Loading...
HomeMy WebLinkAboutINSPECTION TICKET - 18-00281 - 1397 Stone Dr - New SFRInspection Ticket Temporary Electrical Service on 06/20/2018: PASS Permit Number: 18-00281Permit Details Building - Single Family Residence Permit Issued Date: 06/04/2018 Final Inspections Required HVAC Final Inspection Plumbing Final Inspection Residential Electrical Final Inspection Residential Building Final 311 Wind Song Dr 311 Wind Song Dr - New SFR Inspection Details bret.stoddard@rexburg.org Inspected By: Bret Stoddard Temporary Electrical Service on 06/20/2018: PASS D ESCRIPTIO N CO M M EN TS STATUS Unused openings have been effectively closed (K.O. seals, etc.) 110.12(A), 408.7 COMPLETED Securely mounted gear-panels, meter base, etc. 110.13 COMPLETED Proper clearances about electrical equipment indoors and outdoors. 110.26 (A), (E),(E)(2) and (F) COMPLETED •Grounding electrode system installed-ufer, ground rods, etc. 250.52(A)(4-7) COMPLETED Grounding electrode system conductors sized and protected appropriately. 250.66, 250.64(F), 250.64(A)(B) COMPLETED Grounding electrode conductor is either un-spliced or spliced using approved methods. 250.64(C)(F) COMPLETED Temporary 125V & 250V 15A & 20A receptacles must have GFCI protection. 590.4(D) COMPLETED Temporary receptacles in wet/damp locations must have in-use extra duty covers. 590.4(D)(2), 406.9(A)(B) COMPLETED Identify wet and damp locations for panels-NEMA 3R, etc. 408.16, 408.37, 312.12 COMPLETED Panel or switchgear service rated. 408.3(C)COMPLETED Approved to be energized for temporary power (will send permit with temporary note to utility) To be energized for temporary power-pedestal with one GFCI receptacle. COMPLETED