Product Description
Model J112 and JL112 series sprinklers are cULus Listed
extended coverage spray sprinklers intended for installation
in accordance with NFPA 13. The sprinklers also have cU-
Lus Listed Specific Application Criteria for installation under
concrete tee construction in accordance with the require-
ments documented in this bulletin. Coverage areas up to
400 ft2 (37 m2) per sprinkler with a maximum spacing of up
to 20 ft by 20 ft (6.1 m by 6.1 m) are permitted for both Light
Hazard and Ordinary Hazard occupancies. Listed flows and
pressures for each hazard classification and sprinkler spac-
ing are provided in this bulletin. Model J112 and JL112 se-
ries sprinkler are cULus Listed as quick-response sprinklers
for Light Hazard occupancies. When used in the Ordinary
Hazard occupancies, Model J112 and JL112 series sprin-
klers are cULus Listed as quick-response for spacings up
to 14 ft by 14 ft (4.3 m by 4.3 m) and standard-response for
other listed spacings up to 20 ft by 20 ft (6.1 m by 6.1 m).
Model J112 Pendent and J112 Upright sprinklers use a
glass bulb operating element and are cULus Listed as
Corrosion Resistant Sprinklers when ordered with White
Polyester, Black Polyester, or Electroless Nickel PTFE (ENT)
finish. Model JL112 Pendent and JL112 Upright sprinklers
use a fusible link operating element. Model J112 Pendent
and Model JL112 Pendent sprinklers are cULus Listed for
use with the Model F2 and Model FP recessed escutch-
eons, which provide up to ½ inch (13 mm) of adjustment. In
addition, for Ordinary Hazard occupancies, the Model J112
Pendent and Model JL112 Pendent sprinklers are cULus
Listed for use with the Model F1 recessed escutcheon that
provides up to ¾ inch (19 mm) of adjustment.
Application
Model J112 and JL112 series sprinklers are intended for
installation in Light Hazard and Ordinary Hazard occupan-
cies in accordance with NFPA 13. The sprinklers must be
installed in accordance with the requirements of NFPA 13
for extended coverage spray sprinklers and the require-
ments identified in this bulletin. In addition to the installation
requirements of NFPA 13, cULus Listed Specific Application
Criteria for installation under concrete tee construction is
provided in this bulletin.
Model J112 and JL112 Sprinklers
Bulletin 172 Rev. G June 2018
cULus Listed
K11.2 (160 metric)Extended Coverage Sprinklers for Light Hazard and Ordinary Hazard
Model J112 UprightModel JL112 Upright
Model J112 PendentModel JL112 Pendent
Model J112 and JL112 Series Sprinkler Summary
Model Orientation Operating Element Sprinkler Identification Number
(SIN)
J112 Pendent Glass Bulb RA7216
JL112 Pendent Fusible Link R7216
J112 Upright Glass Bulb RA7326
JL112 Upright Fusible Link R7326
Table A
FP Recessed EscutcheonF1/F2 Recessed Escutcheon
Bulletin 172 Rev. G
June 2018
Page 2 of 7
www.reliablesprinkler.com
Model J112 Pendent Sprinkler SIN RA7216
Technical Specifications Style: Extended Coverage Pendent
Threads: 3/4” NPT or ISO 7-1R3/4
Nominal K-Factor: 11.2 (160 metric)
Max. Working Pressure: 175 psi (12 bar)
Min. Spacing: 8 ft. (2.4 m)
Material Specifications
Thermal Sensor: Glass Bulb
Cup: Bronze Alloy
Frame: Brass Alloy Sealing Assembly: Nickel Alloy with PTFE
Load Screw: Bronze Alloy
Kick Spring: Steel Alloy
Deflector: Brass Alloy
Sprinkler Wrench
Model J1
Model RJ (recessed)
Finishes
(See Table G)
Sensitivity
(See Table B)
Temperature Ratings
155°F (68°C)
200°F (93°C)
Recessed Escutcheons
F1-3/4” (19mm) adjustment (Ordinary Hazard only)
F2-1/2” (13mm) adjustment
FP-1/2” (13mm) adjustment
Listings and Approvals
cULus Listed
cULus Listed as Corrosion Resistant
with White Polyester, Black Polyester,
and ENT finish only
Max. Spacing
ft. x ft.(m x m)
Light Hazard Ordinary Hazard
Group 1
Ordinary Hazard
Group 2
Flow gpm (l/m)Pressure psi (bar)Flow gpm (l/m)Pressure psi (bar)Flow gpm (l/m)Pressure psi (bar)
12 x 12
(3.7 x 3.7)
30 (114)
QR
7.2 (0.50)
QR
30 (114)
QR
7.2 (0.50)
QR
39 (148)
QR
12.1 (0.8)
QR
14 x 14(4.3 x 4.3)30 (114)QR 7.2 (0.50)QR 30 (114)QR 7.2 (0.50)QR 39 (148)QR 12.1 (0.8)QR
16 x 16
(4.9 x 4.9)
30 (114)
QR
7.2 (0.50)
QR
39 (148)
SR
12.1 (0.8)
SR
51 (193)
SR
20.7 (1.4)
SR
18 x 18(5.5 x 5.5)33 (125)QR 8.7 (0.60)QR 49 (186)SR 19.1 (1.3)SR 65 (246)SR 33.7 (2.3)SR
20 x 20
(6.1 x 6.1)
40 (152)
QR
12.8 (0.88)
QR
60 (227)
SR
28.7 (2.0)
SR
80 (303)
SR
51.0 (3.5)
SR
Table B
QR = Quick-response
SR = Standard-response
Listed Design Criteria and Sensitivity
Model J112 Pendent Sprinkler Components Figure 1
Bulletin 172 Rev. G
June 2018
Page 3 of 7
www.reliablesprinkler.com
Model JL112 Pendent Sprinkler SIN R7216
Technical Specifications
Style: Extended Coverage Pendent
Threads: 3/4” NPT or ISO 7-1R3/4 Nominal K-Factor: 11.2 (160 metric)
Max. Working Pressure: 175 psi (12 bar) Min. Spacing: 8 ft. (2.4 m)
Material Specifications Thermal Sensor: Nickel Alloy Solder Link
Frame: Brass Alloy Levers: Brass Alloy
Cap: Bronze Alloy
Sealing Assembly: Nickel Alloy with PTFE Load Screw: Bronze Alloy
Deflector: Brass Alloy
Strut: Copper Alloy
Sprinkler Wrench
Model J1
Model RJ (recessed)
Finishes
(See Table G)
Sensitivity
(See Table C)
Temperature Rating* 165°F (74°C)
212°F (100°C)
Recessed Escutcheons
F1-3/4” (19mm) adjustment (Ordinary Hazard only)
F2-1/2” (13mm) adjustment
FP-1/2” (13mm) adjustment
Listings and Approvals
cULus Listed
*Chrome and white polyester finish is supplied
with white link regardless of temperature rating
Max. Spacing
ft. x ft.(m x m)
Light Hazard Ordinary Hazard
Group 1
Ordinary Hazard
Group 2
Flow
gpm (l/m)
Pressure
psi (bar)
Flow
gpm (l/m)
Pressure
psi (bar)
Flow
gpm (l/m)
Pressure
psi (bar)
12 x 12
(3.7 x 3.7)
30 (114)
QR
7.2 (0.50)
QR
30 (114)
QR
7.2 (0.50)
QR
39 (148)
QR
12.1 (0.8)
QR
14 x 14(4.3 x 4.3)30 (114)QR 7.2 (0.50)QR 30 (114)QR 7.2 (0.50)QR 39 (148)QR 12.1 (0.8)QR
16 x 16
(4.9 x 4.9)
30 (114)
QR
7.2 (0.50)
QR
39 (148)
SR
12.1 (0.8)
SR
51 (193)
SR
20.7 (1.4)
SR
18 x 18(5.5 x 5.5)33 (125)QR 8.7 (0.60)QR 49 (186)SR 19.1 (1.3)SR 65 (246)SR 33.7 (2.3)SR
20 x 20
(6.1 x 6.1)
40 (152)
QR
12.8 (0.88)
QR
60 (227)
SR
28.7 (2.0)
SR
80 (303)
SR
51.0 (3.5)
SR
Table C
QR = Quick-response
SR = Standard-response
Listed Design Criteria and Sensitivity
Model J112 Pendent Sprinkler Components Figure 2
Bulletin 172 Rev. G
June 2018
Page 4 of 7
www.reliablesprinkler.com
Model J112 Upright Sprinkler SIN RA7326
Technical Specifications Style: Extended Coverage Upright
Threads: 3/4” NPT or ISO 7-1 R3/4 Nominal K-Factor: 11.2 (160 metric)
Max. Working Pressure: 175 psi (12 bar)
Min. Spacing: 8 ft. (2.4 m)
Material Specifications Thermal Sensor: Glass Bulb
Cup: Bronze Alloy
Frame: Brass Alloy Sealing Assembly: Nickel Alloy with PTFE
Load Screw: Bronze Alloy Kick Spring: Steel Alloy
Deflector: Brass Alloy
Finishes (See Table G)
Sensitivity
(See Table D)
Temperature Rating
155°F (68°C)
200°F (93°C)
Sprinkler Wrench
Model J1
Listings and Approvals
cULus Listed
cULus Listed as Corrosion Resistant
with White Polyester, Black Polyester,
and ENT finish only
Max. Spacing
ft. x ft.(m x m)
Light Hazard Ordinary Hazard
Group 1
Ordinary Hazard
Group 2
Flow
gpm (l/m)
Pressure
psi (bar)
Flow
gpm (l/m)
Pressure
psi (bar)
Flow
gpm (l/m)
Pressure
psi (bar)
12 x 12
(3.7 x 3.7)
30 (114)
QR
7.2 (0.50)
QR
30 (114)
QR
7.2 (0.50)
QR
39 (148)
QR
12.1 (0.8)
QR
14 x 14(4.3 x 4.3)30 (114)QR 7.2 (0.50)QR 30 (114)QR 7.2 (0.50)QR 39 (148)QR 12.1 (0.8)QR
16 x 16
(4.9 x 4.9)
30 (114)
QR
7.2 (0.50)
QR
39 (148)
SR
12.1 (0.8)
SR
51 (193)
SR
20.7 (1.4)
SR
18 x 18(5.5 x 5.5)33 (125)QR 8.7 (0.60)QR 49 (186)SR 19.1 (1.3)SR 65 (246)SR 33.7 (2.3)SR
20 x 20
(6.1 x 6.1)
40 (152)
QR
12.8 (0.88)
QR
60 (227)
SR
28.7 (2.0)
SR
80 (303)
SR
51.0 (3.5)
SR
Table D
QR = Quick-response
SR = Standard-response
Listed Design Criteria and Sensitivity
Model J112 Upright Sprinkler Components Figure 3
Bulletin 172 Rev. GJune 2018 Page 5 of 7www.reliablesprinkler.com
Model JL112 Upright Sprinkler SIN R7326
Technical Specifications Style: Extended Coverage Upright
Threads: 3/4” NPT or ISO 7-1 R3/4 Nominal K-Factor: 11.2 (160 metric)
Max. Working Pressure: 175 psi (12 bar)
Min. Spacing: 8 ft. (2.4 m)
Material Specifications Thermal Sensor: Nickel Alloy Solder Link
Frame: Brass Alloy
Levers: Brass Alloy
Strut: Brass Alloy
Cap: Bronze Alloy Sealing Assembly: Nickel Alloy with PTFE
Load Screw: Bronze Alloy
Deflector: Brass Alloy
Finishes (See Table G)
Sensitivity
(See Table E)
Temperature Rating*
165°F (74°C)
212°F (100°C)
Sprinkler Wrench
Model J1
Listings and Approvals
cULus Listed
*Chrome and white polyester finish is supplied
with white link regardless of temperature rating
Max. Spacing
ft. x ft.
(m x m)
Light Hazard Ordinary Hazard
Group 1
Ordinary Hazard
Group 2
Flow
gpm (l/m)
Pressure
psi (bar)
Flow
gpm (l/m)
Pressure
psi (bar)
Flow
gpm (l/m)
Pressure
psi (bar)
12 x 12
(3.7 x 3.7)
30 (114)
QR
7.2 (0.50)
QR
30 (114)
QR
7.2 (0.50)
QR
39 (148)
QR
12.1 (0.8)
QR
14 x 14
(4.3 x 4.3)
30 (114)
QR
7.2 (0.50)
QR
30 (114)
QR
7.2 (0.50)
QR
39 (148)
QR
12.1 (0.8)
QR
16 x 16
(4.9 x 4.9)
30 (114)
QR
7.2 (0.50)
QR
39 (148)
SR
12.1 (0.8)
SR
51 (193)
SR
20.7 (1.4)
SR
18 x 18
(5.5 x 5.5)
33 (125)
QR
8.7 (0.60)
QR
49 (186)
SR
19.1 (1.3)
SR
65 (246)
SR
33.7 (2.3)
SR
20 x 20
(6.1 x 6.1)
40 (152)
QR
12.8 (0.88)
QR
60 (227)
SR
28.7 (2.0)
SR
80 (303)
SR
51.0 (3.5)
SR
Table E
QR = Quick-response
SR = Standard-response
Listed Design Criteria and Sensitivity
Model JL112 Upright Sprinkler Components Figure 4
Note: The Model FP, F1, or F2 may be used for ordinary hazard occupancies. For light hazard occupancies, the Model FP or F2
recessed escutcheon must be used. Model J112 and JL112 sprinklers with Model F1 recessed escutcheon are not listed for use
in light hazard occupancies.
Bulletin 172 Rev. GJune 2018 Page 6 of 7www.reliablesprinkler.com
The Model J112 and JL112 pendent and upright sprinklers are cULus Listed for installation under concrete tee construction in ac-
cordance with the following specific application criteria:
• Max. Tee Depth: 2’- 6” (0.8m)
• Max. Tee Stem Spacing: 7’- 6” (2.3m)
• Min. Tee Stem Spacing: 3’- 0” (0.9m)
• Max. Tee Length: 32’- 0” (9.8m) or baffles not less than the depth of the tees must be installed so that the longitudinal space
between baffles does not exceed 32ft (9.8m) in length.
• Max. Deflector distance below Tee: 1” (25mm)
• Comply with obstructions to the Sprinkler Discharge Pattern Development requirements of the NFPA13 where deflector is lo-
cated above bottom of tee.
Model J112 and JL112 Specific Application Criteria for Use Under Concrete Tee Construction cULus Listed
Figure 7Model F1/F2 Escutcheon
Installation DimensionsFigure 6Model FP Escutcheon
Installation Dimensions
Figure 5Application and Installation for Use Under Concrete Tee
1” (25mm) max.
1” (25mm) max.
2’-6” (0.8m) max.
7’-6” (2.3m) max.3’-0” (0.9m) min.
P
/
N
9
9
9
9
9
7
0
3
1
0
Bulletin 172 Rev. G
June 2018
Page 7 of 7
www.reliablesprinkler.com
Installation
Glass bulb sprinklers have orange bulb protectors to minimize
bulb damage during shipping, handling, and installation. Re-
liable sprinkler installation wrenches are designed to install
sprinklers with bulb protectors in place. Remove the bulb pro-
tector at the time when the sprinkler system is placed in service
for fire protection. Removal of the bulb protector before this time
may leave the bulb vulnerable to damage. Remove bulb protec-
tors by undoing the clasp by hand. Do not use tools to remove
bulb protectors.
Models J112 and JL112 series sprinklers must be installed
with the Reliable sprinkler installation wrench identified in this
bulletin. Any other wrench may damage the sprinkler. Recom-
mended installation torque is 14 to 20 lb.ft (19 to 27 N.m). Do
not tighten sprinklers over the maximum recommended installa-
tion torque. Exceeding the maximum recommended installation
torque may cause leakage or impairment of the sprinkler.
Recessed pendent sprinklers are to be installed as shown in
Fig. 6 or Fig 7., as applicable to the specific model being in-
stalled. Models J112 and JL112 series recessed pendent sprin-
klers may only be installed with the Reliable Model F1, Model
F2, or Model FP recessed escutcheon. The use of any other
recessed escutcheon will void all approvals and negate all war-
ranties. The Reliable Model FP escutcheon may not be used
in ceilings having positive pressure with respect to the space
below. Ensure that the openings in the Model FP escutcheon/
can assembly are unobstructed following installation.
Maintenance
Models J112 and JL112 series sprinklers should be inspect-
ed and the sprinkler system maintained in accordance with
NFPA 25. Do not clean sprinklers with soap and water, ammo-
nia or any other cleaning fluids. Remove dust by gentle vacu-
uming. Replace any sprinkler which has been painted (other
than factory applied) or damaged in any way. A stock of spare
sprinklers should be maintained to allow quick replacement of
damaged or operated sprinklers. Prior to installation, sprinklers
should be maintained in the original cartons and packaging un-
til used to minimize the potential for damage to sprinklers that
would cause improper operation or non-operation.
J1 Wrench RJ Wrench
Table G
Sprinkler Finishes Special Application Sprinkler Finishes
Sprinkler F1, F2, & FP(3) Escutcheons Sprinkler F1, F2, & FP(3) Escutcheons
Bronze
Chrome Plated
White Polyester (2)
Brass
Chrome Plated
White Polyester
Bright Brass
Dull Chrome
Black Polyester (2)
Custom Color Polyester
Electroless Nickel PTFE (2) (4)
Bright Brass
Dull Chrome
Black Polyester
Custom Color Polyester
Type 316 Stainless Steel
Sprinkler & Escutcheon Finishes (1)
Notes: (1) Paint or any other coating applied over the factory finish will void all approvals and warranties.
(2) cULus Listed Corrosion Resistant when ordered with Model J112 Pendent (RA7216) or Model J112 Upright (RA7326).
(3) The Model FP escutcheon assembly consists of an unfinished galvanized cup with a finished escutcheon ring.
(4) Available with Model J112 Pendent (RA7216) and Model J112 Upright (RA7326) only.
Listings and Approvals
Listed by Underwriters Laboratories, Inc. and certified by
Underwriters Laboratories of Canada (cULus)
UL Listing Category
Sprinklers, Automatic and Open Extended Coverage Sprinklers
UL Guide Number – VNIV.
Ordering Information
Specify:
1. Sprinkler Model: [J112 Pendent] [JL112 Pendent]
[J112 Upright] [JL112 Upright]
2. Temperature Rating: J112: [155°F (68°C)] [200°F (93°C)]
JL112: [165°F (74°C)] [212°F (100°C)]
3. Finish: (See Table G)
4. Escutcheon (Pendent Only; for 3/4” threads)
Model F1 (Ordinary Hazard Only)
Model F2
Model FP