Bulletin 003 Rev. F
Model DH80
Model DH80 Recessed
Model DH80 Concealed
Quick Response,
Extended Coverage Sprinkler
For coverages up to 28 feet wide and
14 feet long(1). 250 psi (17,2 bar) rated.
Features:
1. Coverage for long and narrow spaces such as
hallways, corridors, decks and rooms up to 28
feet wide and 14 feet long.(1)
2. Deflector to ceiling dimensions are:
4” (102mm) min. to 12” (305mm) max.
3. Minimum spacing between sprinklers 12 feet
(3,6m).
4. UL Listed for light hazard applications.
5. 8.0 K Factor.
6. Sprinkler is approved for 250 psi (17,2 bar) ap-
plications.
7. Quick response performance.
8. ½” (13mm) adjustment of escutcheon and cover.
9. Tamper resistant cover plate can prevent the
sprinkler from being used for unintended pur-
poses. No exposed thermal element with the
concealed version.
10. Push-on/thread-off sturdy convenient escutch-
eon for recessed and cover for concealed.
11. Factory assembled sprinkler & cup, shipped
complete with protective cap for concealed
and FP recessed versions.
12. Sprinkler & cup assembly and escutcheon or
cover are separately packaged.
13. Cover finishes available in standard white paint,
special bronze, black paint or flat white paint.
14. Polyester Coated or Electroless Nickel PTFE
(Teflon®)* Plated cULus Listed Corrosion
Resistant Sprinklers
*Concealed Sprinkler is not corrosion resistance
(1) See Figure 3.
Approval Organizations
1. Listed by Underwriters Laboratories Inc. and
UL certified for Canada (cULus)
2. NYC MEA 258-93-E
Patents: US patent number 6,374,919
SWC Cover Plate
US Patent Number 6, 920, 937, B2
DH80 Sprinkler
Products Description
The Model DH80 family of sprinklers are quick response
extended coverage sidewall sprinklers for use in light haz-
ard applications. The Model DH80 with SWC cover plate is
a concealed sprinkler that uses Reliable’s push on/thread off
sidewall cover. This sprinkler has the cup factory mounted
and is shipped with a protective cap that protects the 3mm
frangible glass bulb during shipping and post installation fin-
ishing operations. The DH80 can be combined in the field
with the FP or F2 Escutcheon to make a recessed sprinkler.
The SWC cover plate, FP and F2 recessed escutcheons
have ½” adjustment. The SWC cover plate is attached with
135-degree solder. In the event of a fire the rising ambient
temperature melts the solder and the cover plate is ejected
away by springs exposing the 3mm frangible glass bulb.
The use of a 3mm bulb allows quick response which enables
the sprinkler to apply water to a fire sooner than standard
response sprinkles of the same temperature rating.
Application
The Model DH80 is a horizontal sidewall sprinkler intended
for installation in light hazard occupancies in accordance
with NFPA 13. These sprinklers are designed to provide fire
protection in long and narrow spaces such as hallways, cor-
ridors, decks and rooms up to 28 feet (8,5m) wide and 14
feet (4,3m) long. They are rated for 250 psi (17,2 bar) and
can be mounted between 4 and 12 inches (102 and 305mm)
down from the ceiling.
DH80 Concealed
with SWC cover plate DH80 F2 Recessed
DH80 DH80 Recessed
*DuPont Registered Trademark
Installation
DH80 Recessed, FP Escutcheon
To install the DH80 with the FP Escutcheon as a recessed
sprinkler cut a 25/8” diameter hole in the wall as shown in Fig-
ure1. Remove temporarily the plastic protective cap, then
use the GFR1 wrench to tighten the sprinkler until secured in
the sprinkler fitting. NOTE: The GFR1 wrench has a notch in
it to accommodate the deflector top. This wrench can only
be inserted one way. Care must be taken not to damage the
deflector during tightening. Apply a Teflon* based sealant
to the sprinkler threads before installing in the fitting. When
inserting or removing the wrench from the sprinkler cup, care
must be taken to prevent damage to the sprinkler. Wrench
only on the square boss. DO NOT WRENCH ON ANY OTH-
ER PART OF THE SPRINKLER. It is recommended that the
sprinkler be protected during plastering and painting opera-
tions by reinstalling the protective cap P/N 6802710003. In-
stallation is completed by removing the protective cap and
inserting the push-on escutcheon. Turn clockwise to adjust
the escutcheon against the wall.
DH80 Recessed, F2 Escutcheon
To install the DH80 with the F2 Escutcheon as a recessed
sprinkler cut a 2¼” diameter hole in the wall as shown in
Figure 2. Thread the DH80 into the collar hand tight. Apply
a Teflon* based sealant to the sprinkler threads and install
in the fitting. Wrench only on the square boss. NOTE: The
GFR1 wrench has a notch in it to accommodate the deflec-
tor top. This wrench can only be inserted one way. When
inserting or removing the wrench from the sprinkler cup care
must be taken to prevent damage to the sprinkler. DO NOT
WRENCH ON ANY OTHER PART OF THE SPRINKLER. It is
recommended that the sprinkler be protected during plaster-
ing and painting operations by using the protective cap P/N
6999991009. These must be ordered separately. Installation
is completed by removing the protective cap and inserting
the F2 Escutcheon over the collar.
DH80 with SWC Cover Plate Concealed
To install the sprinkler, cut a 25/8” diameter hole into the
wall as shown in Figure1. A Teflon* based thread sealant
should be applied to the sprinkler threads only. Remove
the protective cap (P/N 6802710003) and then position
the GFR1 wrench into the sprinkler/cup assembly until the
wrench engages the flats of the square boss. Then tighten
the sprinkler into the pipe fitting. When inserting or removing
the wrench from the sprinkler/cup assembly, care should be
taken to prevent damage to the sprinkler. DO NOT WRENCH
ON ANY OTHER PART OF THE SPRINKLER. The protective
caps should be reinstalled for protection during plastering
and painting. Remove caps only when covers are being in-
stalled. The cover assembly is then pushed onto the cup.
Cover assemblies provide ½” (13mm) of adjustment. Final
adjustment is made by turning the cover clockwise until the
skirt flange makes full contact with the wall surface. Cover
removal requires turning in the counter- clockwise direction.
Concealed cover/cup assemblies are listed only for use
with specific sprinklers. The use of any other concealed
cover/cup assembly with the Model DH80 Horizontal Side-
wall Sprinkler or the use of the concealed cover assembly on
any sprinkler with which it is not specifically listed will void all
guarantees, warranties, listings and approvals.
Note: DH80 and DH80 Recessed Sprinklers have orange
bulb protectors to minimize bulb damage during shipping,
handling, and installation. REMOVE THIS PROTECTION AT
THE TIME THE SPRINKLER SYSTEM IS PLACED IN SER-
VICE FOR FIRE PROTECTION. Removal of the protectors
before this time may leave the bulb vulnerable to damage.
RASCO wrenches are designed to install sprinklers when
covers are in place. REMOVE PROTECTORS BY UNDOING
THE CLASP BY HAND. DO NOT USE TOOLS TO REMOVE
THE PROTECTORS.
Technical Data(1):
K Factor Thread
Size
Temperature
Rating Maximum
Ambient
Temperature
Sprinkler
Identification
Number
(SIN)US Metric Sprinkler
SWC
Cover
8.0 115,3 ¾”
155°F
(68°C)135°F
(57°C)
135°F (57°C)100°F(38°C)RA0362
(1) Minimum spacing of 12 feet (3,7m).
Coverage Area
Flow Rate
gpm (L/min)
Pressure
psi (bar)
Maximum Coverage Area
Width x Length
ft x ft (m xm)
40 (151,4) 25 (1,7) 28 x 14 (8,5 x 4,3)
Approval Type:
• Quick Response, Extended Coverage.
• Approved for installation in accordance with NFPA
13 for light hazard occupancies.
Maintenance
Model DH80 should be inspected and the sprinkler main-
tained in accordance with NFPA 25. Do not clean sprinklers
with soap and water, ammonia or any other cleaning fluids.
Remove dust by using a soft brush or gentle vacuuming. Re-
move any sprinkler/cover assembly, which has been painted
(other than factory applied) or damaged in any way. A stock
of spare sprinklers should be maintained to allow quick re-
placement of damaged or operated sprinklers. Prior to in-
stallation, sprinklers should be maintained in their original
cartons and packaging until used to minimize the potential
for damage to sprinklers that would cause improper opera-
tion or non-operation.
2.
*DuPont Registered Trademark
Model DH80 Quick Response
Extended Coverage Horizontal
Sidewall Sprinkler Specifi cation
Sprinklers shall be a [quick response – cULus Listed]
[quick response - New York City MEA Approved (258-93-E)]
extended coverage horizontal sidewall sprinkler for light haz-
ard occupancies. Sprinklers to be of bronze frame construc-
tion with a special deflector capable of providing a discharge
over a coverage area of 28 ft. (8,5m) wide, and 14 ft. (4,3m)
long horizontal throw. Water seal assembly shall consist of a
Teflon* coated Belleville spring washer and machined brass
cup with 3 mm glass bulb containing no plastic parts. Instal-
lation shall permit sprinkler deflectors to be positioned 4“
(102mm) to 12” (305mm) below the ceiling. Sprinklers shall
have a nominal K-factor of 8.0 (115.3), and ¾” NPT thread.
Sprinkler temperature rating shall be [135°F (57° C)][155°F
(68°C)]. Rated working pressure shall be 250 psi (17.2 bar).
Standard finish: [white][chrome][bronze][Special finish–
specify]. Quick response horizontal sidewall sprinklers shall
be Reliable Model DH80, SIN RA0362 (Bulletin 003).
For recessed horizontal sidewall sprinklers: Replace “hori-
zontal sidewall” with “recessed horizontal sidewall.” Add:
(1) Recessed escutcheon assembly shall be a two-piece es-
cutcheon of push-on and thread off design with ½” (12.7mm)
adjustment. Standard finish shall be [chrome] [white]; or (2)
Recessed escutcheon assembly shall be a two-piece “fric-
tion fit” escutcheon with ½” adjustment. Standard finish:
[white][chrome][bright brass][Special finish– specify]. Quick
response recessed horizontal sidewall sprinklers shall be Re-
liable Model DH80, SIN RA0362 (Bulletin 003).
For concealed horizontal sidewall sprinklers: Replace
“horizontal sidewall” with “concealed horizontal sidewall.”
Add: Cover plate assembly shall consist of a brass cover
plate and copper alloy retainer flange. Method of attach-
ing the cover plate to the sprinkler cup shall be a push-on
and thread-off design allowing a ½” (12.7mm) cover plate
adjustment. Cover plate temperature rating shall be 135°F
Figure 1
(57°C). A plastic protective cap shall be provided and fac-
tory installed inside the sprinkler cup to protect the sprinkler
from damage, which could occur during construction be-
fore the cover plate is installed. Standard cover plate finish:
[white] [Custom Color– specify]. Quick response concealed
horizontal sidewall sprinklers shall be Reliable Model DH80,
SIN RA0362 (Bulletin 003).
3.
UL Listing Category
Sprinklers, Automatic
and Open.
Quick Response Sprinklers.
Installation Wrench
Model GFR1 Sprinkler Wrench
Installation Aid
For concealed, a protective plas-
tic cap is included for use during
installation.
Escutcheon Data:
FP cup/escutcheon
assembly - ½” (13mm) adjustment
F2 - ½” (13mm) adjustment
Ordering Information
Specify:
• DH80
- Sprinkler Finish
• DH80 Recessed
-Sprinkler Finish
• FP or F2 Escutcheon
-Escutcheon Finish
• SWC Concealed
-Cover-Plate Finish
• Protective cap for use
with F2 escutcheons
Finishes(1)
Standard Finishes(1)
Sprinkler FP
Escutcheon
F2
Escutcheon
Cover
Plate
White and Black
Polyester(2)
Chrome
Bronze
White
Chrome
White
Chrome
Bright Brass
White
Special Application Finishes
Sprinkler FP/F2 Escutcheons
Electroless Nickel PTFE(Teflon®)*(2)Electroless Nickel PTFE (Teflon®)*
(1) Other colors and finishes are available. Consult factory for details.
(2) cULus listed Corrosion Resistant.
Note: Paint or any other coatings applied over the factory finish will void all
approvals and warranties.
*DuPont Registered Trademark
The Reliable Automatic Sprinkler Co., Inc.(800) 431-1588 Sales Offices
(800) 848-6051 Sales Fax
(914) 829-2042 Corporate Offices
www.reliablesprinkler.com Internet Address
Manufactured by
Recycled
Paper
Revision lines indicate updated or new data.
EG. Printed in U.S.A. 01/14 P/N 9999970246
The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association, Factory
Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Products manufactured and distributed by Reliable have been protecting life and property for over 90 years, and are installed and serviced by the most highly qualified and reputable sprinkler contractors located throughout the United States, Canada and foreign countries.
Figure 2.
Figure 3.