Loading...
The URL can be used to link to this page
Your browser does not support the video tag.
Home
My WebLink
About
PROJECT INFO - 18-00552 - 532 Woodbridge St - SFR
Bold/italic values have been manually overridden Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2018-Oct-05 09:21:52 Rig ht-Su ite® U niv er sal 20 18 18 .0.27 RSU1 4674 Page 1 ...Alpine - Mt Timp Stonebridge 3-4-4 - 100518.rup Calc = MJ8 Front Door faces: N Stonebridge 3-4-4Job:Load Short Form Jul 27, 2018Date:Entire House Jay - Heating Supply CoBy: Project Information Mt Timpanogas, AlpineFor: Stonebridge 3-4-4, Idaho Falls, ID Email: jhooper@heatingsupplyco.com Design Information InfiltrationClgHtg SimplifiedMethod89-6Outside db (°F) AverageConstruction quality7570Inside db (°F) 0Fireplaces1476Design TD (°F) H-Daily range 5030Inside humidity (%) -2835Moisture difference (gr/lb) HEATING EQUIPMENT COOLING EQUIPMENT Make Carrier Make Carrier Trade Carrier Performance 95 Single-...Trade CARRIER Model 59SP5A060E17--14 Cond 24ABB330ABN33 AHRI ref 4702805 Coil CNPVP3017ALA+ AHRI ref 9858191 Efficiency 96.5 AFUE Efficiency 11.5 EER, 14 SEER Heating input Btuh60000 Sensible cooling Btuh22950 Heating output Btuh58000 Latent cooling Btuh4050 Temperature rise °F70 Total cooling Btuh27000 Actual air flow cfm900 Actual air flow cfm900 Air flow factor cfm/Btuh0.027 Air flow factor cfm/Btuh0.045 Static pressure in H2O0.70 Static pressure in H2O0.70 Space thermostat Load sensible heat ratio 1.00 ROOM NAME Area Htg load Clg load Htg AVF Clg AVF (ft²)(Btuh)(Btuh)(cfm)(cfm) Bed 6 234 2162 1053 59 47 Bath 1 63 583 0 16 0 Mechanical 110 0 0 0 0 Stairs 1 62 0 0 0 0 Bed 5 174 2256 395 62 18 Bed 4 218 1767 794 48 35 Family Room 666 3877 2104 106 94 Master Bed 252 4769 3420 131 153 Master Bath 90 1194 406 33 18 Master WIC 54 0 0 0 0 Bath 2 43 600 244 16 11 Bed 2 163 3218 561 88 25 Bed 3 132 1743 424 48 19 Entry 143 1379 333 38 15 Bold/italic values have been manually overridden Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2018-Oct-05 09:21:52 Rig ht-Su ite® U niv er sal 20 18 18 .0.27 RSU1 4674 Page 2 ...Alpine - Mt Timp Stonebridge 3-4-4 - 100518.rup Calc = MJ8 Front Door faces: N Mud Room 58 114 639 3 28 Kitchen/Great 613 9144 9808 251 437 Entire House 3074 32805 20181 900 900 Other equip loads 7508 1383 Equip. @ 0.94 RSM 20270 Latent cooling 0 TOTALS 3074 40313 20270 900 900 Bold/italic values have been manually overridden 2018-Oct-05 09:21:52 Rig ht-Su ite® U niv er sal 20 18 18 .0.27 RSU1 4674 Page 1 ...Alpine - Mt Timp Stonebridge 3-4-4 - 100518.rup Calc = MJ8 Front Door faces: N Stonebridge 3-4-4Job:Building Analysis Jul 27, 2018Date:Entire House Jay - Heating Supply CoBy: Project Information Mt Timpanogas, AlpineFor: Stonebridge 3-4-4, Idaho Falls, ID Email: jhooper@heatingsupplyco.com Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temp era ture (°F)Idaho Falls Rgnl, ID, US 1476Design TD (°F)ft4744Elevation: 5030Relative humidity (%)°N44Latitude:Outdoor:-28.435.2Moisture difference (gr/lb)CoolingHeating Infiltration:89-6Dry bul b (°F) SimplifiedMethod)H(35-Da ily ra nge (°F) AverageConstruction quality61-We t bu lb (°F) 0Fireplaces7.515.0Wind speed (mph) Heating Walls Glazing DoorsCeilingsFloors Infiltration Ducts Ventilation % of loadBtuhBtuh/ft²Component 19.377803.1Walls 18.0726323.4Glazing 3.1124529.6Doors 6.024211.5Ceilings 6.224821.51.5Floors 10.843393.7Infiltration 18.17277Ducts 00Piping 00Humidification 18.67508Ventilation0Adjustments 100.040313Total Cooling Other Glazing Ceilings Ducts Internal Gains Ventilation % of loadBtuhBtuh/ft²Component 1.22630.1Walls 31.2672821.7Glazing 1.42957.0Doors 6.113220.8Ceilings 0.1300.0Floors 2.04280.4Infiltration 17.63806Ducts 6.41383Ventilation 33.97310Internal gains 00Blower 0Adjustments 100.021564Total Latent Cooling Load = 0 Btuh Overall U-va lue = 0.0 47 Btuh/ft²-°F Data entries checked. Bold/italic values have been manually overridden 2018-Oct-05 09:21:52 Rig ht-Su ite® U niv er sal 20 18 18 .0.27 RSU1 4674 Page 1 ...Alpine - Mt Timp Stonebridge 3-4-4 - 100518.rup Calc = MJ8 Front Door faces: N Stonebridge 3-4-4Job:Component Constructions Jul 27, 2018Date:Entire House Jay - Heating Supply CoBy: Project Information Mt Timpanogas, AlpineFor: Stonebridge 3-4-4, Idaho Falls, ID Email: jhooper@heatingsupplyco.com Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temp era ture (°F)Idaho Falls Rgnl, ID, US 1476Design TD (°F)ft4744Elevation: 5030Relative humidity (%)°N44Latitude: Outdoor:-28.435.2Moisture difference (gr/lb)CoolingHeating Infiltration:89-6Dry bul b (°F) SimplifiedMethod)H(35-Da ily ra nge (°F) AverageConstruction quality61-We t bu lb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12F-2sw: Frm wall, wd ext, 1/2" wood shth, r-21 cav ins, 1/2" gypsum board int fnsh, r-2 ext bd ins, 2"x6" wood frm, 16" o.c. stud 470.297434.5623.00.060163n 820.2913044.5623.00.060286e 750.2911904.5623.00.060261s 580.299264.5623.00.060203w 2630.2941634.5623.00.060913all 15B19-0wc-8: Bg wall, heavy dry or light damp soil, 2"x4" wood int frm, concrete wall, r-19 cav ins, 10" thk, 5/8" gypsum board int fnsh 009862.9419.00.040336n 007432.9019.00.040256e 0011442.9519.00.040388s 007432.9019.00.040256w 0036162.9319.00.0401236all Partitions 12C-0sw 000000323 Windows 2 glazing, clr outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/4" thk: 2 glazing, clr outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/4" thk; NFRC rated (SHGC=0.30); 6.67 ft head ht 3969.9091222.800.30040n 109732.377522.800.30034e 253117.7326022.800.300143s 93632.366122.800.30029w 496020.2560922.800.300246all 2 glazing, clr outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/4" thk: 2 glazing, clr outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/4" thk; NFRC rated (SHGC=0.34); 6.67 ft head ht 17911.241325.800.34016n 58536.641325.800.34016e 32120.141325.800.34016s 58536.641325.800.34016w 167126.1165425.800.34064all Doors 11D0: Door, wd sc type 1477.0262229.600.39021n 1477.0262229.600.39021n 2957.02124529.600.39042all Ceilings 16B-30ad 0000008 Bold/italic values have been manually overridden 2018-Oct-05 09:21:52 Rig ht-Su ite® U niv er sal 20 18 18 .0.27 RSU1 4674 Page 2 ...Alpine - Mt Timp Stonebridge 3-4-4 - 100518.rup Calc = MJ8 Front Door faces: N 16B-50ad: Attic ceiling, asphalt shingles roof mat, r-50 ceil ins, 5/8" gypsum board int fnsh 13220.8324211.5250.00.0201593 Floors 19A-30bscp: Part floor, carpet flr fnsh, r-30 ins, frm flr, 12" thkns, 5/8" gypsum board int fnsh 300.401602.1730.00.03474 21A-32c: Bg floor, heavy dry or light damp soil, 8' depth, carpet flr fnsh 023211.5200.0201527 0 Bold/italic values have been manually overridden Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2018-Oct-05 09:21:52 Rig ht-Su ite® U niv er sal 20 18 18 .0.27 RSU1 4674 Page 1 ...Alpine - Mt Timp Stonebridge 3-4-4 - 100518.rup Calc = MJ8 Front Door faces: N Stonebridge 3-4-4Job:Project Summary Jul 27, 2018Date:Entire House Jay - Heating Supply CoBy: Project Information Mt Timpanogas, AlpineFor:Stonebridge 3-4-4, Idaho Falls, ID Email: jhooper@heatingsupplyco.com Notes: Design Information Idaho Falls Rgnl, ID, USWeather: Winter Design Conditions Summer Design Conditions Outside db °F-6 Outside db °F89Inside db °F70 Inside db °F75 Design TD °F76 Design TD °F14Daily range H Relative humidity %50Moisture difference gr/lb-28 Heating Summary Sensible Cooling Equipment Load Sizing Structure Btuh25528 Structure Btuh16375 Ducts Btuh7277 Ducts Btuh3806Central vent (107 cfm)7508 Btuh Central vent (107 cfm)Btuh1383 Outside air Outside airHumidificationBtuh0Blower Btuh0 Piping Btuh0Equipment load Btuh40313 Use manufacturer's data n Rate/swing multiplier 0.94InfiltrationEquipment sensible load Btuh20270 Method Latent Cooling Equipment Load SizingSimplified Construction quality Average0Fireplaces Structure Btuh863 Ducts Btuh-127Central vent (107 cfm)Btuh-1735 CoolingHeating Outside air30743074Area (ft²)Equipment latent load Btuh0 1323813238Volume (ft³)Air changes/hour 0.150.28 Equipment Total Load (Sen+Lat)Btuh20270 Equiv. AVF (cfm)3362 Req. total capacity at 0.85 SHR ton2.0 Heating Equipment Summary Cooling Equipment Summary Make Carrier Make CarrierTradeCarrier Performance 95 Single-...Trade CARRIER Model 59SP5A060E17--14 Cond 24ABB330ABN33AHRI ref 4702805 Coil CNPVP3017ALA+ AHRI ref 9858191Efficiency96.5 AFUE Efficiency 11.5 EER, 14 SEER Heating input Btuh60000 Sensible cooling Btuh22950Heating output Btuh58000 Latent cooling Btuh4050 Temperature rise °F70 Total cooling Btuh27000Actual air flow cfm900 Actual air flow cfm900 Air flow factor cfm/Btuh0.027 Air flow factor cfm/Btuh0.045Static pressure in H2O0.70 Static pressure in H2O0.70 Space thermostat Load sensible heat ratio 1.00 Bold/italic values have been manually overridden 2018-Oct-05 09:21:52 Rig ht-Su ite® U niv er sal 20 18 18 .0.27 RSU1 4674 Page 1 ...Alpine - Mt Timp Stonebridge 3-4-4 - 100518.rup Calc = MJ8 Front Door faces: N Stonebridge 3-4-4Job:AED Assessment Jul 27, 2018Date:Entire House Jay - Heating Supply CoBy: Project Information Mt Timpanogas, AlpineFor: Stonebridge 3-4-4, Idaho Falls, ID Email: jhooper@heatingsupplyco.com Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temp era ture (°F)Idaho Falls Rgnl, ID, US 1476Design TD (°F)ft4744Elevation: 5030Relative humidity (%)°N44Latitude: Outdoor:-28.435.2Moisture difference (gr/lb)CoolingHeating Infiltration:89-6Dry bul b (°F) )H(35-Da ily ra nge (°F) 61-We t bu lb (°F) 7.515.0Wind speed (mph) Test for Adequate Exposure Diversity Hourly Glazing Load Hourly Average AED limit Gl a z i n g l o a d ( B t u h ) Hour of Day 0 1,000 2,000 3,000 4,000 5,000 6,000 7,000 8,000 9,000 10,000 11,000 8 9 10 11 12 13 14 15 16 17 18 19 20 Maximum hourly glazing load exceeds average by 31.3%. House does not have adequate exposure diversity (AED), based on AED limit of 30%. AED excursion: 98 Btuh (PFG - 1.3*AFG) Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2018-Oct-05 09:21:53Right-Su ite® U niv er sal 20 18 18 .0.27 RSU1 4674 Page 1...Alpine - Mt Timp Stonebridge 3-4-4 - 100518.rup Calc = MJ8 Front Door faces: N Stonebridge 3-4-4Job:Right-J® W or ksheet Jul 27, 2018Date:Entire House Jay - Heating Supply CoBy: 1 Room name Entire House Bed 6 2 Exposed wall 310.0 ft 41.0 ft 3 Room height 8.1 ft 8.0 heat/coolft 4 Room dimensions ft234.0x1.0 5 Room area 3073.8 f t²234.0 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12F-2sw12F-2sw 0.0600.060 nn 4.564.56 0.290.29 224 163 743 47 0 0 0 0 .GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 nn 22.8022.80 9.909.90 40 0 912 396 0 0 0 0 .DD 11D011D0 0.3900.390 nn 29.6429.64 7.027.02 21 21 622 147 0 0 0 0 .WW 15B19-0wc-815B19-0wc-8 0.0690.069 nn 2.942.94 0.000.00 352 336 986 0 48 48 146 0 1 1 GG 2 glazing, clr outr,0.3402 glazing, clr outr,0.340 nn 25.8425.84 11.2211.22 16 0 413 179 0 0 0 0 WW 12F-2sw12F-2sw 0.0600.060 ee 4.564.56 0.290.29 320 286 1304 82 0 0 0 0 GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 ee 22.8022.80 32.2732.27 34 0 775 1097 0 0 0 0 WW 15B19-0wc-815B19-0wc-8 0.0690.069 ee 2.902.90 0.000.00 272 256 743 0 0 0 0 0 GG 2 glazing, clr outr,0.3402 glazing, clr outr,0.340 ee 25.8425.84 36.5836.58 16 0 413 585 0 0 0 0 WW 12F-2sw12F-2sw 0.0600.060 ss 4.564.56 0.290.29 404 261 1190 75 0 0 0 0 GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 ss 22.8022.80 17.7017.70 143 0 3260 2531 0 0 0 0 WW 15B19-0wc-815B19-0wc-8 0.0690.069 ss 2.952.95 0.000.00 404 388 1144 0 96 96 292 0 GG 2 glazing, clr outr,0.3402 glazing, clr outr,0.340 ss 25.8425.84 20.0620.06 16 0 413 321 0 0 0 0 WW 12F-2sw12F-2sw 0.0600.060 ww 4.564.56 0.290.29 232 203 926 58 0 0 0 0 GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 ww 22.8022.80 32.2732.27 29 0 661 936 0 0 0 0 WW 15B19-0wc-815B19-0wc-8 0.0690.069 ww 2.902.90 0.000.00 272 256 743 0 184 168 475 0 GG 2 glazing, clr outr,0.3402 glazing, clr outr,0.340 ww 25.8425.84 36.5836.58 16 0 413 585 16 0 413 585 PP 12C-0sw12C-0sw 0.0000.000 --0.000.00 0.000.00 344 323 0 0 0 0 0 0 DD 11D011D0 0.3900.390 nn 29.6429.64 7.027.02 21 21 622 147 0 0 0 0 CC 16B-30ad16B-30ad 0.0000.000 --0.000.00 0.000.00 8 8 0 0 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.521.52 0.830.83 1593 1593 2421 1322 0 0 0 0 FF 19A-30bscp19A-30bscp 0.0340.034 --2.172.17 0.400.40 74 74 160 30 0 0 0 0 FF 21A-32c21A-32c 0.0200.020 --1.521.52 0.000.00 1527 1527 2321 0 234 234 356 0 6 c) AED excursion 98 269 Envelope loss/gain 21190 8637 1682 855 12 a)Infiltration 4339 428 0 0 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 7 1610 0 0 Appliances/other 5700 0 Subtotal (lines 6 to 13)25528 16375 1682 855 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 25528 16375 1682 855 15 Duct loads 29%23%7277 3806 29%23%480 199 Total room load 32805 20181 2162 1053 Air required (cfm)Air required (cfm)900 900 59 47 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2018-Oct-05 09:21:53Right-Su ite® U niv er sal 20 18 18 .0.27 RSU1 4674 Page 2...Alpine - Mt Timp Stonebridge 3-4-4 - 100518.rup Calc = MJ8 Front Door faces: N Stonebridge 3-4-4Job:Right-J® W or ksheet Jul 27, 2018Date:Entire House Jay - Heating Supply CoBy: 1 Room name Bath 1 Mechanical 2 Exposed wall 5.0 ft 16.5 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft7.0x9.0 ft110.0x1.0 5 Room area 63.0 f t²110.0 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12F-2sw12F-2sw 0.0600.060 nn 4.564.56 0.290.29 0 0 0 0 0 0 0 0 .GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 nn 22.8022.80 9.909.90 0 0 0 0 0 0 0 0 .DD 11D011D0 0.3900.390 nn 29.6429.64 7.027.02 0 0 0 0 0 0 0 0 .WW 15B19-0wc-815B19-0wc-8 0.0690.069 nn 2.942.94 0.000.00 40 40 122 0 92 92 280 0 1 1 GG 2 glazing, clr outr,0.3402 glazing, clr outr,0.340 nn 25.8425.84 11.2211.22 0 0 0 0 0 0 0 0 WW 12F-2sw12F-2sw 0.0600.060 ee 4.564.56 0.290.29 0 0 0 0 0 0 0 0 GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 ee 22.8022.80 32.2732.27 0 0 0 0 0 0 0 0 WW 15B19-0wc-815B19-0wc-8 0.0690.069 ee 2.902.90 0.000.00 0 0 0 0 0 0 0 0 GG 2 glazing, clr outr,0.3402 glazing, clr outr,0.340 ee 25.8425.84 36.5836.58 0 0 0 0 0 0 0 0 WW 12F-2sw12F-2sw 0.0600.060 ss 4.564.56 0.290.29 0 0 0 0 0 0 0 0 GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 ss 22.8022.80 17.7017.70 0 0 0 0 0 0 0 0 WW 15B19-0wc-815B19-0wc-8 0.0690.069 ss 2.952.95 0.000.00 0 0 0 0 0 0 0 0 GG 2 glazing, clr outr,0.3402 glazing, clr outr,0.340 ss 25.8425.84 20.0620.06 0 0 0 0 0 0 0 0 WW 12F-2sw12F-2sw 0.0600.060 ww 4.564.56 0.290.29 0 0 0 0 0 0 0 0 GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 ww 22.8022.80 32.2732.27 0 0 0 0 0 0 0 0 WW 15B19-0wc-815B19-0wc-8 0.0690.069 ww 2.902.90 0.000.00 0 0 0 0 40 40 122 0 GG 2 glazing, clr outr,0.3402 glazing, clr outr,0.340 ww 25.8425.84 36.5836.58 0 0 0 0 0 0 0 0 PP 12C-0sw12C-0sw 0.0000.000 --0.000.00 0.000.00 0 0 0 0 0 0 0 0 DD 11D011D0 0.3900.390 nn 29.6429.64 7.027.02 0 0 0 0 0 0 0 0 CC 16B-30ad16B-30ad 0.0000.000 --0.000.00 0.000.00 0 0 0 0 8 8 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.521.52 0.830.83 0 0 0 0 0 0 0 0 FF 19A-30bscp19A-30bscp 0.0340.034 --2.172.17 0.400.40 0 0 0 0 0 0 0 0 FF 21A-32c21A-32c 0.0200.020 --1.521.52 0.000.00 63 63 96 0 110 110 167 0 6 c) AED excursion 0 0 Envelope loss/gain 217 0 568 0 12 a)Infiltration 0 0 0 0 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)217 0 568 0 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 236 0 -568 0 14 Subtotal 453 0 0 0 15 Duct loads 29%23%129 0 29%23%0 0 Total room load 583 0 0 0 Air required (cfm)Air required (cfm)16 0 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2018-Oct-05 09:21:53Right-Su ite® U niv er sal 20 18 18 .0.27 RSU1 4674 Page 3...Alpine - Mt Timp Stonebridge 3-4-4 - 100518.rup Calc = MJ8 Front Door faces: N Stonebridge 3-4-4Job:Right-J® W or ksheet Jul 27, 2018Date:Entire House Jay - Heating Supply CoBy: 1 Room name Stairs 1 Bed 5 2 Exposed wall 0 ft 13.0 ft 3 Room height 13.9 heat/coolft 8.0 heat/coolft 4 Room dimensions ft4.0x15.5 ft174.0x1.0 5 Room area 62.0 f t²174.0 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12F-2sw12F-2sw 0.0600.060 nn 4.564.56 0.290.29 0 0 0 0 0 0 0 0 .GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 nn 22.8022.80 9.909.90 0 0 0 0 0 0 0 0 .DD 11D011D0 0.3900.390 nn 29.6429.64 7.027.02 0 0 0 0 0 0 0 0 .WW 15B19-0wc-815B19-0wc-8 0.0690.069 nn 2.942.94 0.000.00 0 0 0 0 56 40 86 0 1 1 GG 2 glazing, clr outr,0.3402 glazing, clr outr,0.340 nn 25.8425.84 11.2211.22 0 0 0 0 16 0 413 179 WW 12F-2sw12F-2sw 0.0600.060 ee 4.564.56 0.290.29 0 0 0 0 0 0 0 0 GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 ee 22.8022.80 32.2732.27 0 0 0 0 0 0 0 0 WW 15B19-0wc-815B19-0wc-8 0.0690.069 ee 2.902.90 0.000.00 0 0 0 0 0 0 0 0 GG 2 glazing, clr outr,0.3402 glazing, clr outr,0.340 ee 25.8425.84 36.5836.58 0 0 0 0 0 0 0 0 WW 12F-2sw12F-2sw 0.0600.060 ss 4.564.56 0.290.29 0 0 0 0 0 0 0 0 GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 ss 22.8022.80 17.7017.70 0 0 0 0 0 0 0 0 WW 15B19-0wc-815B19-0wc-8 0.0690.069 ss 2.952.95 0.000.00 0 0 0 0 0 0 0 0 GG 2 glazing, clr outr,0.3402 glazing, clr outr,0.340 ss 25.8425.84 20.0620.06 0 0 0 0 0 0 0 0 WW 12F-2sw12F-2sw 0.0600.060 ww 4.564.56 0.290.29 0 0 0 0 0 0 0 0 GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 ww 22.8022.80 32.2732.27 0 0 0 0 0 0 0 0 WW 15B19-0wc-815B19-0wc-8 0.0690.069 ww 2.902.90 0.000.00 0 0 0 0 48 48 146 0 GG 2 glazing, clr outr,0.3402 glazing, clr outr,0.340 ww 25.8425.84 36.5836.58 0 0 0 0 0 0 0 0 PP 12C-0sw12C-0sw 0.0000.000 --0.000.00 0.000.00 0 0 0 0 52 31 0 0 DD 11D011D0 0.3900.390 nn 29.6429.64 7.027.02 0 0 0 0 21 21 622 147 CC 16B-30ad16B-30ad 0.0000.000 --0.000.00 0.000.00 0 0 0 0 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.521.52 0.830.83 46 46 70 38 0 0 0 0 FF 19A-30bscp19A-30bscp 0.0340.034 --2.172.17 0.400.40 0 0 0 0 0 0 0 0 FF 21A-32c21A-32c 0.0200.020 --1.521.52 0.000.00 62 62 94 0 174 174 264 0 6 c) AED excursion -2 -18 Envelope loss/gain 164 36 1533 309 12 a)Infiltration 0 0 0 0 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)164 36 1533 309 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution -164 -36 223 11 14 Subtotal 0 0 1756 320 15 Duct loads 29%23%0 0 29%23%501 74 Total room load 0 0 2256 395 Air required (cfm)Air required (cfm)0 0 62 18 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2018-Oct-05 09:21:53Right-Su ite® U niv er sal 20 18 18 .0.27 RSU1 4674 Page 4...Alpine - Mt Timp Stonebridge 3-4-4 - 100518.rup Calc = MJ8 Front Door faces: N Stonebridge 3-4-4Job:Right-J® W or ksheet Jul 27, 2018Date:Entire House Jay - Heating Supply CoBy: 1 Room name Bed 4 Family Room 2 Exposed wall 28.5 ft 58.5 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft218.0x1.0 ft666.0x1.0 5 Room area 218.0 f t²666.0 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12F-2sw12F-2sw 0.0600.060 nn 4.564.56 0.290.29 0 0 0 0 0 0 0 0 .GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 nn 22.8022.80 9.909.90 0 0 0 0 0 0 0 0 .DD 11D011D0 0.3900.390 nn 29.6429.64 7.027.02 0 0 0 0 0 0 0 0 .WW 15B19-0wc-815B19-0wc-8 0.0690.069 nn 2.942.94 0.000.00 116 116 353 0 0 0 0 0 1 1 GG 2 glazing, clr outr,0.3402 glazing, clr outr,0.340 nn 25.8425.84 11.2211.22 0 0 0 0 0 0 0 0 WW 12F-2sw12F-2sw 0.0600.060 ee 4.564.56 0.290.29 0 0 0 0 0 0 0 0 GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 ee 22.8022.80 32.2732.27 0 0 0 0 0 0 0 0 WW 15B19-0wc-815B19-0wc-8 0.0690.069 ee 2.902.90 0.000.00 112 96 257 0 160 160 486 0 GG 2 glazing, clr outr,0.3402 glazing, clr outr,0.340 ee 25.8425.84 36.5836.58 16 0 413 585 0 0 0 0 WW 12F-2sw12F-2sw 0.0600.060 ss 4.564.56 0.290.29 0 0 0 0 0 0 0 0 GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 ss 22.8022.80 17.7017.70 0 0 0 0 0 0 0 0 WW 15B19-0wc-815B19-0wc-8 0.0690.069 ss 2.952.95 0.000.00 0 0 0 0 308 292 852 0 GG 2 glazing, clr outr,0.3402 glazing, clr outr,0.340 ss 25.8425.84 20.0620.06 0 0 0 0 16 0 413 321 WW 12F-2sw12F-2sw 0.0600.060 ww 4.564.56 0.290.29 0 0 0 0 0 0 0 0 GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 ww 22.8022.80 32.2732.27 0 0 0 0 0 0 0 0 WW 15B19-0wc-815B19-0wc-8 0.0690.069 ww 2.902.90 0.000.00 0 0 0 0 0 0 0 0 GG 2 glazing, clr outr,0.3402 glazing, clr outr,0.340 ww 25.8425.84 36.5836.58 0 0 0 0 0 0 0 0 PP 12C-0sw12C-0sw 0.0000.000 --0.000.00 0.000.00 0 0 0 0 0 0 0 0 DD 11D011D0 0.3900.390 nn 29.6429.64 7.027.02 0 0 0 0 0 0 0 0 CC 16B-30ad16B-30ad 0.0000.000 --0.000.00 0.000.00 0 0 0 0 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.521.52 0.830.83 0 0 0 0 0 0 0 0 FF 19A-30bscp19A-30bscp 0.0340.034 --2.172.17 0.400.40 0 0 0 0 0 0 0 0 FF 21A-32c21A-32c 0.0200.020 --1.521.52 0.000.00 218 218 331 0 666 666 1012 0 6 c) AED excursion 54 6 Envelope loss/gain 1354 640 2765 327 12 a)Infiltration 0 0 0 0 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 2 460 Appliances/other 0 900 Subtotal (lines 6 to 13)1354 640 2765 1687 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 21 5 252 20 14 Subtotal 1375 644 3017 1707 15 Duct loads 29%23%392 150 29%23%860 397 Total room load 1767 794 3877 2104 Air required (cfm)Air required (cfm)48 35 106 94 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2018-Oct-05 09:21:53Right-Su ite® U niv er sal 20 18 18 .0.27 RSU1 4674 Page 5...Alpine - Mt Timp Stonebridge 3-4-4 - 100518.rup Calc = MJ8 Front Door faces: N Stonebridge 3-4-4Job:Right-J® W or ksheet Jul 27, 2018Date:Entire House Jay - Heating Supply CoBy: 1 Room name Master Bed Master Bath 2 Exposed wall 34.0 ft 9.0 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft18.0x14.0 ft10.0x9.0 5 Room area 252.0 f t²90.0 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12F-2sw12F-2sw 0.0600.060 nn 4.564.56 0.290.29 0 0 0 0 0 0 0 0 .GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 nn 22.8022.80 9.909.90 0 0 0 0 0 0 0 0 .DD 11D011D0 0.3900.390 nn 29.6429.64 7.027.02 0 0 0 0 0 0 0 0 .WW 15B19-0wc-815B19-0wc-8 0.0690.069 nn 2.942.94 0.000.00 0 0 0 0 0 0 0 0 1 1 GG 2 glazing, clr outr,0.3402 glazing, clr outr,0.340 nn 25.8425.84 11.2211.22 0 0 0 0 0 0 0 0 WW 12F-2sw12F-2sw 0.0600.060 ee 4.564.56 0.290.29 144 114 520 33 0 0 0 0 GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 ee 22.8022.80 32.2732.27 30 0 684 968 0 0 0 0 WW 15B19-0wc-815B19-0wc-8 0.0690.069 ee 2.902.90 0.000.00 0 0 0 0 0 0 0 0 GG 2 glazing, clr outr,0.3402 glazing, clr outr,0.340 ee 25.8425.84 36.5836.58 0 0 0 0 0 0 0 0 WW 12F-2sw12F-2sw 0.0600.060 ss 4.564.56 0.290.29 112 87 397 25 72 63 287 18 GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 ss 22.8022.80 17.7017.70 25 0 570 442 9 0 205 159 WW 15B19-0wc-815B19-0wc-8 0.0690.069 ss 2.952.95 0.000.00 0 0 0 0 0 0 0 0 GG 2 glazing, clr outr,0.3402 glazing, clr outr,0.340 ss 25.8425.84 20.0620.06 0 0 0 0 0 0 0 0 WW 12F-2sw12F-2sw 0.0600.060 ww 4.564.56 0.290.29 16 16 73 5 0 0 0 0 GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 ww 22.8022.80 32.2732.27 0 0 0 0 0 0 0 0 WW 15B19-0wc-815B19-0wc-8 0.0690.069 ww 2.902.90 0.000.00 0 0 0 0 0 0 0 0 GG 2 glazing, clr outr,0.3402 glazing, clr outr,0.340 ww 25.8425.84 36.5836.58 0 0 0 0 0 0 0 0 PP 12C-0sw12C-0sw 0.0000.000 --0.000.00 0.000.00 0 0 0 0 0 0 0 0 DD 11D011D0 0.3900.390 nn 29.6429.64 7.027.02 0 0 0 0 0 0 0 0 CC 16B-30ad16B-30ad 0.0000.000 --0.000.00 0.000.00 0 0 0 0 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.521.52 0.830.83 252 252 383 209 90 90 137 75 FF 19A-30bscp19A-30bscp 0.0340.034 --2.172.17 0.400.40 28 28 61 11 0 0 0 0 FF 21A-32c21A-32c 0.0200.020 --1.521.52 0.000.00 0 0 0 0 0 0 0 0 6 c) AED excursion -159 33 Envelope loss/gain 2687 1534 629 285 12 a)Infiltration 1000 99 265 26 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 1 230 0 0 Appliances/other 900 0 Subtotal (lines 6 to 13)3687 2763 894 311 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 23 12 35 18 14 Subtotal 3711 2775 929 330 15 Duct loads 29%23%1058 645 29%23%265 77 Total room load 4769 3420 1194 406 Air required (cfm)Air required (cfm)131 153 33 18 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2018-Oct-05 09:21:53Right-Su ite® U niv er sal 20 18 18 .0.27 RSU1 4674 Page 6...Alpine - Mt Timp Stonebridge 3-4-4 - 100518.rup Calc = MJ8 Front Door faces: N Stonebridge 3-4-4Job:Right-J® W or ksheet Jul 27, 2018Date:Entire House Jay - Heating Supply CoBy: 1 Room name Master WIC Bath 2 2 Exposed wall 0 ft 5.0 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft6.0x9.0 ft5.0x8.5 5 Room area 54.0 f t²42.5 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12F-2sw12F-2sw 0.0600.060 nn 4.564.56 0.290.29 0 0 0 0 0 0 0 0 .GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 nn 22.8022.80 9.909.90 0 0 0 0 0 0 0 0 .DD 11D011D0 0.3900.390 nn 29.6429.64 7.027.02 0 0 0 0 0 0 0 0 .WW 15B19-0wc-815B19-0wc-8 0.0690.069 nn 2.942.94 0.000.00 0 0 0 0 0 0 0 0 1 1 GG 2 glazing, clr outr,0.3402 glazing, clr outr,0.340 nn 25.8425.84 11.2211.22 0 0 0 0 0 0 0 0 WW 12F-2sw12F-2sw 0.0600.060 ee 4.564.56 0.290.29 0 0 0 0 40 36 164 10 GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 ee 22.8022.80 32.2732.27 0 0 0 0 4 0 91 129 WW 15B19-0wc-815B19-0wc-8 0.0690.069 ee 2.902.90 0.000.00 0 0 0 0 0 0 0 0 GG 2 glazing, clr outr,0.3402 glazing, clr outr,0.340 ee 25.8425.84 36.5836.58 0 0 0 0 0 0 0 0 WW 12F-2sw12F-2sw 0.0600.060 ss 4.564.56 0.290.29 0 0 0 0 0 0 0 0 GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 ss 22.8022.80 17.7017.70 0 0 0 0 0 0 0 0 WW 15B19-0wc-815B19-0wc-8 0.0690.069 ss 2.952.95 0.000.00 0 0 0 0 0 0 0 0 GG 2 glazing, clr outr,0.3402 glazing, clr outr,0.340 ss 25.8425.84 20.0620.06 0 0 0 0 0 0 0 0 WW 12F-2sw12F-2sw 0.0600.060 ww 4.564.56 0.290.29 0 0 0 0 0 0 0 0 GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 ww 22.8022.80 32.2732.27 0 0 0 0 0 0 0 0 WW 15B19-0wc-815B19-0wc-8 0.0690.069 ww 2.902.90 0.000.00 0 0 0 0 0 0 0 0 GG 2 glazing, clr outr,0.3402 glazing, clr outr,0.340 ww 25.8425.84 36.5836.58 0 0 0 0 0 0 0 0 PP 12C-0sw12C-0sw 0.0000.000 --0.000.00 0.000.00 0 0 0 0 0 0 0 0 DD 11D011D0 0.3900.390 nn 29.6429.64 7.027.02 0 0 0 0 0 0 0 0 CC 16B-30ad16B-30ad 0.0000.000 --0.000.00 0.000.00 0 0 0 0 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.521.52 0.830.83 54 54 82 45 43 43 65 35 FF 19A-30bscp19A-30bscp 0.0340.034 --2.172.17 0.400.40 0 0 0 0 0 0 0 0 FF 21A-32c21A-32c 0.0200.020 --1.521.52 0.000.00 0 0 0 0 0 0 0 0 6 c) AED excursion -2 9 Envelope loss/gain 82 42 320 183 12 a)Infiltration 0 0 147 15 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)82 42 467 198 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution -82 -42 0 0 14 Subtotal 0 0 467 198 15 Duct loads 29%23%0 0 29%23%133 46 Total room load 0 0 600 244 Air required (cfm)Air required (cfm)0 0 16 11 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2018-Oct-05 09:21:53Right-Su ite® U niv er sal 20 18 18 .0.27 RSU1 4674 Page 7...Alpine - Mt Timp Stonebridge 3-4-4 - 100518.rup Calc = MJ8 Front Door faces: N Stonebridge 3-4-4Job:Right-J® W or ksheet Jul 27, 2018Date:Entire House Jay - Heating Supply CoBy: 1 Room name Bed 2 Bed 3 2 Exposed wall 28.0 ft 12.0 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft162.5x1.0 ft11.0x12.0 5 Room area 162.5 f t²132.0 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12F-2sw12F-2sw 0.0600.060 nn 4.564.56 0.290.29 88 68 310 20 96 76 347 22 .GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 nn 22.8022.80 9.909.90 20 0 456 198 20 0 456 198 .DD 11D011D0 0.3900.390 nn 29.6429.64 7.027.02 0 0 0 0 0 0 0 0 .WW 15B19-0wc-815B19-0wc-8 0.0690.069 nn 2.942.94 0.000.00 0 0 0 0 0 0 0 0 1 1 GG 2 glazing, clr outr,0.3402 glazing, clr outr,0.340 nn 25.8425.84 11.2211.22 0 0 0 0 0 0 0 0 WW 12F-2sw12F-2sw 0.0600.060 ee 4.564.56 0.290.29 120 120 547 35 0 0 0 0 GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 ee 22.8022.80 32.2732.27 0 0 0 0 0 0 0 0 WW 15B19-0wc-815B19-0wc-8 0.0690.069 ee 2.902.90 0.000.00 0 0 0 0 0 0 0 0 GG 2 glazing, clr outr,0.3402 glazing, clr outr,0.340 ee 25.8425.84 36.5836.58 0 0 0 0 0 0 0 0 WW 12F-2sw12F-2sw 0.0600.060 ss 4.564.56 0.290.29 0 0 0 0 0 0 0 0 GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 ss 22.8022.80 17.7017.70 0 0 0 0 0 0 0 0 WW 15B19-0wc-815B19-0wc-8 0.0690.069 ss 2.952.95 0.000.00 0 0 0 0 0 0 0 0 GG 2 glazing, clr outr,0.3402 glazing, clr outr,0.340 ss 25.8425.84 20.0620.06 0 0 0 0 0 0 0 0 WW 12F-2sw12F-2sw 0.0600.060 ww 4.564.56 0.290.29 16 16 73 5 0 0 0 0 GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 ww 22.8022.80 32.2732.27 0 0 0 0 0 0 0 0 WW 15B19-0wc-815B19-0wc-8 0.0690.069 ww 2.902.90 0.000.00 0 0 0 0 0 0 0 0 GG 2 glazing, clr outr,0.3402 glazing, clr outr,0.340 ww 25.8425.84 36.5836.58 0 0 0 0 0 0 0 0 PP 12C-0sw12C-0sw 0.0000.000 --0.000.00 0.000.00 0 0 0 0 0 0 0 0 DD 11D011D0 0.3900.390 nn 29.6429.64 7.027.02 0 0 0 0 0 0 0 0 CC 16B-30ad16B-30ad 0.0000.000 --0.000.00 0.000.00 0 0 0 0 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.521.52 0.830.83 163 163 247 135 132 132 201 110 FF 19A-30bscp19A-30bscp 0.0340.034 --2.172.17 0.400.40 22 22 48 9 0 0 0 0 FF 21A-32c21A-32c 0.0200.020 --1.521.52 0.000.00 0 0 0 0 0 0 0 0 6 c) AED excursion -26 -20 Envelope loss/gain 1681 374 1003 310 12 a)Infiltration 824 81 353 35 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)2505 455 1356 344 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 2505 455 1356 344 15 Duct loads 29%23%714 106 29%23%387 80 Total room load 3218 561 1743 424 Air required (cfm)Air required (cfm)88 25 48 19 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2018-Oct-05 09:21:53Right-Su ite® U niv er sal 20 18 18 .0.27 RSU1 4674 Page 8...Alpine - Mt Timp Stonebridge 3-4-4 - 100518.rup Calc = MJ8 Front Door faces: N Stonebridge 3-4-4Job:Right-J® W or ksheet Jul 27, 2018Date:Entire House Jay - Heating Supply CoBy: 1 Room name Entry Mud Room 2 Exposed wall 5.0 ft 0 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft142.5x1.0 ft58.3x1.0 5 Room area 142.5 f t²58.3 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12F-2sw12F-2sw 0.0600.060 nn 4.564.56 0.290.29 40 19 87 5 0 0 0 0 .GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 nn 22.8022.80 9.909.90 0 0 0 0 0 0 0 0 .DD 11D011D0 0.3900.390 nn 29.6429.64 7.027.02 21 21 622 147 0 0 0 0 .WW 15B19-0wc-815B19-0wc-8 0.0690.069 nn 2.942.94 0.000.00 0 0 0 0 0 0 0 0 1 1 GG 2 glazing, clr outr,0.3402 glazing, clr outr,0.340 nn 25.8425.84 11.2211.22 0 0 0 0 0 0 0 0 WW 12F-2sw12F-2sw 0.0600.060 ee 4.564.56 0.290.29 0 0 0 0 0 0 0 0 GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 ee 22.8022.80 32.2732.27 0 0 0 0 0 0 0 0 WW 15B19-0wc-815B19-0wc-8 0.0690.069 ee 2.902.90 0.000.00 0 0 0 0 0 0 0 0 GG 2 glazing, clr outr,0.3402 glazing, clr outr,0.340 ee 25.8425.84 36.5836.58 0 0 0 0 0 0 0 0 WW 12F-2sw12F-2sw 0.0600.060 ss 4.564.56 0.290.29 0 0 0 0 0 0 0 0 GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 ss 22.8022.80 17.7017.70 0 0 0 0 0 0 0 0 WW 15B19-0wc-815B19-0wc-8 0.0690.069 ss 2.952.95 0.000.00 0 0 0 0 0 0 0 0 GG 2 glazing, clr outr,0.3402 glazing, clr outr,0.340 ss 25.8425.84 20.0620.06 0 0 0 0 0 0 0 0 WW 12F-2sw12F-2sw 0.0600.060 ww 4.564.56 0.290.29 0 0 0 0 0 0 0 0 GG 2 glazing, clr outr,0.3002 glazing, clr outr,0.300 ww 22.8022.80 32.2732.27 0 0 0 0 0 0 0 0 WW 15B19-0wc-815B19-0wc-8 0.0690.069 ww 2.902.90 0.000.00 0 0 0 0 0 0 0 0 GG 2 glazing, clr outr,0.3402 glazing, clr outr,0.340 ww 25.8425.84 36.5836.58 0 0 0 0 0 0 0 0 PP 12C-0sw12C-0sw 0.0000.000 --0.000.00 0.000.00 84 84 0 0 120 120 0 0 DD 11D011D0 0.3900.390 nn 29.6429.64 7.027.02 0 0 0 0 0 0 0 0 CC 16B-30ad16B-30ad 0.0000.000 --0.000.00 0.000.00 0 0 0 0 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.521.52 0.830.83 143 143 217 118 58 58 89 48 FF 19A-30bscp19A-30bscp 0.0340.034 --2.172.17 0.400.40 0 0 0 0 0 0 0 0 FF 21A-32c21A-32c 0.0200.020 --1.521.52 0.000.00 0 0 0 0 0 0 0 0 6 c) AED excursion -16 -30 Envelope loss/gain 926 256 89 19 12 a)Infiltration 147 15 0 0 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 500 Subtotal (lines 6 to 13)1073 270 89 519 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 1073 270 89 519 15 Duct loads 29%23%306 63 29%23%25 120 Total room load 1379 333 114 639 Air required (cfm)Air required (cfm)38 15 3 28 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2018-Oct-05 09:21:53Right-Su ite® U niv er sal 20 18 18 .0.27 RSU1 4674 Page 9...Alpine - Mt Timp Stonebridge 3-4-4 - 100518.rup Calc = MJ8 Front Door faces: N Stonebridge 3-4-4Job:Right-J® W or ksheet Jul 27, 2018Date:Entire House Jay - Heating Supply CoBy: 1 Room name Kitchen/Great 2 Exposed wall 54.5 ft 3 Room height 8.0 heat/coolft 4 Room dimensions ft613.0x1.0 5 Room area 613.0 f t² Ty Construction U-value Or HTM Area (f t²)Load Area Load number (Bt uh/f t²-°F)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 W 12F-2sw 0.060 n 4.56 0.29 0 0 0 0 .G 2 glazing, clr outr,0.300 n 22.80 9.90 0 0 0 0 .D 11D0 0.390 n 29.64 7.02 0 0 0 0 .W 15B19-0wc-8 0.069 n 2.94 0.00 0 0 0 0 1 1 G 2 glazing, clr outr,0.340 n 25.84 11.22 0 0 0 0 W 12F-2sw 0.060 e 4.56 0.29 16 16 73 5 G 2 glazing, clr outr,0.300 e 22.80 32.27 0 0 0 0 W 15B19-0wc-8 0.069 e 2.90 0.00 0 0 0 0 G 2 glazing, clr outr,0.340 e 25.84 36.58 0 0 0 0 W 12F-2sw 0.060 s 4.56 0.29 220 111 506 32 G 2 glazing, clr outr,0.300 s 22.80 17.70 109 0 2485 1929 W 15B19-0wc-8 0.069 s 2.95 0.00 0 0 0 0 G 2 glazing, clr outr,0.340 s 25.84 20.06 0 0 0 0 W 12F-2sw 0.060 w 4.56 0.29 200 171 780 49 G 2 glazing, clr outr,0.300 w 22.80 32.27 29 0 661 936 W 15B19-0wc-8 0.069 w 2.90 0.00 0 0 0 0 G 2 glazing, clr outr,0.340 w 25.84 36.58 0 0 0 0 P 12C-0sw 0.000 -0.00 0.00 88 88 0 0 D 11D0 0.390 n 29.64 7.02 0 0 0 0 C 16B-30ad 0.000 -0.00 0.00 0 0 0 0 C 16B-50ad 0.020 -1.52 0.83 613 613 932 509 F 19A-30bscp 0.034 -2.17 0.40 24 24 52 10 F 21A-32c 0.020 -1.52 0.00 0 0 0 0 6 c) AED excursion -1 Envelope loss/gain 5489 3468 12 a)Infiltration 1603 158 b)Room ventilation 0 0 13 Internal gains:Occupants @ 230 4 920 Appliances/other 3400 Subtotal (lines 6 to 13)7092 7946 Less external load 0 0 Less transfer 0 0 Redistribution 23 12 14 Subtotal 7116 7958 15 Duct loads 29%23%2028 1849 Total room load 9144 9808 Air required (cfm)251 437 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2018-Oct-05 09:21:54Right-Su ite® U niv er sal 20 18 18 .0.27 RSU1 4674 Page 1...Alpine - Mt Timp Stonebridge 3-4-4 - 100518.rup Calc = MJ8 Front Door faces: N Stonebridge 3-4-4Job:Right-J8® For m J1 Jul 27, 2018Date:Entire House Jay - Heating Supply CoBy: 1 Name of Room Entire House Bed 6 2 Running Feet of Exposed Wall 310.0 ft 41.0 ft 3 Ceiling Ht (Ft) and Gross Wall Area (SqFt)8.1 f t²7179.3ft 8.0 f t²560.0ft 4 Room Dimensions (Ft) and Floor Plan Area (SqFt)f t²3073.8 1.0 x 234.0 ft f t²234.0 5 Ceiling Slope (Deg.) and Gross Ceiling Area (SqFt)0 f t²3119.8°0 f t²234.0° Type of Exposure Const., Number Type of Exposure Const., Number Panel Faces HTMPanel Faces HTM Area or Lenght BtuhArea or Lenght Btuh Area or Lenght BtuhArea or Lenght Btuh Htg.Htg.Clg.Clg.HeatingHeating S-ClgS-Clg L-ClgL-Clg HeatingHeating S-ClgS-Clg L-ClgL-Clg 6 WallWall 12F-2sw12F-2sw nn 4.564.56 0.290.29 224 743 47 0 0 0 .GlazGlaz 2 glazing, clr outr,n2 glazing, clr outr,n 22.8022.80 9.909.90 40 912 396 0 0 0 .DoorDoor 11D011D0 nn 29.6429.64 7.027.02 21 622 147 0 0 0 .WallWall 15B19-0wc-815B19-0wc-8 nn 2.942.94 0.000.00 352 986 0 48 146 0 1 1 GlazGlaz 2 glazing, clr outr,n2 glazing, clr outr,n 25.8425.84 11.2211.22 16 413 179 0 0 0 WallWall 12F-2sw12F-2sw ee 4.564.56 0.290.29 320 1304 82 0 0 0 GlazGlaz 2 glazing, clr outr,e2 glazing, clr outr,e 22.8022.80 32.2732.27 34 775 1097 0 0 0 WallWall 15B19-0wc-815B19-0wc-8 ee 2.902.90 0.000.00 272 743 0 0 0 0 GlazGlaz 2 glazing, clr outr,e2 glazing, clr outr,e 25.8425.84 36.5836.58 16 413 585 0 0 0 WallWall 12F-2sw12F-2sw ss 4.564.56 0.290.29 404 1190 75 0 0 0 GlazGlaz 2 glazing, clr outr,s2 glazing, clr outr,s 22.8022.80 17.7017.70 143 3260 2531 0 0 0 WallWall 15B19-0wc-815B19-0wc-8 ss 2.952.95 0.000.00 404 1144 0 96 292 0 GlazGlaz 2 glazing, clr outr,s2 glazing, clr outr,s 25.8425.84 20.0620.06 16 413 321 0 0 0 WallWall 12F-2sw12F-2sw ww 4.564.56 0.290.29 232 926 58 0 0 0 GlazGlaz 2 glazing, clr outr,w2 glazing, clr outr,w 22.8022.80 32.2732.27 29 661 936 0 0 0 WallWall 15B19-0wc-815B19-0wc-8 ww 2.902.90 0.000.00 272 743 0 184 475 0 GlazGlaz 2 glazing, clr outr,w2 glazing, clr outr,w 25.8425.84 36.5836.58 16 413 585 16 413 585 WallWall 12C-0sw12C-0sw --0.000.00 0.000.00 344 0 0 0 0 0 DoorDoor 11D011D0 nn 29.6429.64 7.027.02 21 622 147 0 0 0 CeilCeil 16B-30ad16B-30ad --0.000.00 0.000.00 8 0 0 0 0 0 CeilCeil 16B-50ad16B-50ad --1.521.52 0.830.83 1593 2421 1322 0 0 0 FlorFlor 19A-30bscp19A-30bscp --2.172.17 0.400.40 74 160 30 0 0 0 FlorFlor 21A-32c21A-32c --1.521.52 0.000.00 1527 2321 0 234 356 0 Infiltration Heating Load (Btuh)0.280.28 4339 0 Effect WAR WAR 12 Sensible Load (Btuh)ACH 1.00 428 0 0 0.150.15 Latent Load (Btuh)-537 Internal a Occupants at 230 and 200 Btuh 7 1610 1400 0 0 0 b Scenario number 5700 0 13 c Default Adjustments d Custom Appliances 0 0 0 0 e Plants 0 0 14 Subtotals Sum lines 6 through 12Sum lines 6 through 12 25528 16375 863 1682 855 Duct EHLF & ESGF 0.2850.285 0.2320.232 7277 3806 480 199 15 Loads ELG -127 -10 Vent CfmVent Cfm16Ventilation Loads 107107 E CfmE Cfm 107107 7508 1383 -1735 17 Winter Humidification Load Gal/Day 00 0 18 Piping Load 0 19 Blower Heat 0 20 AED Excursion & Latent Moisture Migration Load 98 269 21 Total Load Sum lines 13 through 19Sum lines 13 through 19 40313 21564 0 2162 1053 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2018-Oct-05 09:21:54Right-Su ite® U niv er sal 20 18 18 .0.27 RSU1 4674 Page 2...Alpine - Mt Timp Stonebridge 3-4-4 - 100518.rup Calc = MJ8 Front Door faces: N Stonebridge 3-4-4Job:Right-J8® For m J1 Jul 27, 2018Date:Entire House Jay - Heating Supply CoBy: 1 Name of Room Bath 1 Mechanical 2 Running Feet of Exposed Wall 5.0 ft 16.5 ft 3 Ceiling Ht (Ft) and Gross Wall Area (SqFt)8.0 f t²256.0ft 8.0 f t²376.0ft 4 Room Dimensions (Ft) and Floor Plan Area (SqFt)9.0 x 7.0 ft f t²63.0 1.0 x 110.0 ft f t²110.0 5 Ceiling Slope (Deg.) and Gross Ceiling Area (SqFt)0 f t²63.0°0 f t²110.0° Type of Exposure Const., Number Type of Exposure Const., Number Panel Faces HTMPanel Faces HTM Area or Lenght BtuhArea or Lenght Btuh Area or Lenght BtuhArea or Lenght Btuh Htg.Htg.Clg.Clg.HeatingHeating S-ClgS-Clg L-ClgL-Clg HeatingHeating S-ClgS-Clg L-ClgL-Clg 6 WallWall 12F-2sw12F-2sw nn 4.564.56 0.290.29 0 0 0 0 0 0 .GlazGlaz 2 glazing, clr outr,n2 glazing, clr outr,n 22.8022.80 9.909.90 0 0 0 0 0 0 .DoorDoor 11D011D0 nn 29.6429.64 7.027.02 0 0 0 0 0 0 .WallWall 15B19-0wc-815B19-0wc-8 nn 2.942.94 0.000.00 40 122 0 92 280 0 1 1 GlazGlaz 2 glazing, clr outr,n2 glazing, clr outr,n 25.8425.84 11.2211.22 0 0 0 0 0 0 WallWall 12F-2sw12F-2sw ee 4.564.56 0.290.29 0 0 0 0 0 0 GlazGlaz 2 glazing, clr outr,e2 glazing, clr outr,e 22.8022.80 32.2732.27 0 0 0 0 0 0 WallWall 15B19-0wc-815B19-0wc-8 ee 2.902.90 0.000.00 0 0 0 0 0 0 GlazGlaz 2 glazing, clr outr,e2 glazing, clr outr,e 25.8425.84 36.5836.58 0 0 0 0 0 0 WallWall 12F-2sw12F-2sw ss 4.564.56 0.290.29 0 0 0 0 0 0 GlazGlaz 2 glazing, clr outr,s2 glazing, clr outr,s 22.8022.80 17.7017.70 0 0 0 0 0 0 WallWall 15B19-0wc-815B19-0wc-8 ss 2.952.95 0.000.00 0 0 0 0 0 0 GlazGlaz 2 glazing, clr outr,s2 glazing, clr outr,s 25.8425.84 20.0620.06 0 0 0 0 0 0 WallWall 12F-2sw12F-2sw ww 4.564.56 0.290.29 0 0 0 0 0 0 GlazGlaz 2 glazing, clr outr,w2 glazing, clr outr,w 22.8022.80 32.2732.27 0 0 0 0 0 0 WallWall 15B19-0wc-815B19-0wc-8 ww 2.902.90 0.000.00 0 0 0 40 122 0 GlazGlaz 2 glazing, clr outr,w2 glazing, clr outr,w 25.8425.84 36.5836.58 0 0 0 0 0 0 WallWall 12C-0sw12C-0sw --0.000.00 0.000.00 0 0 0 0 0 0 DoorDoor 11D011D0 nn 29.6429.64 7.027.02 0 0 0 0 0 0 CeilCeil 16B-30ad16B-30ad --0.000.00 0.000.00 0 0 0 8 0 0 CeilCeil 16B-50ad16B-50ad --1.521.52 0.830.83 0 0 0 0 0 0 FlorFlor 19A-30bscp19A-30bscp --2.172.17 0.400.40 0 0 0 0 0 0 FlorFlor 21A-32c21A-32c --1.521.52 0.000.00 63 96 0 110 167 0 Infiltration Heating Load (Btuh)0.280.28 0 0 Effect WAR WAR 12 Sensible Load (Btuh)ACH 0 0 0 0 0.150.15 Latent Load (Btuh) Internal a Occupants at 230 and 200 Btuh 0 0 0 0 0 0 b Scenario number 0 0 13 c Default Adjustments d Custom Appliances 0 0 0 0 e Plants 0 0 14 Subtotals Sum lines 6 through 12Sum lines 6 through 12 453 0 0 0 Duct EHLF & ESGF 0.2850.285 0.2320.232 129 0 0 0 15 Loads ELG -3 -5 Vent CfmVent Cfm16Ventilation Loads 107107 E CfmE Cfm 107107 17 Winter Humidification Load Gal/Day 00 18 Piping Load 19 Blower Heat 20 AED Excursion & Latent Moisture Migration Load 0 0 21 Total Load Sum lines 13 through 19Sum lines 13 through 19 583 0 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2018-Oct-05 09:21:54Right-Su ite® U niv er sal 20 18 18 .0.27 RSU1 4674 Page 3...Alpine - Mt Timp Stonebridge 3-4-4 - 100518.rup Calc = MJ8 Front Door faces: N Stonebridge 3-4-4Job:Right-J8® For m J1 Jul 27, 2018Date:Entire House Jay - Heating Supply CoBy: 1 Name of Room Stairs 1 Bed 5 2 Running Feet of Exposed Wall 0 ft 13.0 ft 3 Ceiling Ht (Ft) and Gross Wall Area (SqFt)13.9 f t²312.0ft 8.0 f t²419.0ft 4 Room Dimensions (Ft) and Floor Plan Area (SqFt)15.5 x 4.0 ft f t²62.0 1.0 x 174.0 ft f t²174.0 5 Ceiling Slope (Deg.) and Gross Ceiling Area (SqFt)0 f t²108.0°0 f t²174.0° Type of Exposure Const., Number Type of Exposure Const., Number Panel Faces HTMPanel Faces HTM Area or Lenght BtuhArea or Lenght Btuh Area or Lenght BtuhArea or Lenght Btuh Htg.Htg.Clg.Clg.HeatingHeating S-ClgS-Clg L-ClgL-Clg HeatingHeating S-ClgS-Clg L-ClgL-Clg 6 WallWall 12F-2sw12F-2sw nn 4.564.56 0.290.29 0 0 0 0 0 0 .GlazGlaz 2 glazing, clr outr,n2 glazing, clr outr,n 22.8022.80 9.909.90 0 0 0 0 0 0 .DoorDoor 11D011D0 nn 29.6429.64 7.027.02 0 0 0 0 0 0 .WallWall 15B19-0wc-815B19-0wc-8 nn 2.942.94 0.000.00 0 0 0 56 86 0 1 1 GlazGlaz 2 glazing, clr outr,n2 glazing, clr outr,n 25.8425.84 11.2211.22 0 0 0 16 413 179 WallWall 12F-2sw12F-2sw ee 4.564.56 0.290.29 0 0 0 0 0 0 GlazGlaz 2 glazing, clr outr,e2 glazing, clr outr,e 22.8022.80 32.2732.27 0 0 0 0 0 0 WallWall 15B19-0wc-815B19-0wc-8 ee 2.902.90 0.000.00 0 0 0 0 0 0 GlazGlaz 2 glazing, clr outr,e2 glazing, clr outr,e 25.8425.84 36.5836.58 0 0 0 0 0 0 WallWall 12F-2sw12F-2sw ss 4.564.56 0.290.29 0 0 0 0 0 0 GlazGlaz 2 glazing, clr outr,s2 glazing, clr outr,s 22.8022.80 17.7017.70 0 0 0 0 0 0 WallWall 15B19-0wc-815B19-0wc-8 ss 2.952.95 0.000.00 0 0 0 0 0 0 GlazGlaz 2 glazing, clr outr,s2 glazing, clr outr,s 25.8425.84 20.0620.06 0 0 0 0 0 0 WallWall 12F-2sw12F-2sw ww 4.564.56 0.290.29 0 0 0 0 0 0 GlazGlaz 2 glazing, clr outr,w2 glazing, clr outr,w 22.8022.80 32.2732.27 0 0 0 0 0 0 WallWall 15B19-0wc-815B19-0wc-8 ww 2.902.90 0.000.00 0 0 0 48 146 0 GlazGlaz 2 glazing, clr outr,w2 glazing, clr outr,w 25.8425.84 36.5836.58 0 0 0 0 0 0 WallWall 12C-0sw12C-0sw --0.000.00 0.000.00 0 0 0 52 0 0 DoorDoor 11D011D0 nn 29.6429.64 7.027.02 0 0 0 21 622 147 CeilCeil 16B-30ad16B-30ad --0.000.00 0.000.00 0 0 0 0 0 0 CeilCeil 16B-50ad16B-50ad --1.521.52 0.830.83 46 70 38 0 0 0 FlorFlor 19A-30bscp19A-30bscp --2.172.17 0.400.40 0 0 0 0 0 0 FlorFlor 21A-32c21A-32c --1.521.52 0.000.00 62 94 0 174 264 0 Infiltration Heating Load (Btuh)0.280.28 0 0 Effect WAR WAR 12 Sensible Load (Btuh)ACH 0 0 0 0 0.150.15 Latent Load (Btuh) Internal a Occupants at 230 and 200 Btuh 0 0 0 0 0 0 b Scenario number 0 0 13 c Default Adjustments d Custom Appliances 0 0 0 0 e Plants 0 0 14 Subtotals Sum lines 6 through 12Sum lines 6 through 12 0 0 1756 320 Duct EHLF & ESGF 0.2850.285 0.2320.232 0 0 501 74 15 Loads ELG -3 -7 Vent CfmVent Cfm16Ventilation Loads 107107 E CfmE Cfm 107107 17 Winter Humidification Load Gal/Day 00 18 Piping Load 19 Blower Heat 20 AED Excursion & Latent Moisture Migration Load -2 -18 21 Total Load Sum lines 13 through 19Sum lines 13 through 19 0 0 2256 395 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2018-Oct-05 09:21:54Right-Su ite® U niv er sal 20 18 18 .0.27 RSU1 4674 Page 4...Alpine - Mt Timp Stonebridge 3-4-4 - 100518.rup Calc = MJ8 Front Door faces: N Stonebridge 3-4-4Job:Right-J8® For m J1 Jul 27, 2018Date:Entire House Jay - Heating Supply CoBy: 1 Name of Room Bed 4 Family Room 2 Running Feet of Exposed Wall 28.5 ft 58.5 ft 3 Ceiling Ht (Ft) and Gross Wall Area (SqFt)8.0 f t²496.0ft 8.0 f t²936.0ft 4 Room Dimensions (Ft) and Floor Plan Area (SqFt)1.0 x 218.0 ft f t²218.0 1.0 x 666.0 ft f t²666.0 5 Ceiling Slope (Deg.) and Gross Ceiling Area (SqFt)0 f t²218.0°0 f t²666.0° Type of Exposure Const., Number Type of Exposure Const., Number Panel Faces HTMPanel Faces HTM Area or Lenght BtuhArea or Lenght Btuh Area or Lenght BtuhArea or Lenght Btuh Htg.Htg.Clg.Clg.HeatingHeating S-ClgS-Clg L-ClgL-Clg HeatingHeating S-ClgS-Clg L-ClgL-Clg 6 WallWall 12F-2sw12F-2sw nn 4.564.56 0.290.29 0 0 0 0 0 0 .GlazGlaz 2 glazing, clr outr,n2 glazing, clr outr,n 22.8022.80 9.909.90 0 0 0 0 0 0 .DoorDoor 11D011D0 nn 29.6429.64 7.027.02 0 0 0 0 0 0 .WallWall 15B19-0wc-815B19-0wc-8 nn 2.942.94 0.000.00 116 353 0 0 0 0 1 1 GlazGlaz 2 glazing, clr outr,n2 glazing, clr outr,n 25.8425.84 11.2211.22 0 0 0 0 0 0 WallWall 12F-2sw12F-2sw ee 4.564.56 0.290.29 0 0 0 0 0 0 GlazGlaz 2 glazing, clr outr,e2 glazing, clr outr,e 22.8022.80 32.2732.27 0 0 0 0 0 0 WallWall 15B19-0wc-815B19-0wc-8 ee 2.902.90 0.000.00 112 257 0 160 486 0 GlazGlaz 2 glazing, clr outr,e2 glazing, clr outr,e 25.8425.84 36.5836.58 16 413 585 0 0 0 WallWall 12F-2sw12F-2sw ss 4.564.56 0.290.29 0 0 0 0 0 0 GlazGlaz 2 glazing, clr outr,s2 glazing, clr outr,s 22.8022.80 17.7017.70 0 0 0 0 0 0 WallWall 15B19-0wc-815B19-0wc-8 ss 2.952.95 0.000.00 0 0 0 308 852 0 GlazGlaz 2 glazing, clr outr,s2 glazing, clr outr,s 25.8425.84 20.0620.06 0 0 0 16 413 321 WallWall 12F-2sw12F-2sw ww 4.564.56 0.290.29 0 0 0 0 0 0 GlazGlaz 2 glazing, clr outr,w2 glazing, clr outr,w 22.8022.80 32.2732.27 0 0 0 0 0 0 WallWall 15B19-0wc-815B19-0wc-8 ww 2.902.90 0.000.00 0 0 0 0 0 0 GlazGlaz 2 glazing, clr outr,w2 glazing, clr outr,w 25.8425.84 36.5836.58 0 0 0 0 0 0 WallWall 12C-0sw12C-0sw --0.000.00 0.000.00 0 0 0 0 0 0 DoorDoor 11D011D0 nn 29.6429.64 7.027.02 0 0 0 0 0 0 CeilCeil 16B-30ad16B-30ad --0.000.00 0.000.00 0 0 0 0 0 0 CeilCeil 16B-50ad16B-50ad --1.521.52 0.830.83 0 0 0 0 0 0 FlorFlor 19A-30bscp19A-30bscp --2.172.17 0.400.40 0 0 0 0 0 0 FlorFlor 21A-32c21A-32c --1.521.52 0.000.00 218 331 0 666 1012 0 Infiltration Heating Load (Btuh)0.280.28 0 0 Effect WAR WAR 12 Sensible Load (Btuh)ACH 0 0 0 0 0.150.15 Latent Load (Btuh) Internal a Occupants at 230 and 200 Btuh 0 0 0 2 460 400 b Scenario number 0 900 13 c Default Adjustments d Custom Appliances 0 0 0 0 e Plants 0 0 14 Subtotals Sum lines 6 through 12Sum lines 6 through 12 1375 644 3017 1707 Duct EHLF & ESGF 0.2850.285 0.2320.232 392 150 860 397 15 Loads ELG -9 -27 Vent CfmVent Cfm16Ventilation Loads 107107 E CfmE Cfm 107107 17 Winter Humidification Load Gal/Day 00 18 Piping Load 19 Blower Heat 20 AED Excursion & Latent Moisture Migration Load 54 6 21 Total Load Sum lines 13 through 19Sum lines 13 through 19 1767 794 3877 2104 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2018-Oct-05 09:21:54Right-Su ite® U niv er sal 20 18 18 .0.27 RSU1 4674 Page 5...Alpine - Mt Timp Stonebridge 3-4-4 - 100518.rup Calc = MJ8 Front Door faces: N Stonebridge 3-4-4Job:Right-J8® For m J1 Jul 27, 2018Date:Entire House Jay - Heating Supply CoBy: 1 Name of Room Master Bed Master Bath 2 Running Feet of Exposed Wall 34.0 ft 9.0 ft 3 Ceiling Ht (Ft) and Gross Wall Area (SqFt)8.0 f t²512.0ft 8.0 f t²304.0ft 4 Room Dimensions (Ft) and Floor Plan Area (SqFt)14.0 x 18.0 ft f t²252.0 9.0 x 10.0 ft f t²90.0 5 Ceiling Slope (Deg.) and Gross Ceiling Area (SqFt)0 f t²252.0°0 f t²90.0° Type of Exposure Const., Number Type of Exposure Const., Number Panel Faces HTMPanel Faces HTM Area or Lenght BtuhArea or Lenght Btuh Area or Lenght BtuhArea or Lenght Btuh Htg.Htg.Clg.Clg.HeatingHeating S-ClgS-Clg L-ClgL-Clg HeatingHeating S-ClgS-Clg L-ClgL-Clg 6 WallWall 12F-2sw12F-2sw nn 4.564.56 0.290.29 0 0 0 0 0 0 .GlazGlaz 2 glazing, clr outr,n2 glazing, clr outr,n 22.8022.80 9.909.90 0 0 0 0 0 0 .DoorDoor 11D011D0 nn 29.6429.64 7.027.02 0 0 0 0 0 0 .WallWall 15B19-0wc-815B19-0wc-8 nn 2.942.94 0.000.00 0 0 0 0 0 0 1 1 GlazGlaz 2 glazing, clr outr,n2 glazing, clr outr,n 25.8425.84 11.2211.22 0 0 0 0 0 0 WallWall 12F-2sw12F-2sw ee 4.564.56 0.290.29 144 520 33 0 0 0 GlazGlaz 2 glazing, clr outr,e2 glazing, clr outr,e 22.8022.80 32.2732.27 30 684 968 0 0 0 WallWall 15B19-0wc-815B19-0wc-8 ee 2.902.90 0.000.00 0 0 0 0 0 0 GlazGlaz 2 glazing, clr outr,e2 glazing, clr outr,e 25.8425.84 36.5836.58 0 0 0 0 0 0 WallWall 12F-2sw12F-2sw ss 4.564.56 0.290.29 112 397 25 72 287 18 GlazGlaz 2 glazing, clr outr,s2 glazing, clr outr,s 22.8022.80 17.7017.70 25 570 442 9 205 159 WallWall 15B19-0wc-815B19-0wc-8 ss 2.952.95 0.000.00 0 0 0 0 0 0 GlazGlaz 2 glazing, clr outr,s2 glazing, clr outr,s 25.8425.84 20.0620.06 0 0 0 0 0 0 WallWall 12F-2sw12F-2sw ww 4.564.56 0.290.29 16 73 5 0 0 0 GlazGlaz 2 glazing, clr outr,w2 glazing, clr outr,w 22.8022.80 32.2732.27 0 0 0 0 0 0 WallWall 15B19-0wc-815B19-0wc-8 ww 2.902.90 0.000.00 0 0 0 0 0 0 GlazGlaz 2 glazing, clr outr,w2 glazing, clr outr,w 25.8425.84 36.5836.58 0 0 0 0 0 0 WallWall 12C-0sw12C-0sw --0.000.00 0.000.00 0 0 0 0 0 0 DoorDoor 11D011D0 nn 29.6429.64 7.027.02 0 0 0 0 0 0 CeilCeil 16B-30ad16B-30ad --0.000.00 0.000.00 0 0 0 0 0 0 CeilCeil 16B-50ad16B-50ad --1.521.52 0.830.83 252 383 209 90 137 75 FlorFlor 19A-30bscp19A-30bscp --2.172.17 0.400.40 28 61 11 0 0 0 FlorFlor 21A-32c21A-32c --1.521.52 0.000.00 0 0 0 0 0 0 Infiltration Heating Load (Btuh)0.280.28 1000 265 Effect WAR WAR 12 Sensible Load (Btuh)ACH 0.23 99 0.06 26 0.150.15 Latent Load (Btuh) Internal a Occupants at 230 and 200 Btuh 1 230 200 0 0 0 b Scenario number 900 0 13 c Default Adjustments d Custom Appliances 0 0 0 0 e Plants 0 0 14 Subtotals Sum lines 6 through 12Sum lines 6 through 12 3711 2775 929 330 Duct EHLF & ESGF 0.2850.285 0.2320.232 1058 645 265 77 15 Loads ELG -10 -4 Vent CfmVent Cfm16Ventilation Loads 107107 E CfmE Cfm 107107 17 Winter Humidification Load Gal/Day 00 18 Piping Load 19 Blower Heat 20 AED Excursion & Latent Moisture Migration Load -159 33 21 Total Load Sum lines 13 through 19Sum lines 13 through 19 4769 3420 1194 406 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2018-Oct-05 09:21:54Right-Su ite® U niv er sal 20 18 18 .0.27 RSU1 4674 Page 6...Alpine - Mt Timp Stonebridge 3-4-4 - 100518.rup Calc = MJ8 Front Door faces: N Stonebridge 3-4-4Job:Right-J8® For m J1 Jul 27, 2018Date:Entire House Jay - Heating Supply CoBy: 1 Name of Room Master WIC Bath 2 2 Running Feet of Exposed Wall 0 ft 5.0 ft 3 Ceiling Ht (Ft) and Gross Wall Area (SqFt)8.0 f t²240.0ft 8.0 f t²216.0ft 4 Room Dimensions (Ft) and Floor Plan Area (SqFt)9.0 x 6.0 ft f t²54.0 8.5 x 5.0 ft f t²42.5 5 Ceiling Slope (Deg.) and Gross Ceiling Area (SqFt)0 f t²54.0°0 f t²42.5° Type of Exposure Const., Number Type of Exposure Const., Number Panel Faces HTMPanel Faces HTM Area or Lenght BtuhArea or Lenght Btuh Area or Lenght BtuhArea or Lenght Btuh Htg.Htg.Clg.Clg.HeatingHeating S-ClgS-Clg L-ClgL-Clg HeatingHeating S-ClgS-Clg L-ClgL-Clg 6 WallWall 12F-2sw12F-2sw nn 4.564.56 0.290.29 0 0 0 0 0 0 .GlazGlaz 2 glazing, clr outr,n2 glazing, clr outr,n 22.8022.80 9.909.90 0 0 0 0 0 0 .DoorDoor 11D011D0 nn 29.6429.64 7.027.02 0 0 0 0 0 0 .WallWall 15B19-0wc-815B19-0wc-8 nn 2.942.94 0.000.00 0 0 0 0 0 0 1 1 GlazGlaz 2 glazing, clr outr,n2 glazing, clr outr,n 25.8425.84 11.2211.22 0 0 0 0 0 0 WallWall 12F-2sw12F-2sw ee 4.564.56 0.290.29 0 0 0 40 164 10 GlazGlaz 2 glazing, clr outr,e2 glazing, clr outr,e 22.8022.80 32.2732.27 0 0 0 4 91 129 WallWall 15B19-0wc-815B19-0wc-8 ee 2.902.90 0.000.00 0 0 0 0 0 0 GlazGlaz 2 glazing, clr outr,e2 glazing, clr outr,e 25.8425.84 36.5836.58 0 0 0 0 0 0 WallWall 12F-2sw12F-2sw ss 4.564.56 0.290.29 0 0 0 0 0 0 GlazGlaz 2 glazing, clr outr,s2 glazing, clr outr,s 22.8022.80 17.7017.70 0 0 0 0 0 0 WallWall 15B19-0wc-815B19-0wc-8 ss 2.952.95 0.000.00 0 0 0 0 0 0 GlazGlaz 2 glazing, clr outr,s2 glazing, clr outr,s 25.8425.84 20.0620.06 0 0 0 0 0 0 WallWall 12F-2sw12F-2sw ww 4.564.56 0.290.29 0 0 0 0 0 0 GlazGlaz 2 glazing, clr outr,w2 glazing, clr outr,w 22.8022.80 32.2732.27 0 0 0 0 0 0 WallWall 15B19-0wc-815B19-0wc-8 ww 2.902.90 0.000.00 0 0 0 0 0 0 GlazGlaz 2 glazing, clr outr,w2 glazing, clr outr,w 25.8425.84 36.5836.58 0 0 0 0 0 0 WallWall 12C-0sw12C-0sw --0.000.00 0.000.00 0 0 0 0 0 0 DoorDoor 11D011D0 nn 29.6429.64 7.027.02 0 0 0 0 0 0 CeilCeil 16B-30ad16B-30ad --0.000.00 0.000.00 0 0 0 0 0 0 CeilCeil 16B-50ad16B-50ad --1.521.52 0.830.83 54 82 45 43 65 35 FlorFlor 19A-30bscp19A-30bscp --2.172.17 0.400.40 0 0 0 0 0 0 FlorFlor 21A-32c21A-32c --1.521.52 0.000.00 0 0 0 0 0 0 Infiltration Heating Load (Btuh)0.280.28 0 147 Effect WAR WAR 12 Sensible Load (Btuh)ACH 0 0 0.03 15 0.150.15 Latent Load (Btuh) Internal a Occupants at 230 and 200 Btuh 0 0 0 0 0 0 b Scenario number 0 0 13 c Default Adjustments d Custom Appliances 0 0 0 0 e Plants 0 0 14 Subtotals Sum lines 6 through 12Sum lines 6 through 12 0 0 467 198 Duct EHLF & ESGF 0.2850.285 0.2320.232 0 0 133 46 15 Loads ELG -2 -2 Vent CfmVent Cfm16Ventilation Loads 107107 E CfmE Cfm 107107 17 Winter Humidification Load Gal/Day 00 18 Piping Load 19 Blower Heat 20 AED Excursion & Latent Moisture Migration Load -2 9 21 Total Load Sum lines 13 through 19Sum lines 13 through 19 0 0 600 244 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2018-Oct-05 09:21:54Right-Su ite® U niv er sal 20 18 18 .0.27 RSU1 4674 Page 7...Alpine - Mt Timp Stonebridge 3-4-4 - 100518.rup Calc = MJ8 Front Door faces: N Stonebridge 3-4-4Job:Right-J8® For m J1 Jul 27, 2018Date:Entire House Jay - Heating Supply CoBy: 1 Name of Room Bed 2 Bed 3 2 Running Feet of Exposed Wall 28.0 ft 12.0 ft 3 Ceiling Ht (Ft) and Gross Wall Area (SqFt)8.0 f t²405.6ft 8.0 f t²368.0ft 4 Room Dimensions (Ft) and Floor Plan Area (SqFt)1.0 x 162.5 ft f t²162.5 12.0 x 11.0 ft f t²132.0 5 Ceiling Slope (Deg.) and Gross Ceiling Area (SqFt)0 f t²162.5°0 f t²132.0° Type of Exposure Const., Number Type of Exposure Const., Number Panel Faces HTMPanel Faces HTM Area or Lenght BtuhArea or Lenght Btuh Area or Lenght BtuhArea or Lenght Btuh Htg.Htg.Clg.Clg.HeatingHeating S-ClgS-Clg L-ClgL-Clg HeatingHeating S-ClgS-Clg L-ClgL-Clg 6 WallWall 12F-2sw12F-2sw nn 4.564.56 0.290.29 88 310 20 96 347 22 .GlazGlaz 2 glazing, clr outr,n2 glazing, clr outr,n 22.8022.80 9.909.90 20 456 198 20 456 198 .DoorDoor 11D011D0 nn 29.6429.64 7.027.02 0 0 0 0 0 0 .WallWall 15B19-0wc-815B19-0wc-8 nn 2.942.94 0.000.00 0 0 0 0 0 0 1 1 GlazGlaz 2 glazing, clr outr,n2 glazing, clr outr,n 25.8425.84 11.2211.22 0 0 0 0 0 0 WallWall 12F-2sw12F-2sw ee 4.564.56 0.290.29 120 547 35 0 0 0 GlazGlaz 2 glazing, clr outr,e2 glazing, clr outr,e 22.8022.80 32.2732.27 0 0 0 0 0 0 WallWall 15B19-0wc-815B19-0wc-8 ee 2.902.90 0.000.00 0 0 0 0 0 0 GlazGlaz 2 glazing, clr outr,e2 glazing, clr outr,e 25.8425.84 36.5836.58 0 0 0 0 0 0 WallWall 12F-2sw12F-2sw ss 4.564.56 0.290.29 0 0 0 0 0 0 GlazGlaz 2 glazing, clr outr,s2 glazing, clr outr,s 22.8022.80 17.7017.70 0 0 0 0 0 0 WallWall 15B19-0wc-815B19-0wc-8 ss 2.952.95 0.000.00 0 0 0 0 0 0 GlazGlaz 2 glazing, clr outr,s2 glazing, clr outr,s 25.8425.84 20.0620.06 0 0 0 0 0 0 WallWall 12F-2sw12F-2sw ww 4.564.56 0.290.29 16 73 5 0 0 0 GlazGlaz 2 glazing, clr outr,w2 glazing, clr outr,w 22.8022.80 32.2732.27 0 0 0 0 0 0 WallWall 15B19-0wc-815B19-0wc-8 ww 2.902.90 0.000.00 0 0 0 0 0 0 GlazGlaz 2 glazing, clr outr,w2 glazing, clr outr,w 25.8425.84 36.5836.58 0 0 0 0 0 0 WallWall 12C-0sw12C-0sw --0.000.00 0.000.00 0 0 0 0 0 0 DoorDoor 11D011D0 nn 29.6429.64 7.027.02 0 0 0 0 0 0 CeilCeil 16B-30ad16B-30ad --0.000.00 0.000.00 0 0 0 0 0 0 CeilCeil 16B-50ad16B-50ad --1.521.52 0.830.83 163 247 135 132 201 110 FlorFlor 19A-30bscp19A-30bscp --2.172.17 0.400.40 22 48 9 0 0 0 FlorFlor 21A-32c21A-32c --1.521.52 0.000.00 0 0 0 0 0 0 Infiltration Heating Load (Btuh)0.280.28 824 353 Effect WAR WAR 12 Sensible Load (Btuh)ACH 0.19 81 0.08 35 0.150.15 Latent Load (Btuh) Internal a Occupants at 230 and 200 Btuh 0 0 0 0 0 0 b Scenario number 0 0 13 c Default Adjustments d Custom Appliances 0 0 0 0 e Plants 0 0 14 Subtotals Sum lines 6 through 12Sum lines 6 through 12 2505 455 1356 344 Duct EHLF & ESGF 0.2850.285 0.2320.232 714 106 387 80 15 Loads ELG -7 -5 Vent CfmVent Cfm16Ventilation Loads 107107 E CfmE Cfm 107107 17 Winter Humidification Load Gal/Day 00 18 Piping Load 19 Blower Heat 20 AED Excursion & Latent Moisture Migration Load -26 -20 21 Total Load Sum lines 13 through 19Sum lines 13 through 19 3218 561 1743 424 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2018-Oct-05 09:21:54Right-Su ite® U niv er sal 20 18 18 .0.27 RSU1 4674 Page 8...Alpine - Mt Timp Stonebridge 3-4-4 - 100518.rup Calc = MJ8 Front Door faces: N Stonebridge 3-4-4Job:Right-J8® For m J1 Jul 27, 2018Date:Entire House Jay - Heating Supply CoBy: 1 Name of Room Entry Mud Room 2 Running Feet of Exposed Wall 5.0 ft 0 ft 3 Ceiling Ht (Ft) and Gross Wall Area (SqFt)8.0 f t²637.6ft 8.0 f t²264.0ft 4 Room Dimensions (Ft) and Floor Plan Area (SqFt)1.0 x 142.5 ft f t²142.5 1.0 x 58.3 ft f t²58.3 5 Ceiling Slope (Deg.) and Gross Ceiling Area (SqFt)0 f t²142.5°0 f t²58.3° Type of Exposure Const., Number Type of Exposure Const., Number Panel Faces HTMPanel Faces HTM Area or Lenght BtuhArea or Lenght Btuh Area or Lenght BtuhArea or Lenght Btuh Htg.Htg.Clg.Clg.HeatingHeating S-ClgS-Clg L-ClgL-Clg HeatingHeating S-ClgS-Clg L-ClgL-Clg 6 WallWall 12F-2sw12F-2sw nn 4.564.56 0.290.29 40 87 5 0 0 0 .GlazGlaz 2 glazing, clr outr,n2 glazing, clr outr,n 22.8022.80 9.909.90 0 0 0 0 0 0 .DoorDoor 11D011D0 nn 29.6429.64 7.027.02 21 622 147 0 0 0 .WallWall 15B19-0wc-815B19-0wc-8 nn 2.942.94 0.000.00 0 0 0 0 0 0 1 1 GlazGlaz 2 glazing, clr outr,n2 glazing, clr outr,n 25.8425.84 11.2211.22 0 0 0 0 0 0 WallWall 12F-2sw12F-2sw ee 4.564.56 0.290.29 0 0 0 0 0 0 GlazGlaz 2 glazing, clr outr,e2 glazing, clr outr,e 22.8022.80 32.2732.27 0 0 0 0 0 0 WallWall 15B19-0wc-815B19-0wc-8 ee 2.902.90 0.000.00 0 0 0 0 0 0 GlazGlaz 2 glazing, clr outr,e2 glazing, clr outr,e 25.8425.84 36.5836.58 0 0 0 0 0 0 WallWall 12F-2sw12F-2sw ss 4.564.56 0.290.29 0 0 0 0 0 0 GlazGlaz 2 glazing, clr outr,s2 glazing, clr outr,s 22.8022.80 17.7017.70 0 0 0 0 0 0 WallWall 15B19-0wc-815B19-0wc-8 ss 2.952.95 0.000.00 0 0 0 0 0 0 GlazGlaz 2 glazing, clr outr,s2 glazing, clr outr,s 25.8425.84 20.0620.06 0 0 0 0 0 0 WallWall 12F-2sw12F-2sw ww 4.564.56 0.290.29 0 0 0 0 0 0 GlazGlaz 2 glazing, clr outr,w2 glazing, clr outr,w 22.8022.80 32.2732.27 0 0 0 0 0 0 WallWall 15B19-0wc-815B19-0wc-8 ww 2.902.90 0.000.00 0 0 0 0 0 0 GlazGlaz 2 glazing, clr outr,w2 glazing, clr outr,w 25.8425.84 36.5836.58 0 0 0 0 0 0 WallWall 12C-0sw12C-0sw --0.000.00 0.000.00 84 0 0 120 0 0 DoorDoor 11D011D0 nn 29.6429.64 7.027.02 0 0 0 0 0 0 CeilCeil 16B-30ad16B-30ad --0.000.00 0.000.00 0 0 0 0 0 0 CeilCeil 16B-50ad16B-50ad --1.521.52 0.830.83 143 217 118 58 89 48 FlorFlor 19A-30bscp19A-30bscp --2.172.17 0.400.40 0 0 0 0 0 0 FlorFlor 21A-32c21A-32c --1.521.52 0.000.00 0 0 0 0 0 0 Infiltration Heating Load (Btuh)0.280.28 147 0 Effect WAR WAR 12 Sensible Load (Btuh)ACH 0.03 15 0 0 0.150.15 Latent Load (Btuh) Internal a Occupants at 230 and 200 Btuh 0 0 0 0 0 0 b Scenario number 0 500 13 c Default Adjustments d Custom Appliances 0 0 0 0 e Plants 0 0 14 Subtotals Sum lines 6 through 12Sum lines 6 through 12 1073 270 89 519 Duct EHLF & ESGF 0.2850.285 0.2320.232 306 63 25 120 15 Loads ELG -6 -2 Vent CfmVent Cfm16Ventilation Loads 107107 E CfmE Cfm 107107 17 Winter Humidification Load Gal/Day 00 18 Piping Load 19 Blower Heat 20 AED Excursion & Latent Moisture Migration Load -16 -30 21 Total Load Sum lines 13 through 19Sum lines 13 through 19 1379 333 114 639 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2018-Oct-05 09:21:54Right-Su ite® U niv er sal 20 18 18 .0.27 RSU1 4674 Page 9...Alpine - Mt Timp Stonebridge 3-4-4 - 100518.rup Calc = MJ8 Front Door faces: N Stonebridge 3-4-4Job:Right-J8® For m J1 Jul 27, 2018Date:Entire House Jay - Heating Supply CoBy: 1 Name of Room Kitchen/Great 2 Running Feet of Exposed Wall 54.5 ft 3 Ceiling Ht (Ft) and Gross Wall Area (SqFt)8.0 f t²840.0ft 4 Room Dimensions (Ft) and Floor Plan Area (SqFt)1.0 x 613.0 ft f t²613.0 5 Ceiling Slope (Deg.) and Gross Ceiling Area (SqFt)0 f t²613.0° Type of Exposure Const., Number Panel Faces HTM Area or Lenght Btuh Area or Lenght Btuh Htg.Clg.Heating S-Clg L-Clg Heating S-Clg L-Clg 6 Wall 12F-2sw n 4.56 0.29 0 0 0 .Glaz 2 glazing, clr outr,n 22.80 9.90 0 0 0 .Door 11D0 n 29.64 7.02 0 0 0 .Wall 15B19-0wc-8 n 2.94 0.00 0 0 0 1 1 Glaz 2 glazing, clr outr,n 25.84 11.22 0 0 0 Wall 12F-2sw e 4.56 0.29 16 73 5 Glaz 2 glazing, clr outr,e 22.80 32.27 0 0 0 Wall 15B19-0wc-8 e 2.90 0.00 0 0 0 Glaz 2 glazing, clr outr,e 25.84 36.58 0 0 0 Wall 12F-2sw s 4.56 0.29 220 506 32 Glaz 2 glazing, clr outr,s 22.80 17.70 109 2485 1929 Wall 15B19-0wc-8 s 2.95 0.00 0 0 0 Glaz 2 glazing, clr outr,s 25.84 20.06 0 0 0 Wall 12F-2sw w 4.56 0.29 200 780 49 Glaz 2 glazing, clr outr,w 22.80 32.27 29 661 936 Wall 15B19-0wc-8 w 2.90 0.00 0 0 0 Glaz 2 glazing, clr outr,w 25.84 36.58 0 0 0 Wall 12C-0sw -0.00 0.00 88 0 0 Door 11D0 n 29.64 7.02 0 0 0 Ceil 16B-30ad -0.00 0.00 0 0 0 Ceil 16B-50ad -1.52 0.83 613 932 509 Flor 19A-30bscp -2.17 0.40 24 52 10 Flor 21A-32c -1.52 0.00 0 0 0 Infiltration Heating Load (Btuh)0.28 1603 Effect WAR 12 Sensible Load (Btuh)ACH 0.37 158 0.15 Latent Load (Btuh) Internal a Occupants at 230 and 200 Btuh 4 920 800 b Scenario number 3400 13 c Default Adjustments d Custom Appliances 0 0 e Plants 0 14 Subtotals Sum lines 6 through 12 7116 7958 Duct EHLF & ESGF 0.285 0.232 2028 1849 15 Loads ELG -25 Vent Cfm16Ventilation Loads 107 E Cfm 107 17 Winter Humidification Load Gal/Day 0 18 Piping Load 19 Blower Heat 20 AED Excursion & Latent Moisture Migration Load -1 21 Total Load Sum lines 13 through 19 9144 9808 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2018-Oct-05 09:21:56 Rig ht-Su ite® U niv er sal 20 18 18 .0.27 RSU1 4674 Page 1 ...Alpine - Mt Timp Stonebridge 3-4-4 - 100518.rup Calc = MJ8 Front Door faces: N Stonebridge 3-4-4Job:Loads for Multiple Orientations Jul 27, 2018Date:Entire House Jay - Heating Supply CoBy: Project Information Mt Timpanogas, AlpineFor: Stonebridge 3-4-4, Idaho Falls, ID Email: jhooper@heatingsupplyco.com Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temp era ture (°F)Idaho Falls Rgnl, ID, US 1476Design TD (°F)ft4744Elevation: 5030Relative humidity (%)°N44Latitude: Outdoor:-28.435.2Moisture difference (gr/lb)CoolingHeating Infiltration:89-6Dry bul b (°F) )H(35-Da ily ra nge (°F) 61-We t bu lb (°F) 7.515.0Wind speed (mph) Front Door North Northeast East Southeast South Southwest West Northwest Sensible Load (Btuh)20270 22933 23155 22011 19423 21259 21867 21847 Latent Load (Btuh)0 0 0 0 0 0 0 0 Total Load (Btuh)20270 22933 23155 22011 19423 21259 21867 21847 Heating AVF (cfm)900 900 900 900 900 900 900 900 Cooling AVF (cfm)900 900 900 900 900 900 900 900 Building Orientation Cooling Load To t a l C o o l i n g L o a d ( B t u h ) Direction Front Door faces 0 5000 10000 15000 20000 25000 N NE E SE S SW W NW Front Door faces NorthCurrent Orientation: Front Door faces EastHighest Cooling Load: Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2018-Oct-05 09:21:57 Rig ht-Su ite® U niv er sal 20 18 18 .0.27 RSU1 4674 Page 1 ...Alpine - Mt Timp Stonebridge 3-4-4 - 100518.rup Calc = MJ8 Front Door faces: N Stonebridge 3-4-4Job:J1 Form - Worksheet A Jul 27, 2018Date:Entire House Jay - Heating Supply CoBy: Supporting Detail Project Name:Jul 27, 2018Alpine - Mt Timp Stonebridge 3-4-4 - 100518 Date: Address:Stonebridge 3-4-4, Idaho Falls, ID Phone:Stonebridge 3-4-4Job ID: Worksheet A Location and Design Conditions Weather Location:Idaho Falls Rgnl, ID, US 444744Latitude =Elevation = Indoor Conditions, Heating:70 °FDB =%50°F75%30 RH =DB =Indoor Conditions, Cooling:RH = Table 1 Conditions 99% DB =-6 °F Hgr/lb-28°F89 Daily Range =Grains Difference =1% DB = Design Temperature Differences °F14°F76 CTD =HTD = Job #: Stonebridge 3-4-4 Performed by Jay - Heating Supply Co f... Mt Timpanogas Stonebridge 3-4-4 Idaho Falls, ID jhooper@heatingsupplyco.com Scale: 1 : 112 Page 1 Ri ght-Suite® Universal 2018 18.0.27 RSU14674 2018-Oct-05 09:22:36 ...p Stonebridge 3-4-4 - 100518.rup N Level 2 Master Bed Master Bath Master WIC Bath 2 Stairs 2 Bed 2 Bed 3 Entry Mud Room Kitchen/Great Garage 33 cfm 48 cfm 38 cfm 28 cfm 87 cfm 87 cfm 87 cfm 76 cfm 16 cfm 87 cfm 87 cfm 88 cfm 14 x 6 14 x 614 x 6 706 cfm 76 cfm Job #: Stonebridge 3-4-4 Performed by Jay - Heating Supply Co f... Mt Timpanogas Stonebridge 3-4-4 Idaho Falls, ID jhooper@heatingsupplyco.com Scale: 1 : 112 Page 2 Ri ght-Suit e® Universal 2018 18.0.27 RSU14674 2018-Oct-05 09:22:36 ...p Stonebridge 3-4-4 - 100518.rup N Level 1 Bed 6 Bath 1 Mechanical Cold Room Stairs 1 Bed 5Bed 4 Family Room 16 cfm 48 cfm 62 cfm 53 cfm 5 " 5 " 59 cfm53 cfm 5 " 4 x 8 6 " 12 x 8 6 " 12 x 8 4 " 6 " 5 " 5 " 6 x 8 22 x 8 4 " 4 " 4 x 8 6 "6 " 7 " 4 " 14 x 6 14 x 6 14 x 6292 cfm 14 " 24 x 8 9 " 6 " Bold/italic values have been manually overridden 2018-Oct-05 09:21:57 Rig ht-Su ite® U niv er sal 20 18 18 .0.27 RSU1 4674 Page 1 ...Alpine - Mt Timp Stonebridge 3-4-4 - 100518.rup Calc = MJ8 Front Door faces: N Stonebridge 3-4-4Job:Duct System Summary Jul 27, 2018Date:Entire House Jay - Heating Supply CoBy: Project Information Mt Timpanogas, AlpineFor: Stonebridge 3-4-4, Idaho Falls, ID Email: jhooper@heatingsupplyco.com CoolingHeating External static pressure in H2O0.70in H2O0.70 Pressure losses in H2O0.37in H2O0.37 Available static pressure in H2O0.33in H2O0.33 Supply / return available pressure 0.199 / 0.131 in H2O in H2O0.199 / 0.131 Lowest friction rate in/100ft0.063in/100ft0.063 Actual air flow cfm900cfm900 Total effective length (TEL)ft523 Supply Branch Detail Table Design Htg Clg Design Diam H x W Duct Actual Ftg.Eqv Name (Btuh)(cfm)(cfm)FR (in)(in)Matl Ln (ft)Ln (ft)Trunk st4275.040.0ShMt0x04.00.063016583hBath 1 st3135.052.5ShMt0x04.00.1061116600hBath 2 00ShMt0x0002588561hBed 2 st1170.019.0ShMt0x05.00.10519481743hBed 3 st1105.029.5ShMt0x05.00.14835481767hBed 4 st1180.017.5ShMt0x05.00.10118622256hBed 5 st4190.036.5ShMt4x84.90.08847592162hBed 6 st1190.06.0ShMt0x05.00.10215381379hEntry st3195.033.0ShMt0x05.00.08747531938hFamily Room st3135.044.0ShMt4x84.50.11147531938hFamily Room-A st4190.031.5ShMt0x06.00.09087501962cKitchen/Great st3205.027.0ShMt0x06.00.08687501962cKitchen/Great-A st4265.035.5ShMt0x07.00.06687501962cKitchen/Great-B st3205.027.0ShMt0x06.00.08687501962cKitchen/Great-C st4255.043.5ShMt0x06.00.06787501962cKitchen/Great-D st3160.035.5ShMt0x04.00.10218331194hMaster Bath st3170.043.9ShMt0x06.00.09376651710cMaster Bed st3180.047.5ShMt0x06.00.08776651710cMaster Bed-A st4190.041.0ShMt0x04.00.086283639cMud Room 2018-Oct-05 09:21:57 Rig ht-Su ite® U niv er sal 20 18 18 .0.27 RSU1 4674 Page 2 ...Alpine - Mt Timp Stonebridge 3-4-4 - 100518.rup Calc = MJ8 Front Door faces: N Supply Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk st4 Peak AVF 229 338 0.063 507 10.1 12x8 ShtMetl st2 st3 Peak AVF 387 450 0.086 675 10.5 12x8 ShtMetl st2 st1 Peak AVF 196 87 0.101 588 7.5 6x8 ShtMetl st2 Peak AVF 616 788 0.063 645 13.8 22x8 ShtMetl Return Branch Detail Table Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size (in)(cfm)(cfm)(ft)FR (fpm)(in)(in)Opening (in)Matl Trunk rb9 0x 6080 706 207.5 0.063 661 14.0 x0 0 ShMt rt1 rb2 0x 2920 194 109.5 0.120 661 9.0 x0 0 ShMt rt1 Return Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk rt1 Peak AVF 900 900 0.063 675 14.5 24x8 ShtMetl 2018-Oct-05 09:21:57 Rig ht-Su ite® U niv er sal 20 18 18 .0.27 RSU1 4674 Page 1 ...Alpine - Mt Timp Stonebridge 3-4-4 - 100518.rup Calc = MJ8 Front Door faces: N Stonebridge 3-4-4Job:Duct system multi orientation report Jul 27, 2018Date:Entire House Jay - Heating Supply CoBy: Project Information Mt Timpanogas, AlpineFor: Stonebridge 3-4-4, Idaho Falls, ID Email: jhooper@heatingsupplyco.com Group 1: ( N, NE, W, NW) Group 2: ( E) Group 3: (SE) Group 4: ( S) Group 5: (SW) Duct Name (SE)(E)(NE)(N) Duct SizeReg SizeReg CFMDuct SizeReg SizeReg CFMDuct SizeReg SizeReg CFMDuct SizeReg SizeReg CFM Supply Branches Bath 1 412x416 h412x416 h412x416 h412x416 h Bath 2 412x416 h412x416 h412x416 h412x416 h Bed 2 012x488 h012x488 h012x488 h012x488 h Bed 3 512x448 h512x448 h512x448 h512x448 h Bed 4 512x448 h512x448 h512x448 h512x449 c Bed 5 512x462 h512x462 h512x462 h512x462 h Bed 6 4x812x459 h4x812x459 h4x812x459 h4x812x459 h Entry 512x438 h512x438 h512x438 h512x438 h Family Room 512x453 h512x453 h512x453 h512x453 h Family Room-A 4x812x453 h4x812x453 h4x812x453 h4x812x453 h Kitchen/Great 612x493 c612x492 c612x482 c612x476 c Kitchen/Great-A 612x493 c612x492 c612x482 c612x476 c Kitchen/Great-B 712x493 c712x492 c612x482 c612x476 c Kitchen/Great-C 612x493 c612x492 c612x482 c612x476 c Kitchen/Great-D 712x493 c712x492 c612x482 c612x476 c Master Bath 412x433 h412x433 h412x433 h412x433 h Master Bed 612x468 c612x466 c612x481 c612x487 c Master Bed-A 612x468 c612x466 c612x481 c612x487 c Mud Room 412x424 c412x423 c412x425 c412x429 c Supply Trunks st4 12x8328 c10x8306 c10x8291 c10x8295 c st3 12x8447 c12x8445 c12x8447 c12x8436 c st1 6x8196 h6x8196 h6x8196 h6x8196 h st2 22x8776 c22x8751 c20x8738 c20x8730 c Return Branches rb9 1420x20728 c1420x20741 c1420x20723 c1420x20700 c rb2 920x20292 h920x20292 h920x20292 h920x20292 h Return Trunks rt1 24x8900 c24x8900 c24x8900 c24x8900 c Friction Rates Heating FR 0.0630.0630.0630.063 Cooling FR 0.0630.0630.0630.063 2018-Oct-05 09:21:57 Rig ht-Su ite® U niv er sal 20 18 18 .0.27 RSU1 4674 Page 2 ...Alpine - Mt Timp Stonebridge 3-4-4 - 100518.rup Calc = MJ8 Front Door faces: N Project Information Mt Timpanogas, AlpineFor: Stonebridge 3-4-4, Idaho Falls, ID Email: jhooper@heatingsupplyco.com Duct Name (NW)(W)(SW)(S) Duct SizeReg SizeReg CFMDuct SizeReg SizeReg CFMDuct SizeReg SizeReg CFMDuct SizeReg SizeReg CFM Supply Branches Bath 1 412x416 h412x416 h412x416 h412x416 h Bath 2 412x416 h412x416 h412x416 h412x416 h Bed 2 012x488 h012x488 h012x488 h012x488 h Bed 3 512x448 c512x454 c512x448 h512x448 h Bed 4 512x448 h512x448 h512x448 h512x448 h Bed 5 512x462 h512x462 h512x462 h512x462 h Bed 6 4x812x459 h4x812x459 h4x812x459 h4x812x459 h Entry 512x438 h512x438 h512x438 h512x438 h Family Room 512x453 h512x453 h512x453 h512x453 h Family Room-A 4x812x453 h4x812x453 h4x812x453 h4x812x453 h Kitchen/Great 612x481 c612x486 c612x485 c612x487 c Kitchen/Great-A 612x481 c612x486 c612x485 c612x487 c Kitchen/Great-B 612x481 c612x486 c612x485 c712x487 c Kitchen/Great-C 612x481 c612x486 c612x485 c612x487 c Kitchen/Great-D 612x481 c612x486 c612x485 c612x487 c Master Bath 412x433 h412x433 h412x433 h412x433 h Master Bed 612x469 c612x465 h612x469 c612x476 c Master Bed-A 612x469 c612x465 h612x469 c612x476 c Mud Room 412x427 c412x425 c412x426 c412x428 c Supply Trunks st4 10x8299 c10x8302 c12x8318 c12x8338 c st3 12x8413 c12x8414 c12x8431 c12x8450 c st1 6x8196 h6x8196 h6x8196 h6x8196 h st2 20x8712 c20x8716 c22x8749 c22x8788 c Return Branches rb9 1420x20712 c1420x20727 c1420x20716 c1420x20706 c rb2 920x20292 h920x20292 h920x20292 h920x20292 h Return Trunks rt1 24x8900 c24x8900 c24x8900 c24x8900 c Friction Rates Heating FR 0.0630.0630.0630.063 Cooling FR 0.0630.0630.0630.063 2018-Oct-05 09:21:57 Rig ht-Su ite® U niv er sal 20 18 18 .0.27 RSU1 4674 Page 3 ...Alpine - Mt Timp Stonebridge 3-4-4 - 100518.rup Calc = MJ8 Front Door faces: N Project Information Mt Timpanogas, AlpineFor: Stonebridge 3-4-4, Idaho Falls, ID Email: jhooper@heatingsupplyco.com Duct Name SmalestLargest Duct SizeReg SizeReg CFMDuct SizeReg SizeReg CFM Supply Branches Bath 1 412x416 h412x416 h Bath 2 412x416 h412x416 h Bed 2 012x488 h012x488 h Bed 3 512x448 h512x454 c Bed 4 512x448 h512x449 c Bed 5 512x462 h512x462 h Bed 6 4x812x459 h4x812x459 h Entry 512x438 h512x438 h Family Room 512x453 h512x453 h Family Room-A 4x812x453 h4x812x453 h Kitchen/Great 612x476 c612x493 c Kitchen/Great-A 612x476 c612x493 c Kitchen/Great-B 612x476 c712x493 c Kitchen/Great-C 612x476 c612x493 c Kitchen/Great-D 612x476 c712x493 c Master Bath 412x433 h412x433 h Master Bed 612x465 h612x487 c Master Bed-A 612x465 h612x487 c Mud Room 412x423 c412x429 c Supply Trunks st4 10x8291 c12x8338 c st3 12x8413 c12x8450 c st1 6x8196 h6x8196 h st2 20x8712 c22x8788 c Return Branches rb9 1420x20700 c1420x20741 c rb2 920x20292 h920x20292 h Return Trunks rt1 24x8900 c24x8900 c Friction Rates Heating FR 0.0630.063 Cooling FR 0.0630.063 2018-Oct-05 09:21:59 Rig ht-Su ite® U niv er sal 20 18 18 .0.27 RSU1 4674 Page 1 ...Alpine - Mt Timp Stonebridge 3-4-4 - 100518.rup Calc = MJ8 Front Door faces: N Stonebridge 3-4-4Job:Static Pressure and Friction Rate Jul 27, 2018Date:Entire House Jay - Heating Supply CoBy: Project Information Mt Timpanogas, AlpineFor: Stonebridge 3-4-4, Idaho Falls, ID Email: jhooper@heatingsupplyco.com Available Static Pressure CoolingHeating (in H2O)(in H2O) 0.700.70External static pressure Pressure losses 0.220.22Coil 00Heat exchanger 0.020.02Supply diffusers 0.020.02Return grilles 0.100.10Filter 00Humidifier 0.010.01Balancing damper 00Other device 0.330.33Available static pressure Total Effective Length ReturnSupply (ft)(ft) 413Measured length of run-out 428Measured length of trunk 200275Equivalent length of fittings 208315Total length 523Total effective length Friction Rate CoolingHeating (in/100ft)(in/100ft) OK0.063OK0.063Supply Ducts OK0.063OK0.063Return Ducts Fitting Equivalent Length Details 4AD=60, 2I2=85, 2I3=95, 1C=35: TotalEL=275Supply 6M=20, 6C5=115, 5A=40, 6CB=25: TotalEL=200Return