HomeMy WebLinkAboutCOMCHECK - 17-00448 - 407 W 1st N - Homestead Bldg 3 - AdditionI -f--vcl�t48
COMcheck Software Version 4.0.6.0
Mechanical Compliance Certificate
Project Information
Energy Code:
Project Title:
Location:
Climate Zone:
Project Type:
Construction Site:
Rexburg, ID
Additional Efficiency Package
Unspecified
Mechanical Systems List
Quantity System Type & Description
2012 IECC
Homestead Building 3 Addn
Rexburg, Idaho
6b
New Construction
Owner/Agent: Designer/Contractor:
Dwayne Sudweeks
Engineered Systems Assoc., Inc.
1355 E. Center St.
Pocatello, ID 83201
208-233-0501
dcs@engsystems.com
18 HVAC System 1 (Single Zone):
Packaged Terminal Heat Pump
Heating Mode: Capacity = 9 kBtuth,
Proposed Efficiency = 3.50 COP, Required Efficiency = 2.97 COP
Cooling Mode: Capacity = 9 kBtu/h,
Proposed Effidency = 12.00 EER, Required Efficiency: 11.30 EER
Fan System: FAN SYSTEM 1 -- Compliance (Motor nameplate HP method) : Passes
Fans:
FAN 1 Supply, Constant Volume, 330 CFM, 0.1 motor nameplate hp
HVAC System 2 (Single Zone):
Heating: 1 each - Central Furnace, Gas, Capacity = 135 kBtulh
Proposed Efficiency = 95.00% Et, Required Efficiency = 80.00% Et
Cooling: 1 each - Split System, Capacity = 54 kBtuth, Air -Cooled Condenser, No Economizer, Economizer exception: Low Capacity
Residential
Proposed Efficiency = 13.00 SEER, Required Efficiency: 13.00 SEER
Fan System: FAN SYSTEM 2 -- Compliance (Motor nameplate HP method) : Passes
Fans:
FAN 3 Supply, Constant Volume, 1920 CFM, 1.0 motor nameplate hp
Water Heater 2:
Gas Instantaneous Water Heater, Capacity: 0 gallons, Input Rating: 199 Btulh w/ Circulation Pump
Proposed Efficiency: 90.00 EF, Required Efficiency: 0.67 EF
Mechanical Compliance Statement
Compliance Statement: The proposed mechanical design represented in this document is consistent with the building plans,
specifications, and other calculations submitted with this permit application. The proposed mechanical systems have been
designed to meet the 2012 IECC requirements In COMcheck Version 4.0.6.0 and to comply with any applicable mandatory
requirements listed in the Inspection Checklist.
Project Title: Homestead Building 3 Addn
Data filename: C:\Users\Dwayne 15\Documents\COMcheck\Homestead3.cck
Report cave: iutuwir
Page 1 of 10
Name -Title Si nature' Date
Project Title: Homestead Building 3 Addn Report date: 10/05/17
Data filename: C:\Users\Dwayne 15\Documents\COMcheck\Homestead3.cck Page 2 of 10