HomeMy WebLinkAboutPRODUCT DATA - VALVESALARM BELLS - 18-00176 - 220 S 2nd W - Arbor Cove - Bldg (C) #2 - 32 Units - New Dormitory HousingBELLS
PBA-AC & PBD-DC
6" BELL SHOWN
These vibrating type bells are designed for use as fire, burglar or general signaling devices. They have low power con-
sumption and high decibel ratings. The unit mounts on a standard 4" (101mm) square electrical box for indoor use or on
a model BBK-1 weatherproof backbox for outdoor applications. Weatherproof backbox model BBK-1, Stock No.
1500001.
ALL DC BELLS ARE POLARIZED AND HAVE BUILT-IN TRANSIENT PROTECTION:
PRINTED IN USA PAGE 1 OF 2MKT. #8850001 - REV Q
MFG. #5400776 - 12/01
Notes:
1. Minimum dB ratings are calculated from integrated sound pressure measurements made at Underwriters Laboratories as
specified in UL Standard 464. UL temperature range is -30° to 150°F (-34° to 66°C).
2. Typical dB ratings are calculated from measurements made with a conventional sound level meter and are indicative of
output levels in an actual installation.
UL Listed, FM Approved
Sizes Available: 6" (150mm), 8" (200mm) and 10" (250mm)
Voltages Available:24VAC
120VAC
12VDC (10.2 to 15.6) Polarized
24VDC (20.4 to 31.2) Polarized
Service Use:Fire Alarm
General Signaling
Burglar Alarm
Environment:Indoor or outdoor use (See Note 1)
-40° to 150°F (-40° to 66°C)
(Outdoor use requires weatherproof
backbox.)
Termination: 4 No. 18 AWG stranded wires
Finish: Red powder coating
Optional: Model BBK-1 weatherproof backbox
Potter Electric Signal Company • 2081 Craig Road, St. Louis, MO, 63146-4161 • Phone: 800-325-3936/Canada 888-882-1833 • www.pottersignal.com
EZIS
SEHCNI
)mm(
EGATLOV.ONLEDOM.ONKCOTS TNERRUC
).XAM(
BdLACIPYT
.TF01TA
)2()m3(
BdMUMINIM
.TF01TA
)1()m3(
)051(6CDV21621DBP2106071A21.5867
)002(8CDV21821DBP2108071A21.0967
)052(01CDV210121DBP2100171A21.2967
)051(6CDV42642DBP4206071A60.7867
)002(8CDV42842DBP4208071A60.1997
)052(01CDV420142DBP4200171A60.4997
)051(6CAV42642ABP4206081A71.1967
)002(8CAV42842ABP4208081A71.4967
)052(01CAV420142ABP4200181A71.4967
)051(6CAV0216021ABP0216081A50.2928
)002(8CAV0218021ABP0218081A50.9928
)052(01CAV02101021ABP0210181A50.9958
DIMENSIONS
INCHES (mm)
FIG. 1 BELLS FIG. 2 WEATHERPROOF BACKBOX
BOX HAS ONE THREADED 1/2" CONDUIT ENTRANCE
INSTALLATION
1. The bell should be mounted a minimum of 8 ft. (2,4m) from the floor or as close to the ceiling as possible.
2. Remove the gong.
3. Connect wiring (see Fig. 3).
4. Mount bell mechanism to backbox (bell mechanism must be mounted with the striker pointing down).
5. Reinstall the gong (be sure that the gong positioning pin, in the mechanism housing, is in the hole in the gong).
6. Test all bells for proper operation and observe that they can be heard where required (bells must be heard in all areas
as designated by the authority having jurisdiction).
MKT. #8850001 - REV Q
MFG. #5400776 - 12/01
PAGE 2 OF 2
FIG. 3 WIRING (REAR VIEW)
BELLS
PBA-AC & PBD-DC
PRINTED IN USA