Ticket
Commercial Electrical Final Inspection on 10/02/2018: FAIL
Permit Number: 18-00386Permit Details
Commercial Remodel
Permit Issued Date: 08/03/2018
Final Inspections Required
Commercial Electrical Final Inspection HVAC Final Inspection
Commercial Building Final
485 N 2nd E
Mongolian Restaurant - Remodel
Inspection Details
bret.stoddard@rexburg.org
Inspected By: Bret Stoddard
Commercial Electrical Final Inspection on 10/02/2018: FAIL
D ESCRIPTIO N CO M M EN TS STATUS
Approved for a Final and C.O.Need to provide GFCI protection for the
receptacle under the kitchen hood near the grill,
dishwasher not wired in and must be GFCI
protected also, please call for a re-inspect when
done.
FAIL
Receptacles have correct polarity, grounding, no
open neutrals, etc. 200.10(B)
COMPLETED
Verify that interrupting ratings are adequate for
the conditions of the installation. 110.9
COMPLETED
Verify that unused openings have been
effectively closed.110.12(A), 408.7
COMPLETED
Check adequacy of entrance to and exit from
working
space in general and verify that spaces
containing large
equipment have at least two entrances/exits.
110.26(C), 110.26(C)(2)
COMPLETED
Check for identification of disconnecting means
and circuit directories for panelboards,
switchboards, and similar equipment.110.22,
408.4
COMPLETED
Check for continuity and completeness in metal
raceways and enclosures. 300.10
COMPLETED
Check for adequate length of free conductors in
boxes. Verify that boxes are installed at junction,
splice, outlet, switch, and pull points.300.14,
300.15
COMPLETED
Identify wet and damp locations and the
suitability of boxes and fittings.314.15
COMPLETED
Check boxes and conduit bodies for adequate
space for conductors.314.16
COMPLETED
Verify that raceways and cables are secured to
boxes.314.17(B) and (C)
COMPLETED
Check for closure of unused openings.314.17(A)COMPLETED
Page 1 of 2
(Continued)
Permit Number: 18-00386
D ESCRIPTIO N CO MMEN TS STATUS
Verify that boxes in walls and ceilings are flush
with the
finished surface or, if surfaces are
noncombustible, within 1/4 in. of the finished
surface.314.20
COMPLETED
Check for excessive gaps between edges of
boxes and
plaster, plasterboard, or drywall surfaces.314.21
COMPLETED
Verify that boxes are securely fastened and
supported.314.23
COMPLETED
Check for covers on boxes.314.25, 314.28(C)COMPLETED
Check lighting outlet boxes for
suitability.314.27(A) and (B)
COMPLETED
Verify that all boxes are accessible. 314.29 COMPLETED
Verify that switches are located not over 6 ft 7
in. (2 m) high and that they can be operated
from readily accessible places unless otherwise
permitted.404.8(A), 240.24(A)
COMPLETED
Verify that the voltage between adjacent
grouped or
ganged devices is not over 300 volts or that
barriers are
installed .404.8(B)
COMPLETED
Verify that switches or receptacles in boxes have
their plaster ears seated against the wall surface
or the box.404.10(B), 406.4(A) and (B)
COMPLETED
Verify that switches and receptacles are used
within
their ratings.404.14, 406.2(A), 430.109
COMPLETED
Check the listing and marking of any switches or
receptacles used with aluminum conductors.
404.14(C),406.2(C), 110.14
COMPLETED
Check receptacles in wet or damp locations for
proper
covers and enclosures.406.8
COMPLETED
Check receptacles for proper polarity and for
grounding
and bonding connections. 406.3, 250.146,
200.11
COMPLETED
Verify that receptacle ratings and branch-circuit
ratings
are compatible. 210.21, 210.24
COMPLETED
Verify that wiring methods are securely fastened
in place, supported independently of suspended
ceilings, and not used as supports.300.11 and
applicable Chapter 3 article(s)
APPROVED
Page 2 of 2