HomeMy WebLinkAboutINTERIOR LIGHTING COMPLIANCE - 08-00033 - Johnson Precast ShopCOMcheck Software Version 3.5.2
Interior Lighting Compliance
Certificate
,tea- ECG ---.77
Report Date: 02/05/08 r
Data filename: Unfifled.cck
Section 1: Project Information
Project Type: New Construction
Project Title : Coring Shop
Construction Site:
551 East Moody Road
Rexburg, ID 83440
Permit No. Applied for
Permit Date: Still Waiting
Owner/Agent:
Johnson Precast
551 East Moody Road
Rexburg, ID 83440
208-656-9977
jpc@ida.net
Section 2: General Information
Building Use Description by:
Building Type Floor Area
Storage, Industrial and Commercial 1200
Section 3: Requirements Checklist
Interior Lighting:
F1 1. Total proposed watts must be less than or equal to total allowed watts.
Allowed Watts Proposed Watts
720 640 YES
0800033
Johnson Precast Sl-iop
Designer/Contractor:
Johnson Precast
551 East Moody Road
Rexburg, ID 83440
208-656-9977
jpc@ida.net
APPROVE
ELE RICAL INSPECTOR
Exterior Lighting:
F1 2. Efficacy greater than 45 lumens/W.
Exceptions:
Specialized lighting highlighting features of historic buildings; signage; safety or secudty, lighting; low -voltage landscape lighting.
Controls, Switching, and Wiring:
Lj 3. Independent controls for each space (switch/occupancy sensor).
Exceptions:
Areas designated as security or emergency areas that must be continuously illuminated.
Lighting in stairways or corridors that are elements of the means of egress.
Li 4. Master switch at entry to hotelimotel guest room.
❑ 5. Each space provided with a manual control to provide uniform light reduction capability.
Exceptions:
Only one luminaire in space;
An occupant -sensing device controls the area;
The area is a corridor, storeroom, restroom, public lobby or guest room;
Areas greater than 250 sq.ft.
Lj 6. Automatic lighting shutoff control in spaces greater than 250 sq.ft in buildings larger than 5,000 sq.ft.
Exceptions.,
Areas with only one luminaire, corridors, storerooms, restrooms, or public lobbies.
Project Title: Coring Shop Report date: 02/05/08
Data filename: Untitled.cck Page 3 of 9
LI 7. Photocell/astronomical time sN �n exterior lights.
Exceptions:
Lighting intended for 24 hour use.
❑ 8. Tandem wired one -lamp and three -lamp ballasted luminaires (No single -lamp ballasts).
Exceptions.
Electronic high -frequency ballasts: Luminaires not on same switch.
Section 4: Compliance Statement
Compliance Statement. The proposed lighting design represented in this document is consistent with the building plans, specifications and
other calculations submitted with this permit application. The proposed lighting system has been designed to meet the 2001 IECC, Chapter 8,
requirements in COMcheck Version 3.5.2 and to comply with the mandatory requirements in the Requirements Checklist.
Name - Title Signature Date
Project Title: Coring Shop Report date: 02/05/08
Data filename: Untitled.cck Page 4 of 9
2001 IECC
COMcheck Software Version 3.5.2
Interior Lighting Application
Worksheet
Report Date:
Data filename: Untided.cck
Section 1: Allowed Lighting Power Calculation
A B C D
Floor Area Allowed Allowed Watts
Watts / ft2
Storage, Industrial and Commercial 1200 0.6 720
Total Allowed Watts = 720
Section 2: Proposed Lighting Power Calculation
A
Fixture ID: Description I Lamp I Wattage Per Lamp I Ballast
B C D E
Lamps/ # of Fixture (C X D)
Fixture Fixtures Watt.
Storage, Industrial and Commercial (1200 sq.ft.)
Compact Fluorescent 1: Twin Tube 40W / Electronic 2 4 160 640
Total Proposed Watts = 640
Section 3: Compliance Calculation
If the Total Allowed Wafts minus the Total Proposed Watts is greater than or equal to zero, the building complies.
Total Allowed Watts = 720
Total Proposed Watts = 640
Project Compliance = 80
Interior Lighting PASSES: Design 11% better than code.
Title: Coring Shop Report date: 02/05/08
Data filename: Untitled.cck Page 5 of 9