HomeMy WebLinkAboutINSPECTION SUMMARY - 18-00478 - 925 River Run - Madison County Mechanical SFRPermit Inspection Summary Permit Status of (Open) as of Report Date: 02/22/2019 9:03 am Permit Details Permit Number: 18-00478 925 River Run - Madison County Mechanical SFR 925 River Run Rd Madison County Mechanical New SFR Permit Issued Date: 08/30/2018 Permit Inspection Statistics 3Total Inspections Completed: 2Total Inspections Passed: Inspection Pass Rate: 66.67% Permit Inspection History *Refer to Individual Inspection Report for more Details Mechanical Inspection Type 08/30/2018FailQuinton OwensHVAC Rough-in * Direct vent for fireplace requires a 1" clearance to combustibles (see roof truss). * Gas piping is not allowed in HVAC vents (see floor joist return air just south of water heater) * Finish sealing all joist cavities used for return air. * Condensate drains to be completed by final inspection. * PVC reducer on exhaust vent cannot be installed in horizontal position. Must be between vertical and 45 degrees to allow drainage of condensate. Make correction by final. Inspector Comments: 09/04/2018PassDon AllenHVAC Rough-in 11/30/2018PassDon AllenHVAC Final Inspection Inspection for PMInspector Comments: