Loading...
HomeMy WebLinkAboutTRUSS SPECS - 18-00662 - 77 S 1st E - Residential Electrical ServiceBeamChek v2017 licensed to: South Fork Design Group Reg # 3039-67201 Home Remodel 77 S. 1st W. Rexburg Window Header Date: 12/27/18 Selection 6x 10 DF -L #2 (3) 6 x6 06 Lu = 0.0 Ft Conditions NDS 2015 101, Min Bearing Area R1= 4.9 int R2= 4.9 int (1.5) DL Defl= 0.03 in Data Attributes Actual Critical Status Ratio Values Adjustments Loads Beam Span 6.0 ft Reaction 1 LL 2100 # Reaction 2 LL 2100 # Beam Wt per ft 12.7 # Reaction 1 TL 3038 # Reaction 2 TL 3038 # Bm Wt Included 76 # Maximum V 3038 # Max Moment 4557'# Max V (Reduced) 2236 # TL Max Defl L/240 TL Actual Defl L/>1000 LL Max Defl L / 360 LL Actual Defl L/>1000 Section (in3) Shear (int) TL Defl (in) LL Defl 82.73 52.25 0.07 0.04 62.50 19.73 0.30 0.20 OK OK OK OK 76% 38% 22% 20% Uniform LL: 700 Uniform TL: 1000 =A ®t 1.Ai 11 372 ���^�T4 Oro Uniform Load A R1 =3038 R2 =3038 SPAN = 6 FT Uniform and partial uniform loads are lbs per lineal ft. Fb (psi) FV (psi) E (psi x mil) Fc! (psi) Reference Values 875 170 1.3 625 Adjusted Values 875 170 1.3 625 CF Size Factor 1.000 Cd Duration 1.00 1.00 Cr Repetitive 1.00 Ch Shear Stress N/A Cm Wet Use 1.00 1.00 1.00 1.00 Cl Stability 1.0000 Rb = 0.00 Le = 0.00 Ft Uniform LL: 700 Uniform TL: 1000 =A ®t 1.Ai 11 372 ���^�T4 Oro Uniform Load A R1 =3038 R2 =3038 SPAN = 6 FT Uniform and partial uniform loads are lbs per lineal ft.