HomeMy WebLinkAboutPRODUCT DATA - SPRINKLER HEADS 2 - 18-00176 - 220 S 2nd W - Arbor Cove - Bldg (C) #2 - 32 Units - New Dormitory HousingThe Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523 B u l l e t i n 0 0 3 R e v . F Bulletin 003 Rev. F Model DH80 Model DH80 Recessed Model DH80 Concealed Quick Response, Extended Coverage Sprinkler For coverages up to 28 feet wide and 14 feet long(1). 250 psi (17,2 bar) rated. Features: 1. Coverage for long and narrow spaces such as hallways, corridors, decks and rooms up to 28 feet wide and 14 feet long.(1) 2. Deflector to ceiling dimensions are: 4” (102mm) min. to 12” (305mm) max. 3. Minimum spacing between sprinklers 12 feet (3,6m). 4. UL Listed for light hazard applications. 5. 8.0 K Factor. 6. Sprinkler is approved for 250 psi (17,2 bar) ap- plications. 7. Quick response performance. 8. ½” (13mm) adjustment of escutcheon and cover. 9. Tamper resistant cover plate can prevent the sprinkler from being used for unintended pur- poses. No exposed thermal element with the concealed version. 10. Push-on/thread-off sturdy convenient escutch- eon for recessed and cover for concealed. 11. Factory assembled sprinkler & cup, shipped complete with protective cap for concealed and FP recessed versions. 12. Sprinkler & cup assembly and escutcheon or cover are separately packaged. 13. Cover finishes available in standard white paint, special bronze, black paint or flat white paint. 14. Polyester Coated or Electroless Nickel PTFE (Teflon®)* Plated cULus Listed Corrosion Resistant Sprinklers *Concealed Sprinkler is not corrosion resistance (1) See Figure 3. Approval Organizations 1. Listed by Underwriters Laboratories Inc. and UL certified for Canada (cULus) 2. NYC MEA 258-93-E Patents: US patent number 6,374,919 SWC Cover Plate US Patent Number 6, 920, 937, B2 DH80 Sprinkler Products Description The Model DH80 family of sprinklers are quick response extended coverage sidewall sprinklers for use in light haz- ard applications. The Model DH80 with SWC cover plate is a concealed sprinkler that uses Reliable’s push on/thread off sidewall cover. This sprinkler has the cup factory mounted and is shipped with a protective cap that protects the 3mm frangible glass bulb during shipping and post installation fin- ishing operations. The DH80 can be combined in the field with the FP or F2 Escutcheon to make a recessed sprinkler. The SWC cover plate, FP and F2 recessed escutcheons have ½” adjustment. The SWC cover plate is attached with 135-degree solder. In the event of a fire the rising ambient temperature melts the solder and the cover plate is ejected away by springs exposing the 3mm frangible glass bulb. The use of a 3mm bulb allows quick response which enables the sprinkler to apply water to a fire sooner than standard response sprinkles of the same temperature rating. Application The Model DH80 is a horizontal sidewall sprinkler intended for installation in light hazard occupancies in accordance with NFPA 13. These sprinklers are designed to provide fire protection in long and narrow spaces such as hallways, cor- ridors, decks and rooms up to 28 feet (8,5m) wide and 14 feet (4,3m) long. They are rated for 250 psi (17,2 bar) and can be mounted between 4 and 12 inches (102 and 305mm) down from the ceiling. DH80 Concealed with SWC cover plate DH80 F2 Recessed DH80 DH80 Recessed *DuPont Registered Trademark Installation DH80 Recessed, FP Escutcheon To install the DH80 with the FP Escutcheon as a recessed sprinkler cut a 25/8” diameter hole in the wall as shown in Fig- ure1. Remove temporarily the plastic protective cap, then use the GFR1 wrench to tighten the sprinkler until secured in the sprinkler fitting. NOTE: The GFR1 wrench has a notch in it to accommodate the deflector top. This wrench can only be inserted one way. Care must be taken not to damage the deflector during tightening. Apply a Teflon* based sealant to the sprinkler threads before installing in the fitting. When inserting or removing the wrench from the sprinkler cup, care must be taken to prevent damage to the sprinkler. Wrench only on the square boss. DO NOT WRENCH ON ANY OTH- ER PART OF THE SPRINKLER. It is recommended that the sprinkler be protected during plastering and painting opera- tions by reinstalling the protective cap P/N 6802710003. In- stallation is completed by removing the protective cap and inserting the push-on escutcheon. Turn clockwise to adjust the escutcheon against the wall. DH80 Recessed, F2 Escutcheon To install the DH80 with the F2 Escutcheon as a recessed sprinkler cut a 2¼” diameter hole in the wall as shown in Figure 2. Thread the DH80 into the collar hand tight. Apply a Teflon* based sealant to the sprinkler threads and install in the fitting. Wrench only on the square boss. NOTE: The GFR1 wrench has a notch in it to accommodate the deflec- tor top. This wrench can only be inserted one way. When inserting or removing the wrench from the sprinkler cup care must be taken to prevent damage to the sprinkler. DO NOT WRENCH ON ANY OTHER PART OF THE SPRINKLER. It is recommended that the sprinkler be protected during plaster- ing and painting operations by using the protective cap P/N 6999991009. These must be ordered separately. Installation is completed by removing the protective cap and inserting the F2 Escutcheon over the collar. DH80 with SWC Cover Plate Concealed To install the sprinkler, cut a 25/8” diameter hole into the wall as shown in Figure1. A Teflon* based thread sealant should be applied to the sprinkler threads only. Remove the protective cap (P/N 6802710003) and then position the GFR1 wrench into the sprinkler/cup assembly until the wrench engages the flats of the square boss. Then tighten the sprinkler into the pipe fitting. When inserting or removing the wrench from the sprinkler/cup assembly, care should be taken to prevent damage to the sprinkler. DO NOT WRENCH ON ANY OTHER PART OF THE SPRINKLER. The protective caps should be reinstalled for protection during plastering and painting. Remove caps only when covers are being in- stalled. The cover assembly is then pushed onto the cup. Cover assemblies provide ½” (13mm) of adjustment. Final adjustment is made by turning the cover clockwise until the skirt flange makes full contact with the wall surface. Cover removal requires turning in the counter- clockwise direction. Concealed cover/cup assemblies are listed only for use with specific sprinklers. The use of any other concealed cover/cup assembly with the Model DH80 Horizontal Side- wall Sprinkler or the use of the concealed cover assembly on any sprinkler with which it is not specifically listed will void all guarantees, warranties, listings and approvals. Note: DH80 and DH80 Recessed Sprinklers have orange bulb protectors to minimize bulb damage during shipping, handling, and installation. REMOVE THIS PROTECTION AT THE TIME THE SPRINKLER SYSTEM IS PLACED IN SER- VICE FOR FIRE PROTECTION. Removal of the protectors before this time may leave the bulb vulnerable to damage. RASCO wrenches are designed to install sprinklers when covers are in place. REMOVE PROTECTORS BY UNDOING THE CLASP BY HAND. DO NOT USE TOOLS TO REMOVE THE PROTECTORS. Technical Data(1): K Factor Thread Size Temperature Rating Maximum Ambient Temperature Sprinkler Identification Number (SIN)US Metric Sprinkler SWC Cover 8.0 115,3 ¾” 155°F (68°C)135°F (57°C) 135°F (57°C)100°F(38°C)RA0362 (1) Minimum spacing of 12 feet (3,7m). Coverage Area Flow Rate gpm (L/min) Pressure psi (bar) Maximum Coverage Area Width x Length ft x ft (m xm) 40 (151,4) 25 (1,7) 28 x 14 (8,5 x 4,3) Approval Type: • Quick Response, Extended Coverage. • Approved for installation in accordance with NFPA 13 for light hazard occupancies. Maintenance Model DH80 should be inspected and the sprinkler main- tained in accordance with NFPA 25. Do not clean sprinklers with soap and water, ammonia or any other cleaning fluids. Remove dust by using a soft brush or gentle vacuuming. Re- move any sprinkler/cover assembly, which has been painted (other than factory applied) or damaged in any way. A stock of spare sprinklers should be maintained to allow quick re- placement of damaged or operated sprinklers. Prior to in- stallation, sprinklers should be maintained in their original cartons and packaging until used to minimize the potential for damage to sprinklers that would cause improper opera- tion or non-operation. 2. *DuPont Registered Trademark Model DH80 Quick Response Extended Coverage Horizontal Sidewall Sprinkler Specifi cation Sprinklers shall be a [quick response – cULus Listed] [quick response - New York City MEA Approved (258-93-E)] extended coverage horizontal sidewall sprinkler for light haz- ard occupancies. Sprinklers to be of bronze frame construc- tion with a special deflector capable of providing a discharge over a coverage area of 28 ft. (8,5m) wide, and 14 ft. (4,3m) long horizontal throw. Water seal assembly shall consist of a Teflon* coated Belleville spring washer and machined brass cup with 3 mm glass bulb containing no plastic parts. Instal- lation shall permit sprinkler deflectors to be positioned 4“ (102mm) to 12” (305mm) below the ceiling. Sprinklers shall have a nominal K-factor of 8.0 (115.3), and ¾” NPT thread. Sprinkler temperature rating shall be [135°F (57° C)][155°F (68°C)]. Rated working pressure shall be 250 psi (17.2 bar). Standard finish: [white][chrome][bronze][Special finish– specify]. Quick response horizontal sidewall sprinklers shall be Reliable Model DH80, SIN RA0362 (Bulletin 003). For recessed horizontal sidewall sprinklers: Replace “hori- zontal sidewall” with “recessed horizontal sidewall.” Add: (1) Recessed escutcheon assembly shall be a two-piece es- cutcheon of push-on and thread off design with ½” (12.7mm) adjustment. Standard finish shall be [chrome] [white]; or (2) Recessed escutcheon assembly shall be a two-piece “fric- tion fit” escutcheon with ½” adjustment. Standard finish: [white][chrome][bright brass][Special finish– specify]. Quick response recessed horizontal sidewall sprinklers shall be Re- liable Model DH80, SIN RA0362 (Bulletin 003). For concealed horizontal sidewall sprinklers: Replace “horizontal sidewall” with “concealed horizontal sidewall.” Add: Cover plate assembly shall consist of a brass cover plate and copper alloy retainer flange. Method of attach- ing the cover plate to the sprinkler cup shall be a push-on and thread-off design allowing a ½” (12.7mm) cover plate adjustment. Cover plate temperature rating shall be 135°F Figure 1 (57°C). A plastic protective cap shall be provided and fac- tory installed inside the sprinkler cup to protect the sprinkler from damage, which could occur during construction be- fore the cover plate is installed. Standard cover plate finish: [white] [Custom Color– specify]. Quick response concealed horizontal sidewall sprinklers shall be Reliable Model DH80, SIN RA0362 (Bulletin 003). 3. UL Listing Category Sprinklers, Automatic and Open. Quick Response Sprinklers. Installation Wrench Model GFR1 Sprinkler Wrench Installation Aid For concealed, a protective plas- tic cap is included for use during installation. Escutcheon Data: FP cup/escutcheon assembly - ½” (13mm) adjustment F2 - ½” (13mm) adjustment Ordering Information Specify: • DH80 - Sprinkler Finish • DH80 Recessed -Sprinkler Finish • FP or F2 Escutcheon -Escutcheon Finish • SWC Concealed -Cover-Plate Finish • Protective cap for use with F2 escutcheons Finishes(1) Standard Finishes(1) Sprinkler FP Escutcheon F2 Escutcheon Cover Plate White and Black Polyester(2) Chrome Bronze White Chrome White Chrome Bright Brass White Special Application Finishes Sprinkler FP/F2 Escutcheons Electroless Nickel PTFE(Teflon®)*(2)Electroless Nickel PTFE (Teflon®)* (1) Other colors and finishes are available. Consult factory for details. (2) cULus listed Corrosion Resistant. Note: Paint or any other coatings applied over the factory finish will void all approvals and warranties. *DuPont Registered Trademark The Reliable Automatic Sprinkler Co., Inc.(800) 431-1588 Sales Offices (800) 848-6051 Sales Fax (914) 829-2042 Corporate Offices www.reliablesprinkler.com Internet Address Manufactured by Recycled Paper Revision lines indicate updated or new data. EG. Printed in U.S.A. 01/14 P/N 9999970246 The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association, Factory Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable. Products manufactured and distributed by Reliable have been protecting life and property for over 90 years, and are installed and serviced by the most highly qualified and reputable sprinkler contractors located throughout the United States, Canada and foreign countries. Figure 2. Figure 3.