HomeMy WebLinkAboutPRODUCT DATA - VALVES CHECK VALVE - 18-00176 - 220 S 2nd W - Arbor Cove - Bldg (C) #2 - 32 Units - New Dormitory HousingTyco Fire Products
Model CV-1F
Check Valve
Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500
www.tyco-fire.com
September 2004 TFP1550Page 1 of 2
The Model CV-1F Fire Protection Check Valve is
furnished with grooved ends and can be installed
using grooved couplings. The Model CV-1F can be
installed with ANSI class 150 Flanges utilizing Grinnell
Figure 71 flange adapters and also ANSI class 300
Flange Adapters. All Model CV-1F Check Valves
have been designed with a removable cover for ease
of field maintenance. Valves installed horizontally
or inclined (flow up or down) are to be positioned
with the cap facing up. Valves installed vertically
may be positioned with flow up or down.
A Maintenance Check Valve Kit is available to allow
the maintenance procedure of backflushing through
the fire department connection without removing
the Model CV-1F Check Valve from the pipe line.
The Model CV-1F Check Valves are a redesignation
for the Central Figure 590F and Grinnell Figure 590F.
WARNING
The Model CV-1F Check Valve described herein
must be installed and maintained in compliance
with this document, as well as with the applicable
standards of the National Fire Protection
Association, in addition to the standards of any
other authorities having jurisdiction. Failure to do
so may impair the performance of this device.
The owner is responsible for maintaining their fire
protection system and devices in proper operating
condition. The installing contractor or sprinkler
manufacturer should be contacted with any questions.
Model: CV-1F
Sizes: 2", 21⁄2", 76.1mm, 3", 4", 139.7mm, 5",
165.1mm, 6", 8", 10" and 12"
Max. Working Pressure: 300 psi (2068 kPa)
Factory Hydro Test: 100% at 600 psi (4137 kPa)
- Seat and shell complies with test requirements
of MSS SP-71, UL, FM and ULC
Approvals: UL, FM and ULC;
See Fire Protection Submittal Sheet for exact
Listing / Approval information.
Body and Cap: Ductile iron conforming to
ASTM A-536, Grade 65-45-12
Clapper: Stainless Steel (2" - 8") or
Ductile Iron (10" and 12")
Seal: Grade “E” EPDM
Protective Coatings: Valve assembly
• Non-lead paint
General
Description
When placing an order, indicate the full product
name. Please specify the quantity, valve model
number, size, type of seal, Grade “E” EPDM, and
part number from the following list.
Valve Valve
Size Part Number
2" 59-590-0-020
21/2"59-590-0-025
76.1mm 59-590-0-076
3" 59-590-0-030
4" 59-590-0-040
139.7mm 59-590-0-139
5" 59-590-0-050
165.1mm 59-590-0-165
6" 59-590-0-060
8" 59-590-0-080
10" 59-590-0-100
12" 59-590-0-120
Ordering
Procedure
Products manufactured by Tyco Fire Products are
warranted solely to the original Buyer for ten (10) years
against defects in material and workmanship when paid
for and properly installed and maintained under normal
use and service. This warranty will expire ten (10) years
from date of shipment by Tyco Fire Products. No
warranty is given for products or components
manufactured by companies not affiliated by ownership
with Tyco Fire Products or for products and components
which have been subject to misuse, improper installation,
corrosion, or which have not been installed, maintained,
modified or repaired in accordance with applicable
Standards of the National Fire Protection Association
(NFPA), and/or the standards of any other Authorities
Having Jurisdiction. Materials found by Tyco Fire
Products to be defective shall be either repaired or
replaced, at Tyco Fire Products’ sole option. Tyco Fire
Products neither assumes, nor authorizes any person
to assume for it, any other obligation in connection with
the sale of products or parts of products. Tyco Fire
Products shall not be responsible for sprinkler system
design errors or inaccurate or incomplete information
supplied by Buyer or Buyer’s representatives.
IN NO EVENT SHALL TYCO FIRE PRODUCTS BE
LIABLE, IN CONTRACT, TORT, STRICT LIABILITY OR
UNDER ANY OTHER LEGAL THEORY, FOR INCIDENTAL,
INDIRECT, SPECIAL OR CONSEQUENTIAL DAMAGES,
INCLUDING BUT NOT LIMITED TO LABOR CHARGES,
REGARDLESS OF WHETHER TYCO FIRE PRODUCTS
WAS INFORMED ABOUT THE POSSIBILITY OF SUCH
DAMAGES, AND IN NO EVENT SHALL TYCO FIRE
PRODUCTS’ LIABILITY EXCEED AN AMOUNT EQUAL
TO THE SALES PRICE.
THE FOREGOING WARRANTY IS MADE IN LIEU OF
ANY AND ALL OTHER WARRANTIES EXPRESS OR
IMPLIED, INCLUDING WARRANTIES OF
MERCHANTABILITY AND FITNESS FOR A
PARTICULAR PURPOSE.
Limited
Warranty
See Fire Protection
Submittal Sheet for Pressure Rating
and Listing/Approval Information
Technical
Data
Tyco Fire Products, valves, accessories and other
products are available throughout the U.S., Canada,
and internationally, through a network of
distribution centers. You may write directly or call
215-362-0700 for the distributor nearest you.
General Notes: It is the Designer’s responsibility to select products suitable for the intended service and to ensure
that pressure ratings and performance data is not exceeded. Always read and understand the installation
instructions (IH-1000). Never remove any piping component or correct or modify any piping deficiencies without
first depressurizing and draining the system. Material and gasket selection should be verified to be compatible
for the specific application.Certified Company
TYCO FIRE PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19946 Printed U.S.A.
Page 2 of 2 TFP1550
Model CV-1F Check Valve
2.5
"
(
7
3
.
0
m
m
)
,
7
6
.
1
m
m
4" (
1
1
4
.
3
m
m
)
165
.
1
m
m
,
6
"
(
1
6
8
.
3
m
m
)
8" (
2
1
9
.
1
m
m
)
3" (
8
8
.
9
m
m
)
10
0
0
0
50
0
0
40
0
0
30
0
0
20
0
0
10
0
0
50
0
40
0
30
0
20
0
10
050403020100.1
0.2
0.3
0.5
0.4
1
2
3
4
5
139
.
7
m
m
,
5
"
(
1
4
1
.
3
m
m
)
37
8
4
8
18
9
2
4
15
1
3
9
.
2
11
3
5
4
.
4
75
6
9
.
6
37
8
4
.
8
18
9
2
.
4
15
1
3
.
9
11
3
5
.
5
75
7
.
0
37
8
.
5
18
9
.
2
15
1
.
4
11
3
.
5
75
.
7
37
.
8
FLOW RATE (LPM)
PR
E
S
S
U
R
E
D
R
O
P
I
N
P
S
I
FLOW RATE (GPM)
2" (
6
0
.
3
m
m
)
10"
(
2
7
3
.
0
m
m
)
12"
(
3
2
3
.
9
m
m
)
Note: It is good piping practice to apply a safety factor of 15% to
20% to the values in the above table for design purposes.
1
4
16
15
3
2
17
18
13
15
16
14
6
10
8
5
11
12
7
9
Detail Part Material Qty.
1 Body Ductile Iron 1
2 Cap Ductile Iron 1
3 Gasket Synthetic Fiber 1
4 Hex Cap Screw Steel, Zinc Plated AR
5 Clapper Stainless Steel or 1
Ductile Iron
6 Seal Facing EPDM Grade “E” 1
7 Spring Stainless Steel 1
8 Hinge Shaft Stainless Steel 1
9 Retaining Ring Stainless Steel AR
10 Washer Teflon 2
11 Retention Bolt Stainless Steel 1
12 Seal Ring Neoprene 1
13 Retaining Disc Stainless Steel 1
14 Locknut Stainless Steel 1
15 Plug-
1⁄2"-14 NPT Cast Iron 2
16 Adhesive Thread Sealer AR
17 Nameplate Aluminum 1
18 Rivet Steel 2
Nominal Dimensions Approx.
Size A B C D E F J Cover Weight
Inches Inches Inches Inches Inches Inches Inches Inches Bolt Torq. lbs.
mm mm mm mm mm mm mm mm Lb.-ft./Nm Kg.
2" 6.75 4.38 2.55 2.57 3.25 4.75 1.62 15 9.0
60.3 171.5 111.3 64.8 65.3 82.3 120.7 41.5 21 4.5
21/2"8.00 5.80 3.41 3.40 3.88 6.00 1.70 39 10.0
73.0 203.2 147.3 86.6 86.4 98.6 152.4 43.2 54 4.5
8.00 5.80 3.41 3.40 3.88 6.00 1.70 39 10.00
203.2 147.3 86.6 86.4 98.6 152.4 43.2 54 4.5
3" 8.37 5.76 3.60 3.40 3.88 6.00 1.70 39 11.0
88.9 212.6 1.46.3 91.4 86.4 98.6 152.4 43.2 54 5.0
4" 9.63 6.74 4.61 3.63 4.56 7.13 1.84 39 25.0
114.3 244.6 171.2 117.1 92.2 115.1 181.1 46.7 54 11.3
10.50 7.50 5.29 4.20 4.90 7.60 1.90 39 29.0
266.7 190.5 134.4 106.7 124.5 193.0 48.3 54 13.2
5" 10.50 7.50 5.29 4.20 4.90 7.60 1.90 39 29.0
141.3 266.7 190.5 134.4 106.7 124.5 193.0 48.3 54 13.2
11.50 80.5 5.75 4.50 5.00 7.60 1.48 60 47.0
292.1 204.5 146.1 114.3 127.0 193.0 37.6 82 21.3
6" 11.50 8.05 5.75 4.50 5.00 7.60 1.48 60 47.0
168.3 292.1 204.5 146.1 114.3 127.0 193.0 37.6 82 21.3
8" 14.00 10.25 7.75 5.62 5.45 8.40 2.20 120 66.0
219.1 355.6 260.4 196.9 142.7 138.4 213.4 58.9 164 29.9
10" 18.00 13.00 10.21 6.38 7.50 10.50 3.00 120 109.7
273.0 457.2 330.2 259.3 162.1 190.5 266.7 76.2 164 49.4
12" 21.0 14.28 11.31 7.26 7.62 10.62 2.75 120 151.0
323.9 533.4 362.7 287.2 184.4 193.5 269.7 69.9 164 68.0
76.1mm
139.7mm
165.1mm
Care and
Maintenance
The owner is responsible for the inspection,
testing, and maintenance of their fire protection
system and devices in accordance with the
applicable standards of the National Fire Protection
Association (e.g., NFPA 25), in addition to the
standards of any authority having jurisdiction.
The installing contractor or product manufacturer
should be contacted relative to any questions.
Any impairment must be immediately corrected.
It is recommended that automatic sprinkler
systems be inspected, tested, and maintained by
a qualified Inspection Service.