COMcheck Software Version 4.1.0.0
Mechanical Compliance Certificate
Project Information
Energy Code:
Project Title:
Location:
Climate Zone:
Project Type:
Construction Site:
472 N. Yellowstone Hwy
Rexburg, ID 83440
Additional Efficiency Package(s)
Unspecified
Mechanical Systems List
Quantity System Type & Description
2015 I ECC
Thomson Farms Clubhouse
Rexburg, Idaho
6b
New Construction
Owner/Agent:
Stillwater Equity Partners
Designer/Contractor:
Dwayne Sudweeks
Engineered Systems Assoc., Inc.
1355 E. Center St.
Pocatello, ID 83201
208-233-0501
dcs@engsystems.com
HVAC System 1 (Single Zone):
Heating: 1 each - Duct Furnace, Gas, Capacity = 110 kBtu/h
Proposed Efficiency = 95.00% Ec, Required Efficiency: 80.00 % Ec
Cooling: 1 each - Split System, Capacity = 54 kBtu/h, Air -Cooled Condenser, No Economizer, Economizer exception: Low Capacity
Residential
Proposed Efficiency = 13.00 SEER, Required Efficiency: 13.00 SEER
Fan System: FAN SYSTEM 1 -- Compliance (Motor nameplate HP method) : Passes
Fans:
FAN 1 Supply, Constant Volume, 800 CFM, 0.3 motor nameplate hp, 0.8 fan efficiency grade
Water Heater 1:
Gas Storage Water Heater, Capacity: 75 gallons, Input Rating: 70 kBtu/h w/ Circulation Pump
No minimum efficiency requirement applies
Mechanical Compliance Statement
Compliance Statement: The proposed mechanical design represented in this document is consistent with the building plans,
specifications, and other calculations submitted with this permit application. The proposed mechanical systems have been
designed to meet the 2015 IECC requirements in COMcheck Version 4.1,0.0 and to comply with any applicable mandatory
requirements listed in the Inspection Checklist.
bwau�ne. Sw�w�c�S P�'• r� � u> r
Name - TRI 5i ture Dat
Project Title: Thomson Farms Clubhouse
Data filename: C:\Users\Dwayne 15\Documents\COMcheck\Thomson Farms Clubhouse.cck
Report date: 08/20/18
Page 1 of 9
COMcheck Software Version 4.1.0.0
Inspection Checklist
Energy Code: 2015 IECC
Requirements: 0.0% were addressed directly in the COMcheck software
Text in the "Comments/Assumptions" column is provided by the user in the COMcheck Requirements screen. For each
requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception
is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided.
Section
#Plan
Review
Complies?
Comments/Assumptions
& Req. IDI
C103.2
Plans, specifications, and/or
.❑Complies
[PR2)1
calculations provide all information❑Does
Not
with which compliance can be❑Not
Observable
determined for the mechanical
Applicable
systems and equipment and❑Not
document where exceptions to the
standard are claimed. Load
calculations per acceptable
engineering standards and
handbooks.
C103.2
Plans, specifications, and/or
❑Complies
[PR3)1
calculations provide all information -
❑Does Not
with which compliance can be
[-]Not Observable;
determined for the service water
❑Not Applicable'.
heating systems and equipment and
document where exceptions to the
standard are claimed. Hot water
system sized per manufacturer's
sizing guide.
C406
Plans, specifications, and/or
❑Complies
[PR911 ;calculations
provide all information j❑Does
Not
with which compliance can be
Not Observable
:efflclency
determined for the additlonal energy
❑Not Applicable
package options.
Additional Comments/Assumptions:
1 I High Impact (Tier 1)2ij Medium Impact (Tier 2) 3 1 Low Impact (Tier 3)
Project Title: Thomson Farms Clubhouse Report date: 08/20/18
Data filename: CAUsers\Dwayne 15\Documents\COMcheck\Thomson Farms Clubhouse.cck Page 2 of 9
#
& Re .ID
Footing / Foundation Inspection
I
Complies?
.Comments/Assumptions
- -
C403.2.4.
Snow/ice melting system sensors for❑Complies
5,
future connection to controls. Freeze
j❑Does Not
C403.2.4..
protection systems have automatic❑Not
Observable
6
[FO9]3,❑Not
controls installed.
Applicable
Additional Comments/Assumptions:
11 High Impact (Tier 1) Medium Impact (Tier 2) 3 1 Low Impact (Tier 3)
Project Title: Thomson Farms Clubhouse Report date: 08/20/18
Data filename: C:\Users\Dwayne 15\Documents\COMcheck\Thomson Farms Clubhouse.cck Page 3 of 9
Section
#Plumbing
Rough -In Inspection
Complies?
Comments/Assumptions
& Req.ID
C404.5,
Heated water supply piping conforms❑Complies
C404.5. 1,
to pipe length and volume
❑Does Not
C404.5.2
requirements. Refer to section details. '�.❑Not
Observable
[PL6]3
❑Not Applicable
C404.5,
Heated water supply piping conforms❑Complies
C404.5.1,
to pipe length and volume
❑Does Not
C4045.2
requirements. Refer to section details.
❑Not Observable
[PL6]
❑Not Applicable
C404.6.1,
Automatic time switches Installed to
❑Complies
C404.6.2
automatically switch off the
❑Does Not
[PL311
recirculating hot-water system or heat
❑Not Observable
trace.
❑Not Applicable
C404.6.3
Pumps that circulate water between a❑Complies
[PL7]3
heater and storage tank have controls
❑Does Not
that limit operation from startup to❑Not
Observable;
<= 5 minutes after end of heating
Applicable
C404.63
_cycle.;❑Not
Pumps that circulate water between a
❑Complies
[PL7]3
heater and storage tank have controls
❑Does Not
that limit operation from startup to❑Not
Observable
<= 5 minutes after end of heating
;❑Not
Applicable',
cycle.
C404.7
Water distribution system that pumps❑Complies
Roes
[PL8]3
water from a heated -water supply
Not
pipe back to the heated -water source❑Not
Observable
through a cold -water supply pipe is a
Applicable
demand recirculation water system.❑Not
Pumps within this system have
controls that start the pump upon
receiving a signal from the action of a
user of a fixture or appliance and
limits the temperature of the water
entering the cold -water piping to
104°F.
C404.7
Water distribution system that pumps❑Complies
[PL813
water from a heated -water supply❑Does
Not
pipe back to the heated -water source❑Not
Observable
through a cold -water supply pipe is a
:❑Not
Applicable
demand recirculation water system.
Pumps within this system have
controls that start the pump upon
receiving a signal from the action of a j
user of a fixture or appliance and
limits the temperature of the water
entering the cold -water piping to
104°F.
Additional Comments/Assumptions:
111 High Impact (Tier 1) 12 1 Medium Impact (Tier 2) 13 J Low Impact (Tier 3)
Project Title: Thomson Farms Clubhouse Report date: 08/20/18
Data filename: C:\Users\Dwayne 15\Documents\COMcheck\Thomson Farms Clubhouse.cck Page 4 of 9
Section
#
Mechanical Rough-In Inspection
Complies?
Comments/Assumptions
& Re .ID
C402.2.6
Thermally ineffective panel surfaces of;❑Complies
[ME41]3
sensible heating panels have
❑Does Not
insulation >= R-3.5.
;❑Not Observable;
I❑Not
Applicable
C403.2.13
Unenclosed spaces that are heated I❑Complies
[ME71]2
use only radiant heat. j❑Does
Not
;❑Not
Observable
❑Not Applicable
C403.2.3
HVAC equipment efficiency verified.❑Complies
See the Mechanical Systems list for values.
[ME55]2 -',❑Does
Not
❑Not Observable ,
❑Not Applicable
C403.2.6.
Demand control ventilation provided❑Complies
1
for spaces >500 ft2 and >25❑Does
Not
[ME59]1
people/1000 ft2 occupant density and❑Not
Observable;
served by systems with air side
Applicable
economizer, auto modulating outside :❑Not
.
air damper control, or design airflow
>3,000 cfm.
C403.2.6.
Enclosed parking garage ventilation❑Complies
2
has automatic contaminant detection
❑Does Not
(ME115]3
and capacity to stage or modulate
❑Not Observable
fans to 50% or less of design capacity. !❑Not
Applicable I
C403.2.7
Exhaust air energy recovery on ;❑Complies
[ME57)1 !
systems meeting Table C403.2.7(1)
❑Does Not
and 0403.2.7(2).
-
❑Not Observable;
I❑Not
Applicable
C403.2.8
Kitchen exhaust systems comply with
Complies
[ME116]3
replacement air and conditioned j❑Does
Not',
supply air limitations, and satisfy hood
Observable;
rating requirements and maximum❑Not
Applicable
exhaust rate criteria.❑Not
C403.2.9 -.
HVAC ducts and plenums Insulated.❑Complies
[ME60]'
Where ducts or plenums are Installed
❑Does Not
in or under a slab, verification may
Observable;
need to occur during Foundation❑Not
Applicable
Inspection.❑Not
C403.2.9
Ducts and plenums sealed based on I❑complies
[ME10]2
static pressure and location.
❑Does Not',
❑Not Observable
❑Not Applicable
C403.2.9..
Ductwork operating >3 in. water❑Complies
-
1.3
column requires air leakage testing.
❑Does Not
[MEll]3
❑Not Observable
❑Not Applicable
C403.4.4.
Multiple zone VAV systems with DDC❑Complies ISee the Mechanical Systems list for values.
6
of individual zone boxes have static❑Does Not
[ME110]3
pressure setpoint reset controls.
:[_-]Not Observable ;
❑Not Applicable I
1 I High Impact (Tier 1) Iffll Medium Impact (Tier 2) 13 1 Low Impact (Tier 3)
Project Title: Thomson Farms Clubhouse Report date: 08/20/18
Data filename: C:\Users\Dwayne 15\Documents\COMcheck\Thomson Farms Clubhouse.cck Page 5 of 9
#
& Req.ID
I Mechanical Rough -In Inspection
Complies?
C404.2.1
Gas-fired water -heating equipment❑Complies
_
[ME111]2
installed in new buildings: where a❑Does
Not
singular piece of water -heating I
Observable; '
equipment >= 1,000 kBtu/h serves❑Not
Applicable
the entire building, thermal efficiency❑Not
>= 90 Et. Where multiple pieces of
water -heating equipment serve the
building with combined rating >_
1,000 kBtu/h, the combined input -
capacity -weighted -average thermal
efficiency >= 90 Et. Exclude input
rating of equipment in individual
dwelling units and equipment <= 100
kBtu/h.
C408.2.2.
Air outlets and zone terminal devices❑Complies
1
have means for air balancing.,❑Does
Not
[ME53]3
;❑Not
Observable;
❑Not ApDlicable
C403.5, Refrigerated display cases, walk-in 'LJComplies
C403.5.1, coolers or walk-in freezers served by ❑Does Not
C403.5.2 remote compressors and remote
[ME123)3 condensers not located in a ❑Not Observable
condensing unit, have fan -powered ❑Not Applicable
condensers that comply with Sections
0403.5.1 and refrigeration compressor'
systems that comply with C403.5.2..
Additional Comments/Assumptions:
Comments/Assumptions
1 I High Impact (Tier 1) 12 1 Medium Impact (Tier 2) 1 !i I Low Impact (Tier 3)
Project Title: Thomson Farms Clubhouse Report date: 08/20/18
Data filename: C:\Users\Dwayne 15\Documents\COMcheck\Thomson Farms Clubhouse.cck Page 6 of 9
Section
-
-#Final
Inspection
Complies7
Comments/Assumptions
& Reg. ID
-
C303.3,
Furnished O&M manuals for HVAC
:❑Complies
C408.2.5.:
systems within 90 days of system❑Does
Not',
3
[F1813
acceptance.
![-]Not Observable;
❑Not Applicable
C403.2.2
HVAC systems and equipment❑Complies
[F127]3
capacity does not exceed calculated❑Does
Not
loads.
I❑Not Observable I
!❑Not Applicable
C403.2.4.
Heating and cooling to each zone is❑Complies
1
controlled by a thermostat control.
:❑Does Not
[FI4713
Minimum one humidity control device
;❑Not Observable
per installed
Applicable
humidification/dehumidification❑Not
system.
C403.2.4.
Thermostatic controls have a 5 °F❑Complies
1.2
deadband. j❑Does
Not
[F[38]3
I❑Not
Observable'
❑Not Applicable
C403.2.4.
Temperature controls have setpoint ;❑Complies
,
1.3
overlap restrictions. j❑Does
Not
[FI20]3
I❑Not
Observable;
:El
Not Applicable
C403.2.4.
Each zone equipped with setback I❑Complies
2
controls using automatic time clock or :F
-]Does Not
(F139]3
programmable control system. j❑Not
Observable
j❑NotAppllcable
C403.2.4.
Automatic Controls: Setback to 55°F❑Complies
2.1, i
(heat) and 85°F (cool); 7 -day clock, 2 -❑Does
Not
C403.2.4.
hour occupant override, 10 -hour
EINot Observable;
2.2 :backup
[F140]3❑Not
Applicable
C403.2.4. I
Systems include optimum start
:]Com
2.3 l
controls. �',❑Does
Not
[F14 1]3
![]Not
Observable I
❑Not Applicable
C404.3
Heat traps installed on supply and❑Complies
[Fill]3
discharge piping of non -circulating j❑Does
Not
systems.❑Not
bservableI
Observable:
❑Not Applicable
ONot
C404.4
All piping Insulated in accordance with❑Complies
[FI25]2
section details and Table C403.2.10.
❑Does Not
,J
i❑Not
Observable
-
f❑Not
Applicable
C404.6.1
Controls are installed that limit the❑Complies
[FI12]3
operation of a recirculation pump
❑Does Not
installed to maintain temperature of a
❑Not Observable;
storage tank. System return pipe is a
❑Not Applicable
dedicated return pipe or a cold water
supply pipe.
C408.2.1
Commissioning plan developed by❑Complies
[F12811
registered design professional or j❑Does
Not j
approved agency. j❑Not
Observable
❑Not Applicable
1 JHIgh Impact (Tier 1) JIM Medium Impact (Tier 2) '''39 Low Impact (Tier 3)
Project Title: Thomson Farms Clubhouse Report date: 08/20/18
Data filename: C:\Users\Dwayne 15\Documents\COMcheck\Thomson Farms Clubhouse.cck Page 7 of 9
Section
--_-----_---
#
Final Inspection
Complies? Comments/Assumptions
& Req.ID
C408.2.3.
HVAC equipment has been tested to❑Complies
1
ensure proper operation.
❑Does Not
[FI31]1❑Not
Observable;
❑Not Applicable
C408.2.3.
HVAC control systems have been
❑Complies
2
-tested to ensure proper operation,
❑Does Not
[FI10]1
calibration and adjustment of controls..❑Not
Observable
[]Not Applicable
C408.2.4
Preliminary commissioning report
'❑Complles
[F129]1
completed and certified by registered
:❑Does Not
design professional or approved
Observable;
agency.❑Not
j❑Not Applicable
C408.2.5.
Furnished HVAC as -built drawings
;❑Complies
1
'submitted within 90 days of system
j❑Does Not
[F]7]3
acceptance.
❑Not Observable
I❑Not Applicable
C408.2.5.
An air and/or hydronlc system❑Complies
3
balancing report is provided for HVAC
.❑Does Not
[FI43]1
systems.
;❑Not Observable;
❑Not Applicable j
C408.2.5.
Final commissioning report due to❑Complies
4
building owner within 90 days of
j❑Does Not
[F130]1
receipt of certificate of occupancy.
I❑Not Observable I
❑Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1) 2 Medium Impact (Tier 2) 3 Low Impact (Tier 3)
Project Title: Thomson Farms Clubhouse Report date: 08/20/18
Data filename: C:\Users\Dwayne 15\Documents\COMcheck\Thomson Farms Clubhouse.cck Page 8 of 9