HomeMy WebLinkAboutPRODUCT DATA - HANGING MATERIAL - 18-00176 - 220 S 2nd W - Arbor Cove - Bldg (C) #2 - 32 Units - New Dormitory HousingPROJECT INFORMATION APPROVAL STAMP
Project:q Approved
Address:q Approved as noted
Contractor:q Not approved
Engineer:Remarks:
Submittal Date:
Notes 1:
Notes 2:
SEISMIC BRACES
PH-1.18
Fig. AF077 (Formerly Afcon Fig. 077) Sway Brace Swivel Attachment
Size Range: Brace Pipe: 1" through 11/2" Sch. 40; Anchor Size: 1/2"
Material: Carbon Steel
Finish: q Plain or q Electro-Galvanized per ASTM B633
Service: A seismic swivel attachment designed to connect brace pipe to
the building structure or to a seismic structural attachment. The Sway
Brace Swivel Attachment rigidly braces piping systems subjected to
horizontal seismic loads.
Approvals: cULus Listed (UL 203a) and FM Approved (FM 1950-10 & FM
1950-13). Complies with the hanging and bracing requirements listed in
NFPA 13.
Features:
• Field adjustable design requires no threading of the brace pipe
• The set screw design provides a visual indication that the desired
torque value has been achieved.
Installation Instructions:
• Insert anchor though the mounting hole and into the structure or seismic structural attachment.
• For connection to Fig. AF085, AF086, AF087, and AF779 seismic structural attachments, the bolt and nuts shall be installed
wrench tight (typically finger tight plus 1/4 to 1/2 turns).
• For connection to concrete, wood, timber, steel, and other structures, install fasteners per the fastener manufacturer’s
installation instructions.
• Insert Sch. 40 brace pipe into the bracket end. The brace pipe should extend a minimum of 0.50" past the back of the bracket.
• Torque set screw until the head bottoms out on the bracket.
• Check the cross bolt and nut and ensure the nut is wrench tight.
• Fire Protection applications shall also be installed per the requirements of NFPA 13 and local codes.
Ordering: Specify brace pipe size, figure number, finish, and description.
Notes: Anvil International® brand bracing components are designed to be compatible ONLY with other Anvil International® brand bracing components, resulting in
a Listed seismic bracing assembly. Updated UL listing information may be viewed at www.ul.com and updated FM approval information may be viewed at
www.approvalguide.com.
Disclaimer: Anvil International (“Anvil”) does not provide any warranties and specifically disclaims any liability whatsoever with respect to Anvil bracing products and components that are used in combination with products, parts or systems not manufactured or sold by Anvil. In no event shall Anvil be liable for any incidental, direct, consequential, special or indirect damages or lost profits where non-Anvil bracing components have been, or are used.
SeisBrace® Seismic Fire Protection Design Tool may be accessed at www.seisbrace.com
SEISMIC BRACES
Fig. AF077 (Formerly Afcon Fig. 077) Sway Brace Swivel Attachment (cont.)
FIG. AF077 cULus MAX SEISMIC HORIZONTAL LOADS:
DIMENSIONS (IN) • LOADS (LBS)
Brace Pipe Size FastenerSize Max Seismic Brace Load Max Service Pipe Size
1 - 11/4 1/2 1000 4
FIG. AF077 FM MAX SEISMIC HORIZONTAL ASD LOADS**:
DIMENSIONS (IN) • LOADS (LBS)
BracePipe Size FastenerSize
Max Seismic Brace Load at Brace Pipe Angle*
30-44 45-59 60-74 75-90
1 - 11/4 1/2 430 620 760 840
* Brace Pipe Angles are determined from vertical.
**The allowable FM approved capacity of brace subassemblies are listed in Allowable Stress
Design (ASD). For Load Resistance Factor Design (LRFD) capacities, the above values will
need to be multiplied by 1.5.
FIG. AF077 HORIZONTAL PRYING FACTORS (Pr) PER NFPA: ANGLES (DEG)
Brace Orientation*A B C D E F G H I
Brace Angle**30-44 45-59 60-90 30-44 45-59 60-90 30-44 45-59 60-90
Prying Factor (Pr)3.724 2.150 1.375 2.150 2.150 2.250 2.750 1.945 1.588
* Brace Orientation per NFPA 13-2016 Figure 9.3.5.12.1.** Brace Pipe Angles are determined from vertical.
0.50" Min.
FIG. AF077: DIMENSIONS (IN) • WEIGHT (LBS)
Fastener Size Brace Size A B C D E L W Weight
1⁄2 1 1.00 1.83 1.25 1.38 11⁄8 23⁄16 21⁄8 1.12
11⁄4 27⁄16 1.28
Set Screw CFastener Hole
W
L
E
D
B A
PH-1.18