SEISMIC BRACES
PH-1.18
q Fig. AF411 (Formerly Afcon Fig. 411) Longitudinal Seismic Clamp
q Fig. AF074 (Formerly Afcon Fig. 074) Brace Attachment Fitting
q Fig. AF078 (Formerly Afcon Fig. 078) Brace Attachment Fitting
Size Range: Service Pipe: 1" through 10" Carbon Steel
Brace Pipe: 1" through 2" Sch. 40
Material: Carbon Steel (AF074 Only: Ductile Iron Brace Socket)
Finish: q Plain or q Electro-Galvanized per ASTM B633
Service: Designed to rigidly brace piping systems subjected to longitudinal seismic loads. The Fig.
AF411 may be installed with Fig. AF074 or AF078 Brace Attachment Fittings.
Approvals: cULus Listed (UL 203a) and FM Approved (FM 1950-10 & FM 1950-13). Complies with the
hanging and bracing requirements listed in NFPA 13.
Features: Visual indication of assembly when the clamp ears make metal-to-metal contact.
Installation Instructions:
• Mount the Fig. AF074 or AF078 on the outside of the outside of the Fig. AF411 clamps ears.
• Position the clamp at the desired location on the service pipe and hand tighten the hex bolts.
• Insert brace pipe into the AF074 or AF078 socket and torque the set screw until the head bottoms
out on the AF074 or AF078. Brace pipe must extend 1/2" past the end of the brace socket.
• Ensure the brace pipe is set to the desired installation brace angle.
• Tighten the clamp bolts and nuts equally and alternately until metal-to-metal contact is achieved
and the nuts are wrench tight.
• Fire Protection applications shall also be installed per the requirements of NFPA 13 and local codes.
Ordering: AF411: Specify service pipe size, figure number, finish, and description.
AF074 & AF078: Specify brace pipe size, figure number, finish, and description.
AF411, AF074, & AF078 all sold separately.
Fig. AF411
Fig. AF074
Fig. AF078
Notes: Anvil International® brand bracing components are designed to be compatible ONLY with other Anvil International®
brand bracing components, resulting in a Listed seismic bracing assembly. Updated UL listing information may be
viewed at www.ul.com and updated FM approval information may be viewed at www.approvalguide.com.
Disclaimer: Anvil International (“Anvil”) does not provide any warranties and specifically disclaims any liability whatsoever with respect to Anvil bracing products and components that are used in combination with products, parts or systems not manufactured or sold by Anvil. In no event shall Anvil be liable for any incidental, direct, consequential, special or indirect damages or lost profits where non-Anvil bracing components have been, or are used.
SeisBrace® Seismic Fire Protection Design Tool may be accessed at www.seisbrace.com
SEISMIC BRACES
PH-1.18
Fig. AF411 (Formerly Afcon Fig. 411) Longitudinal Seismic ClampFig. AF074 (Formerly Afcon Fig. 074) Brace Attachment FittingFig. AF078 (Formerly Afcon Fig. 078) Brace Attachment Fitting
FIG. AF411 cULus
MAX SEISMIC LONGITUDINAL LOADS:
DIMENSIONS (IN) • LOADS (LBS)
ServicePipe size
BraceAttachment Fitting
BracePipe Size
Max Seismic Brace Load
Sch. 10 Sch. 40
1 AF074 1 – 2 ––2015
AF078 1 – 11/4 ––1000
11/4 – 4 AF074 1 – 2 2015 2015
AF078 1 – 11/4 1000 1000
6 – 8 AF074 1 – 2 2015 2015
Fig. AF411
Fig. AF074 Fig AF078
Service Pipe
Brace Pipe
Fig AF411 & AF074
Installation
Fig AF411 & AF078
Installation
FIG. AF411: DIMENSIONS (IN) • WEIGHT (LBS)
ServicePipe Size A B Weight
1 55⁄8 21⁄8 1.75
11⁄4 6 21⁄4 1.90
11⁄2 61⁄8 21⁄4 2.00
2 63⁄4 21⁄2 2.15
21⁄2 73⁄8 27⁄8 2.40
3 77⁄8 31⁄8 2.60
4 9 37⁄8 3.10
6 111⁄2 47⁄8 4.50
8 131⁄2 57⁄8 5.50
FIG. AF074 & AF078: DIMENSIONS (IN) • WEIGHT (LBS)
BracePipe AF074 AF078
C D Weight C D Weight
1
23⁄16 17⁄16
0.97 25⁄16 11⁄8
0.38
11⁄4 1.07 0.54
11⁄2 1.17
2 1.31
A
B
C D
C
D
SEISMIC BRACES
PH-1.18
Fig. AF411 (Formerly Afcon Fig. 411) Longitudinal Seismic ClampFig. AF074 (Formerly Afcon Fig. 074) Brace Attachment FittingFig. AF078 (Formerly Afcon Fig. 078) Brace Attachment Fitting
FIG. AF411 FM MAX SEISMIC LONGITUDINAL ASD LOADS***: DIMENSIONS (IN) • LOADS (LBS) • ANGLES (DEG)
ServicePipe Size PipeSchedules BraceAttachment Fitting BracePipe Size
Max Seismic Brace Load at Brace Pipe Angle**
30-44 45-59 60-74 75-90
1 – 11/2 Sch. 10 – Sch. 40 AF074 1 – 2 1070 420 510 570
AF078 1 – 11/4 430 420 510 570
2 LW – Sch. 40 AF074 1 – 2 1410 1900 1730 1930
AF078 1 – 11/4 430 620 760 840
21/2 – 3 LW – Sch. 40 AF074 1 – 2 1000 860 1030 1150
AF078 1 – 11/4 430 620 760 840
4
LW AF074 1 – 2 1000 860 1030 1150
AF078 1 – 11/4 430 620 760 840
Sch. 10 – Sch. 40 AF074 1 – 2 1000 950 1150 1280
AF078 1 – 11/4 430 620 760 840
6 LW – Sch. 40 AF074 1 – 2 1410 2000 2450 2740
AF078 1 – 11/4 430 620 760 840
8 Sch. 10 – Sch. 40 AF074 1 – 2 1410 1250 1510 1690
AF078 1 – 11/4 430 620 760 840
* Load rating for LW above refers to FM Approved Lightwall pipe, commonly referred to as Sch.7 and Flow Pipe. See FM Approval Guide for approved Lightwall pipe.
** Brace Pipe Angles are determined from vertical.
*** The allowable FM approved capacity of brace subassemblies are listed in Allowable Stress Design (ASD). For Load Resistance Factor Design (LRFD) capacities, the above values
will need to be multiplied by 1.5.