HomeMy WebLinkAboutELECTRICAL CALCULATIONS - 18-00527 - 430 W 2nd S - Providence Square - ClubhouseF:,T•N
BUSSMANN
SERIES
Your System Details
Project Name: Providence clubhouse
System Type: Three -Phase
Creator Email: greg@nelson-electricllc.com
Creation Date: Oct 2, 2018 @ 10:37pm
INFINITE PRIMARY SOURCE
TRANSFORMER
ICVA 25
Voltage S.Cq ., 208
%Z 7.00
%Z TOL -10% (Max Fault)
TAULT X1
1,102AMPS
Voltage (L -L) 208 V
CONDUCTOR
LENGTH 25 FT
Cz SIZE 3/0
QTY 1
i (per phase)
"TYPE Three Single Conductors
CJ CONDUIT Steel
WIRE Cu, 600 V
FAULT - X2
1,083 AMPS
Voltage (L -L) 208 V
FC2 1 availablE fault
currEnt calculator
Created Using Eaton's Bussmann Series - Available Fault Current Calculator 1.5 Page i
E:,T*N
BUSSMANN
SERIES
CONDUCTOR RUN - C2
LENGTH 35 FT
SIZE 3/0
QTY 1
(per phase)
TYPE Three Single Conductors
CONDUIT Steel
WIRE Cu, 600 V
FAULT - X3
1,057 AMPS
Voltage (L -L) 208 V
FC2 availablE fault
currEnt calculator
Created Using Eaton's Bussmann Series - Available Fault Current Calculator 1.5
Page 2