HomeMy WebLinkAboutINSPECTION TICKET - 18-00281 - 1397 Stone Dr - New SFRInspection
Ticket
Temporary Electrical Service on 06/20/2018: PASS
Permit Number: 18-00281Permit Details
Building - Single Family Residence
Permit Issued Date: 06/04/2018
Final Inspections Required
HVAC Final Inspection Plumbing Final Inspection
Residential Electrical Final Inspection Residential Building Final
311 Wind Song Dr
311 Wind Song Dr - New SFR
Inspection Details
bret.stoddard@rexburg.org
Inspected By: Bret Stoddard
Temporary Electrical Service on 06/20/2018: PASS
D ESCRIPTIO N CO M M EN TS STATUS
Unused openings have been effectively closed
(K.O. seals, etc.) 110.12(A), 408.7
COMPLETED
Securely mounted gear-panels, meter base, etc.
110.13
COMPLETED
Proper clearances about electrical equipment
indoors and outdoors. 110.26 (A), (E),(E)(2) and
(F)
COMPLETED
•Grounding electrode system installed-ufer,
ground rods, etc. 250.52(A)(4-7)
COMPLETED
Grounding electrode system conductors sized
and protected appropriately. 250.66, 250.64(F),
250.64(A)(B)
COMPLETED
Grounding electrode conductor is either
un-spliced or spliced using approved methods.
250.64(C)(F)
COMPLETED
Temporary 125V & 250V 15A & 20A receptacles
must have GFCI protection. 590.4(D)
COMPLETED
Temporary receptacles in wet/damp locations
must have in-use extra duty covers. 590.4(D)(2),
406.9(A)(B)
COMPLETED
Identify wet and damp locations for
panels-NEMA 3R, etc. 408.16, 408.37, 312.12
COMPLETED
Panel or switchgear service rated. 408.3(C)COMPLETED
Approved to be energized for temporary power
(will send permit with temporary note to utility)
To be energized for temporary power-pedestal
with one GFCI receptacle.
COMPLETED