Inspection
Summary
Permit Status of (Open) as of Report Date: 10/08/2018 8:09 am
Permit Details Permit Number: 18-00093
Navex Global
155 W 2nd S
Commercial Tenant Finish
Permit Issued Date: 04/19/2018
Permit Inspection Statistics
35Total Inspections Completed:
8Total Inspections Passed:
Inspection Pass Rate: 22.86%
Permit Inspection History *Refer to Individual Inspection Report for more Details
Building Inspection Type
05/22/2018PARTPASSTed DyeCommercial Insulation Inspection
05/23/2018PARTPASSTed DyeCommercial Insulation Inspection
05/24/2018PARTPASSTed DyeCommercial Sheetrock/Drywall Inspection
05/31/2018PARTPASSQuinton OwensCommercial Insulation Inspection
Remaining insulation in tenant space east of lobby installed and approved to
cover.
Also looked at rated penetrations above west side restrooms (6 penetrations
found unprotected - Failed)
Inspector Comments:
Restrooms at lobby on 2nd floor are shown to have one hour fire-rated walls.
Penetrations above dropped ceiling are not rated yet - Do not cover.
Inspector Comments:
06/01/2018PARTPASSQuinton OwensCommercial Framing/Structure Inspection
Penetrations through concrete slab above in west restrooms are rated and
approved for hanging dropped ceiling.
Inspector Comments:
06/11/2018PARTPASSTed DyeCommercial Sheetrock/Drywall Inspection
06/11/2018PARTPASSTed DyeCommercial Framing/Structure Inspection
06/13/2018PARTPASSTed DyeCommercial Sheetrock/Drywall Inspection
06/20/2018PassTed DyeCommercial Framing/Structure Inspection
Inspection of Steel stud framing and fire caulking of pipes through concrete floor
in the chase.
Located on the west side of the center stairs.
Approved for cover.
Inspector Comments:
06/21/2018PARTPASSTed DyeCommercial Sheetrock/Drywall Inspection
06/27/2018PARTPASSQuinton OwensCommercial Insulation Inspection
West end shaft insulation and fireblocking in floor by exhaust fan on south wall
on second floor was inspected.
Inspector Comments:
Page 1 of 3
(Continued)
Permit Details Permit Number: 18-00093
Navex Global
155 W 2nd S
Commercial Tenant Finish
Permit Status of (Open) as of Report Date: 10/08/2018 8:09 am
Permit
Inspection
Summary
06/29/2018PARTPASSQuinton OwensCommercial Framing/Structure Inspection
Inspected penetrations through rated ceiling.
* One hole found unused and unprotected in northwest corner room and needs
to be rated.
* All other ceiling penetrations under apartments have been protected for fire
rating.
Inspector Comments:
07/03/2018PARTPASSQuinton OwensCommercial Insulation Inspection
* South exterior wall (west side) insulated behind pop out for exhaust fan ducts.
* Sleeve through floor above is rated in northwest corner room.
Inspector Comments:
07/06/2018FailQuinton OwensCommercial Insulation Inspection
Verify average thickness to show compliance to energy codes for ceiling
insulation R-value.
Inspector Comments:
ceiling 2nd story lobby before putting on hard lid; AMInspector Comments:
07/13/2018PARTPASSQuinton OwensCommercial Framing/Structure Inspection
Approved to hang dropped ceiling in lobby on 2nd floor.Inspector Comments:
07/13/2018PARTPASSQuinton OwensCommercial Insulation Inspection
* Foam insulation approved to apply thermal barrier (east half - no ceiling grid).
* Patch cutout spots for ceiling grid supports and ceiling tile to be reviewed as a
thermal barrier.
* Penetrations into stair enclosure above door was fire rated during inspection.
Inspector Comments:
07/31/2018PARTPASSQuinton OwensSuspending Ceiling Inspection
Suspended ceiling grid inspected in Navex tenant space on west side. Some
offices remain to have ceiling grid installed.
Inspector Comments:
08/16/2018FailQuinton OwensCommercial Building Final
Re-inspection planned for Monday morning for items listed (actual tenant
occupancy is planned for Tuesday). Temporary occupancy approved for installing
furnishings by tenant.
Inspector Comments:
Page 2 of 3
(Continued)
Permit Details Permit Number: 18-00093
Navex Global
155 W 2nd S
Commercial Tenant Finish
Permit Status of (Open) as of Report Date: 10/08/2018 8:09 am
Permit
Inspection
Summary
Electrical Inspection Type
04/11/2018PassBret StoddardCOM & MFR Electrical Service Inspection
04/11/2018PARTPASSBret StoddardCommercial Electrical Rough-in
05/01/2018PARTPASSBret StoddardCommercial Electrical Rough-in
05/29/2018PARTPASSBret StoddardCommercial Electrical Rough-in
06/05/2018PARTPASSBret StoddardCommercial Electrical Rough-in
07/12/2018PARTPASSBret StoddardCommercial Electrical Rough-in
07/31/2018PARTPASSBret StoddardCommercial Electrical Rough-in
08/09/2018FailBret StoddardCommercial Electrical Final Inspection
Mike w/Nelson Electric called in an inspection, he said he needed a final
inspection, but the electrical rough-in was never inspected as well a temporary
electrical service. Late PM
Inspector Comments:
08/14/2018PassBret StoddardCommercial Electrical Final Inspection
Fire Inspection Type
08/15/2018PassBret StoddardFire Alarm Final Inspection
08/15/2018PassDavid DavisFire Sprinkler Final Inspection
Mechanical Inspection Type
05/31/2018PARTPASSDon AllenHVAC Rough-in
08/08/2018PassDon AllenHVAC Final Inspection
Plumbing Inspection Type
04/13/2018PARTPASSDon AllenPlumbing Rough-in
07/12/2018PassDon AllenPlumbing Water
Good to cover the water lines in the navex part of the building.Inspector Comments:
08/15/2018PassDon AllenPlumbing Final Inspection
Inspections Required
Fire Alarm Rough-in
Electrical Underground Inspection
Plumbing Rough-in
Fire Department Final Inspection
Commercial Sheetrock/Drywall Inspection
Fire Sprinkler Rough-in
Commercial Insulation Inspection
Commercial Framing/Structure Inspection
Suspending Ceiling Inspection
Commercial Building Final