7 . 4 4 8 0 SHEET NAME PAGE NUMBER REVISION 1220 S. 630 E STE. 430 AMERICAN FORK, UT 84003 800-377-4480 WWW.BLUERAVENSOLAR.COM CONFIDENTIAL - THE INFORMATION HEREIN CONTAINED SHALL NOT BE USED FOR THE BENEFIT OF ANYONE EXCEPT BLUERAVENSOLAR NOR SHALL IT BE DISCLOSED IN WHOLE OR IN PART TO OTHERS OUTSIDE RECIPIENTS ORGANIZATION, EXCEPT IN CONNEC TION WITH THE SALE AND USE OF THE RESPECTIVE EQUIPMENT, WITHOUT THE WRITTEN PERMISSION OF BLUERAVENSOLAR LLC. '6 '$7$6+((7  PR O J E C T M A N A G E R : SC O T T G U R N E Y 38 5 - 4 9 8 - 4 4 0 1 CO N T R A C T O R : BL U E R A V E N S O L A R 80 0 . 3 7 7 . 4 4 8 0 SHEET NAME PAGE NUMBER REVISION 1220 S. 630 E STE. 430 AMERICAN FORK, UT 84003 800-377-4480 WWW.BLUERAVENSOLAR.COM CONFIDENTIAL - THE INFORMATION HEREIN CONTAINED SHALL NOT BE USED FOR THE BENEFIT OF ANYONE EXCEPT BLUERAVENSOLAR NOR SHALL IT BE DISCLOSED IN WHOLE OR IN PART TO OTHERS OUTSIDE RECIPIENTS ORGANIZATION, EXCEPT IN CONNEC TION WITH THE SALE AND USE OF THE RESPECTIVE EQUIPMENT, WITHOUT THE WRITTEN PERMISSION OF BLUERAVENSOLAR LLC. '6 '$7$6+((7  PR O J E C T M A N A G E R : SC O T T G U R N E Y 38 5 - 4 9 8 - 4 4 0 1 CO N T R A C T O R : BL U E R A V E N S O L A R 80 0 . 3 7 7 . 4 4 8 0