HomeMy WebLinkAboutLOAD SHORT FORM - 18-00434 - 1140 John Hancock Ave - New SFRCalculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2018-Aug-02 07:04:27 Rig ht-Su ite® U niv er sal 20 18 18 .0.19 RSU2 0477 Page 1 ...are\Kartchner\FS5B5 princeton with basement.rup Calc = MJ8 House faces: SW FS5B5Job:Load Short Form 8/2/18Date:Entire House Vince ByramBy: Modern Plumbing, Heating, and Electric P.O. Box 627, Rigby, Id 83442 Phone: 208-745-7021 Fax: 208-745-7329 Email: highcountryph@yahoo.com Project Information Cody PuzeyFor: 3758 Yellowstones Hwy, Idaho Falls, Id 83401 Phone: 208-529-2116 Design Information InfiltrationClgHtg SimplifiedMethod89-6Outside db (°F) AverageConstruction quality7570Inside db (°F) 0Fireplaces1476Design TD (°F) H-Daily range 5050Inside humidity (%) -3162Moisture difference (gr/lb) HEATING EQUIPMENT COOLING EQUIPMENT Make Goodman Mfg.Make Goodman Mfg. Trade GOODMAN Trade GOODMAN, JANITROL, AMANA DISTI... Model GMH950703BX Cond GSX130241C* AHRI ref 2002183 Coil Capf3030bx AHRI ref 4765510 Efficiency 95 AFUE Efficiency 11.0 EER, 13 SEER Heating input Btuh69000 Sensible cooling Btuh16100 Heating output Btuh52440 Latent cooling Btuh6900 Temperature rise °F67 Total cooling Btuh23000 Actual air flow cfm850 Actual air flow cfm850 Air flow factor cfm/Btuh0.024 Air flow factor cfm/Btuh0.081 Static pressure in H2O0.70 Static pressure in H2O0.70 Space thermostat Load sensible heat ratio 1.00 ROOM NAME Area Htg load Clg load Htg AVF Clg AVF (ft²)(Btuh)(Btuh)(cfm)(cfm) Room1 604 9289 2688 227 219 Room2 116 1905 204 47 17 Room3 150 2075 285 51 23 Room4 250 3232 1594 79 130 Room5 242 2001 845 49 69 Room7 45 523 69 13 6 Room8 154 2087 1299 51 106 Room9 120 2553 1312 62 107 Room6 156 2569 850 63 69 Room10 441 4903 1179 120 96 Room11 321 3274 82 80 7 Room13 25 369 33 9 3 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2018-Aug-02 07:04:27 Rig ht-Su ite® U niv er sal 20 18 18 .0.19 RSU2 0477 Page 2 ...are\Kartchner\FS5B5 princeton with basement.rup Calc = MJ8 House faces: SW Entire House d 2624 34779 10441 850 850 Other equip loads 3121 575 Equip. @ 0.94 RSM 10355 Latent cooling 0 TOTALS 2624 37900 10355 850 850 2018-Aug-02 07:04:27 Rig ht-Su ite® U niv er sal 20 18 18 .0.19 RSU2 0477 Page 1 ...are\Kartchner\FS5B5 princeton with basement.rup Calc = MJ8 House faces: SW FS5B5Job:Building Analysis 8/2/18Date:Entire House Vince ByramBy: Modern Plumbing, Heating, and Electric P.O. Box 627, Rigby, Id 83442 Phone: 208-745-7021 Fax: 208-745-7329 Email: highcountryph@yahoo.com Project Information Cody PuzeyFor: 3758 Yellowstones Hwy, Idaho Falls, Id 83401 Phone: 208-529-2116 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temp era ture (°F)Idaho Falls, ID, US 1476Design TD (°F)ft4741Elevation: 5050Relative humidity (%)°N44Latitude:Outdoor:-31.561.5Moisture difference (gr/lb)CoolingHeating Infiltration:89-6Dry bul b (°F) SimplifiedMethod)H(34-Da ily ra nge (°F) AverageConstruction quality60-We t bu lb (°F) 0Fireplaces7.515.0Wind speed (mph) Heating Walls Glazing OtherCeilings Floors Infiltration Ventilation % of loadBtuhBtuh/ft²Component 40.0151504.6Walls 15.6589424.3Glazing 1.247211.4Doors 4.718001.5Ceilings 6.123232.02.0Floors 24.191403.3Infiltration 00Ducts 00Piping 00Humidification 8.23121Ventilation0Adjustments 100.037900Total Cooling Walls Glazing Other Ceilings Infiltration Ventilation % of loadBtuhBtuh/ft²Component 9.810830.3Walls 66.1727630.0Glazing 1.01152.8Doors 9.09950.8Ceilings 1.01090.1Floors 7.88620.3Infiltration 00Ducts 5.2575Ventilation 00Internal gains 00Blower 0Adjustments 100.011015Total Latent Cooling Load = 0 Btuh Overall U-va lue = 0.0 55 Btuh/ft²-°F Data entries checked. 2018-Aug-02 07:04:28 Rig ht-Su ite® U niv er sal 20 18 18 .0.19 RSU2 0477 Page 1 ...are\Kartchner\FS5B5 princeton with basement.rup Calc = MJ8 House faces: SW FS5B5Job:Component Constructions 8/2/18Date:Entire House Vince ByramBy: Modern Plumbing, Heating, and Electric P.O. Box 627, Rigby, Id 83442 Phone: 208-745-7021 Fax: 208-745-7329 Email: highcountryph@yahoo.com Project Information Cody PuzeyFor: 3758 Yellowstones Hwy, Idaho Falls, Id 83401 Phone: 208-529-2116 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temp era ture (°F)Idaho Falls, ID, US 1476Design TD (°F)ft4741Elevation: 5050Relative humidity (%)°N44Latitude: Outdoor:-31.561.5Moisture difference (gr/lb)CoolingHeating Infiltration:89-6Dry bul b (°F) SimplifiedMethod)H(34-Da ily ra nge (°F) AverageConstruction quality60-We t bu lb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 15B19-0wc-6: Bg wall, heavy dry or light damp soil, 2"x6" wood int frm, concrete wall, r-19 cav ins, 8" thk, 1/2" gypsum board int fnsh 200.0613083.9319.00.043333ne 160.0610603.9319.00.043270se 200.0613083.9319.00.043333sw 100.048923.7519.00.043238nw 660.0645683.8919.00.0431174all Frm wall, vnl ext, 3/8" wood shth, r-22 cav ins, 1/2" gypsum board int fnsh, 2"x6" wood frm, 16" o.c. stud 2570.4726764.9422.00.065542ne 2650.4727574.9422.00.065558se 2170.4722604.9422.00.065458sw 2780.4728904.9422.00.065585nw 10160.47105834.9422.00.0652142all Partitions (none) Windows 61C: 61C; 6.67 ft head ht 254223.9258624.300.320106ne 316130.4252924.300.320104sw 76523.977824.300.32032nw 646826.7589424.300.320242all Doors metal: Door, mtl pur core type 1152.7747211.46.70.15041sw Ceilings 16B-50ad: Attic ceiling, asphalt shingles roof mat, r-50 ceil ins, 1/2" gypsum board int fnsh 380.84681.5250.00.02045 16B-50ad: Attic ceiling, asphalt shingles roof mat, r-50 ceil ins, 5/8" gypsum board int fnsh 9570.8417311.5250.00.0201139 Floors 19A-30bscp: Part floor, carpet flr fnsh, r-30 ins, frm flr, 12" thkns, 5/8" gypsum board int fnsh 1090.405942.1730.00.034274 2018-Aug-02 07:04:28 Rig ht-Su ite® U niv er sal 20 18 18 .0.19 RSU2 0477 Page 2 ...are\Kartchner\FS5B5 princeton with basement.rup Calc = MJ8 House faces: SW 21A-24c: Bg floor, heavy dry or light damp soil, 6' depth, carpet flr fnsh 014481.9000.025762 0 00821.9000.02543 002001.9000.025105 0017291.9000.025910all Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2018-Aug-02 07:04:28 Rig ht-Su ite® U niv er sal 20 18 18 .0.19 RSU2 0477 Page 1 ...are\Kartchner\FS5B5 princeton with basement.rup Calc = MJ8 House faces: SW FS5B5Job:Project Summary 8/2/18Date:Entire House Vince ByramBy: Modern Plumbing, Heating, and Electric P.O. Box 627, Rigby, Id 83442 Phone: 208-745-7021 Fax: 208-745-7329 Email: highcountryph@yahoo.com Project Information Cody PuzeyFor:3758 Yellowstones Hwy, Idaho Falls, Id 83401 Phone: 208-529-2116 Notes: Design Information Idaho Falls, ID, USWeather: Winter Design Conditions Summer Design Conditions Outside db °F-6 Outside db °F89Inside db °F70 Inside db °F75 Design TD °F76 Design TD °F14Daily range H Relative humidity %50Moisture difference gr/lb-31 Heating Summary Sensible Cooling Equipment Load Sizing Structure Btuh34779 Structure Btuh10441 Ducts Btuh0 Ducts Btuh0Central vent (44 cfm)3121 Btuh Central vent (44 cfm)Btuh575 Outside air Outside airHumidificationBtuh0Blower Btuh0 Piping Btuh0Equipment load Btuh37900 Use manufacturer's data n Rate/swing multiplier 0.94InfiltrationEquipment sensible load Btuh10355 Method Latent Cooling Equipment Load SizingSimplified Construction quality Average0Fireplaces Structure Btuh-1199 Ducts Btuh0Central vent (44 cfm)Btuh-799 CoolingHeating Outside air26242624Area (ft²)Equipment latent load Btuh0 1904419044Volume (ft³)Air changes/hour 0.210.41 Equipment Total Load (Sen+Lat)Btuh10355 Equiv. AVF (cfm)67130 Req. total capacity at 0.70 SHR ton1.2 Heating Equipment Summary Cooling Equipment Summary Make Goodman Mfg.Make Goodman Mfg.Trade GOODMAN Trade GOODMAN, JANITROL, AMANA DISTI... Model GMH950703BX Cond GSX130241C*AHRI ref 2002183 Coil Capf3030bx AHRI ref 4765510Efficiency95 AFUE Efficiency 11.0 EER, 13 SEER Heating input Btuh69000 Sensible cooling Btuh16100Heating output Btuh52440 Latent cooling Btuh6900 Temperature rise °F67 Total cooling Btuh23000Actual air flow cfm850 Actual air flow cfm850 Air flow factor cfm/Btuh0.024 Air flow factor cfm/Btuh0.081Static pressure in H2O0.70 Static pressure in H2O0.70 Space thermostat Load sensible heat ratio 1.00 2018-Aug-02 07:04:28 Rig ht-Su ite® U niv er sal 20 18 18 .0.19 RSU2 0477 Page 1 ...are\Kartchner\FS5B5 princeton with basement.rup Calc = MJ8 House faces: SW FS5B5Job:AED Assessment 8/2/18Date:Entire House Vince ByramBy: Modern Plumbing, Heating, and Electric P.O. Box 627, Rigby, Id 83442 Phone: 208-745-7021 Fax: 208-745-7329 Email: highcountryph@yahoo.com Project Information Cody PuzeyFor: 3758 Yellowstones Hwy, Idaho Falls, Id 83401 Phone: 208-529-2116 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temp era ture (°F)Idaho Falls, ID, US 1476Design TD (°F)ft4741Elevation: 5050Relative humidity (%)°N44Latitude: Outdoor:-31.561.5Moisture difference (gr/lb)CoolingHeating Infiltration:89-6Dry bul b (°F) )H(34-Da ily ra nge (°F) 60-We t bu lb (°F) 7.515.0Wind speed (mph) Test for Adequate Exposure Diversity Hourly Glazing Load Hourly Average AED limit Gl a z i n g l o a d ( B t u h ) Hour of Day 0 1,000 2,000 3,000 4,000 5,000 6,000 7,000 8,000 9,000 8 9 10 11 12 13 14 15 16 17 18 19 20 Maximum hourly glazing load exceeds average by 44.2%. House does not have adequate exposure diversity (AED), based on AED limit of 30%. AED excursion: 808 Btuh (PFG - 1.3*AFG) Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2018-Aug-02 07:04:28Right-Su ite® U niv er sal 20 18 18 .0.19 RSU2 0477 Page 1...are\Kartchner\FS5B5 princeton with basement.rup Calc = MJ8 House faces: SW FS5B5Job:Right-J® W or ksheet 8/2/18Date:Entire House Vince ByramBy:Modern Plumbing, Heating, and Electric P.O. Box 627, Rigby, Id 83442 Phone: 208-745-7021 Fax: 208-745-7329 Email: highcountryph@yahoo.com 1 Room name Entire House Room1 2 Exposed wall 400.0 ft 101.0 ft 3 Room height 9.0 dft 9.0 heat/coolft 4 Room dimensions ft604.0x1.0 5 Room area 2624.0 f t²604.0 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 15B19-0wc-615B19-0wc-6 0.0690.069 nene 3.933.93 0.060.06 333 333 1308 20 0 0 0 0 .WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nene 4.944.94 0.470.47 648 542 2676 257 216 160 789 76 .GG 61C61C 0.3200.320 nene 24.3224.32 23.9123.91 106 0 2586 2542 56 0 1370 1347 .WW 15B19-0wc-615B19-0wc-6 0.0690.069 sese 3.933.93 0.060.06 270 270 1060 16 0 0 0 0 1 1 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 sese 4.944.94 0.470.47 558 558 2757 265 180 180 889 85 WW 15B19-0wc-615B19-0wc-6 0.0690.069 swsw 3.933.93 0.060.06 333 333 1308 20 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 swsw 4.944.94 0.470.47 603 458 2260 217 216 170 840 81 GG 61C61C 0.3200.320 swsw 24.3224.32 30.3930.39 104 0 2529 3161 25 0 608 760 DD metalmetal 0.1500.150 swsw 11.4011.40 2.782.78 41 41 472 115 21 21 239 58 WW 15B19-0wc-615B19-0wc-6 0.0690.069 nwnw 3.753.75 0.040.04 270 238 892 10 0 0 0 0 GG 61C61C 0.3200.320 nwnw 24.3224.32 23.9123.91 32 0 778 765 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nwnw 4.944.94 0.470.47 585 585 2890 278 297 297 1467 141 CC 16B-50ad16B-50ad 0.0200.020 --1.521.52 0.840.84 45 45 68 38 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.521.52 0.840.84 1139 1139 1731 957 22 22 33 18 FF 19A-30bscp19A-30bscp 0.0340.034 --2.172.17 0.400.40 274 274 594 109 0 0 0 0 FF 21A-24c21A-24c 0.0250.025 --1.901.90 0.000.00 762 762 1448 0 0 0 0 0 FF 21A-24c21A-24c 0.0250.025 --1.901.90 0.000.00 43 43 82 0 43 43 82 0 FF 21A-24c21A-24c 0.0250.025 --1.901.90 0.000.00 105 105 199 0 0 0 0 0 6 c) AED excursion 808 -158 Envelope loss/gain 25639 9578 6317 2408 12 a)Infiltration 9140 862 2972 280 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)34779 10441 9289 2688 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 34779 10441 9289 2688 15 Duct loads 0%0%0 0 -0%0%0 0 Total room load 34779 10441 9289 2688 Air required (cfm)Air required (cfm)850 850 227 219 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2018-Aug-02 07:04:28Right-Su ite® U niv er sal 20 18 18 .0.19 RSU2 0477 Page 2...are\Kartchner\FS5B5 princeton with basement.rup Calc = MJ8 House faces: SW FS5B5Job:Right-J® W or ksheet 8/2/18Date:Entire House Vince ByramBy:Modern Plumbing, Heating, and Electric P.O. Box 627, Rigby, Id 83442 Phone: 208-745-7021 Fax: 208-745-7329 Email: highcountryph@yahoo.com 1 Room name Room2 Room3 2 Exposed wall 24.0 ft 25.0 ft 3 Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft116.0x1.0 ft15.0x10.0 5 Room area 116.0 f t²150.0 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 15B19-0wc-615B19-0wc-6 0.0690.069 nene 3.933.93 0.060.06 0 0 0 0 0 0 0 0 .WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nene 4.944.94 0.470.47 63 63 311 30 90 90 445 43 .GG 61C61C 0.3200.320 nene 24.3224.32 23.9123.91 0 0 0 0 0 0 0 0 .WW 15B19-0wc-615B19-0wc-6 0.0690.069 sese 3.933.93 0.060.06 0 0 0 0 0 0 0 0 1 1 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 sese 4.944.94 0.470.47 90 90 445 43 0 0 0 0 WW 15B19-0wc-615B19-0wc-6 0.0690.069 swsw 3.933.93 0.060.06 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 swsw 4.944.94 0.470.47 63 43 210 20 0 0 0 0 GG 61C61C 0.3200.320 swsw 24.3224.32 30.3930.39 0 0 0 0 0 0 0 0 DD metalmetal 0.1500.150 swsw 11.4011.40 2.782.78 20 20 233 57 0 0 0 0 WW 15B19-0wc-615B19-0wc-6 0.0690.069 nwnw 3.753.75 0.040.04 0 0 0 0 0 0 0 0 GG 61C61C 0.3200.320 nwnw 24.3224.32 23.9123.91 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nwnw 4.944.94 0.470.47 0 0 0 0 135 135 667 64 CC 16B-50ad16B-50ad 0.0200.020 --1.521.52 0.840.84 0 0 0 0 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.521.52 0.840.84 0 0 0 0 150 150 228 126 FF 19A-30bscp19A-30bscp 0.0340.034 --2.172.17 0.400.40 0 0 0 0 0 0 0 0 FF 21A-24c21A-24c 0.0250.025 --1.901.90 0.000.00 0 0 0 0 0 0 0 0 FF 21A-24c21A-24c 0.0250.025 --1.901.90 0.000.00 0 0 0 0 0 0 0 0 FF 21A-24c21A-24c 0.0250.025 --1.901.90 0.000.00 0 0 0 0 0 0 0 0 6 c) AED excursion -12 -17 Envelope loss/gain 1199 137 1339 216 12 a)Infiltration 706 67 736 69 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)1905 204 2075 285 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 1905 204 2075 285 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 1905 204 2075 285 Air required (cfm)Air required (cfm)47 17 51 23 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2018-Aug-02 07:04:28Right-Su ite® U niv er sal 20 18 18 .0.19 RSU2 0477 Page 3...are\Kartchner\FS5B5 princeton with basement.rup Calc = MJ8 House faces: SW FS5B5Job:Right-J® W or ksheet 8/2/18Date:Entire House Vince ByramBy:Modern Plumbing, Heating, and Electric P.O. Box 627, Rigby, Id 83442 Phone: 208-745-7021 Fax: 208-745-7329 Email: highcountryph@yahoo.com 1 Room name Room4 Room5 2 Exposed wall 31.0 ft 14.0 ft 3 Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft250.0x1.0 ft242.0x1.0 5 Room area 250.0 f t²242.0 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 15B19-0wc-615B19-0wc-6 0.0690.069 nene 3.933.93 0.060.06 0 0 0 0 0 0 0 0 .WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nene 4.944.94 0.470.47 0 0 0 0 126 101 499 48 .GG 61C61C 0.3200.320 nene 24.3224.32 23.9123.91 0 0 0 0 25 0 608 598 .WW 15B19-0wc-615B19-0wc-6 0.0690.069 sese 3.933.93 0.060.06 0 0 0 0 0 0 0 0 1 1 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 sese 4.944.94 0.470.47 0 0 0 0 0 0 0 0 WW 15B19-0wc-615B19-0wc-6 0.0690.069 swsw 3.933.93 0.060.06 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 swsw 4.944.94 0.470.47 135 106 524 50 0 0 0 0 GG 61C61C 0.3200.320 swsw 24.3224.32 30.3930.39 29 0 705 881 0 0 0 0 DD metalmetal 0.1500.150 swsw 11.4011.40 2.782.78 0 0 0 0 0 0 0 0 WW 15B19-0wc-615B19-0wc-6 0.0690.069 nwnw 3.753.75 0.040.04 0 0 0 0 0 0 0 0 GG 61C61C 0.3200.320 nwnw 24.3224.32 23.9123.91 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nwnw 4.944.94 0.470.47 144 144 711 68 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.521.52 0.840.84 0 0 0 0 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.521.52 0.840.84 250 250 380 210 242 242 368 203 FF 19A-30bscp19A-30bscp 0.0340.034 --2.172.17 0.400.40 0 0 0 0 0 0 0 0 FF 21A-24c21A-24c 0.0250.025 --1.901.90 0.000.00 0 0 0 0 0 0 0 0 FF 21A-24c21A-24c 0.0250.025 --1.901.90 0.000.00 0 0 0 0 0 0 0 0 FF 21A-24c21A-24c 0.0250.025 --1.901.90 0.000.00 0 0 0 0 60 60 114 0 6 c) AED excursion 298 -42 Envelope loss/gain 2320 1508 1589 807 12 a)Infiltration 912 86 412 39 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)3232 1594 2001 845 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 3232 1594 2001 845 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 3232 1594 2001 845 Air required (cfm)Air required (cfm)79 130 49 69 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2018-Aug-02 07:04:28Right-Su ite® U niv er sal 20 18 18 .0.19 RSU2 0477 Page 4...are\Kartchner\FS5B5 princeton with basement.rup Calc = MJ8 House faces: SW FS5B5Job:Right-J® W or ksheet 8/2/18Date:Entire House Vince ByramBy:Modern Plumbing, Heating, and Electric P.O. Box 627, Rigby, Id 83442 Phone: 208-745-7021 Fax: 208-745-7329 Email: highcountryph@yahoo.com 1 Room name Room7 Room8 2 Exposed wall 5.0 ft 14.0 ft 3 Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft5.0x9.0 ft14.0x11.0 5 Room area 45.0 f t²154.0 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 15B19-0wc-615B19-0wc-6 0.0690.069 nene 3.933.93 0.060.06 0 0 0 0 0 0 0 0 .WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nene 4.944.94 0.470.47 0 0 0 0 0 0 0 0 .GG 61C61C 0.3200.320 nene 24.3224.32 23.9123.91 0 0 0 0 0 0 0 0 .WW 15B19-0wc-615B19-0wc-6 0.0690.069 sese 3.933.93 0.060.06 0 0 0 0 0 0 0 0 1 1 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 sese 4.944.94 0.470.47 45 45 222 21 18 18 89 9 WW 15B19-0wc-615B19-0wc-6 0.0690.069 swsw 3.933.93 0.060.06 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 swsw 4.944.94 0.470.47 0 0 0 0 99 74 366 35 GG 61C61C 0.3200.320 swsw 24.3224.32 30.3930.39 0 0 0 0 25 0 608 760 DD metalmetal 0.1500.150 swsw 11.4011.40 2.782.78 0 0 0 0 0 0 0 0 WW 15B19-0wc-615B19-0wc-6 0.0690.069 nwnw 3.753.75 0.040.04 0 0 0 0 0 0 0 0 GG 61C61C 0.3200.320 nwnw 24.3224.32 23.9123.91 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nwnw 4.944.94 0.470.47 0 0 0 0 9 9 44 4 CC 16B-50ad16B-50ad 0.0200.020 --1.521.52 0.840.84 0 0 0 0 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.521.52 0.840.84 45 45 68 38 154 154 234 129 FF 19A-30bscp19A-30bscp 0.0340.034 --2.172.17 0.400.40 0 0 0 0 154 154 334 62 FF 21A-24c21A-24c 0.0250.025 --1.901.90 0.000.00 0 0 0 0 0 0 0 0 FF 21A-24c21A-24c 0.0250.025 --1.901.90 0.000.00 0 0 0 0 0 0 0 0 FF 21A-24c21A-24c 0.0250.025 --1.901.90 0.000.00 45 45 85 0 0 0 0 0 6 c) AED excursion -4 261 Envelope loss/gain 376 55 1675 1260 12 a)Infiltration 147 14 412 39 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)523 69 2087 1299 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 523 69 2087 1299 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 523 69 2087 1299 Air required (cfm)Air required (cfm)13 6 51 106 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2018-Aug-02 07:04:28Right-Su ite® U niv er sal 20 18 18 .0.19 RSU2 0477 Page 5...are\Kartchner\FS5B5 princeton with basement.rup Calc = MJ8 House faces: SW FS5B5Job:Right-J® W or ksheet 8/2/18Date:Entire House Vince ByramBy:Modern Plumbing, Heating, and Electric P.O. Box 627, Rigby, Id 83442 Phone: 208-745-7021 Fax: 208-745-7329 Email: highcountryph@yahoo.com 1 Room name Room9 Room6 2 Exposed wall 22.0 ft 25.0 ft 3 Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft12.0x10.0 ft13.0x12.0 5 Room area 120.0 f t²156.0 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 15B19-0wc-615B19-0wc-6 0.0690.069 nene 3.933.93 0.060.06 0 0 0 0 0 0 0 0 .WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nene 4.944.94 0.470.47 0 0 0 0 108 83 410 39 .GG 61C61C 0.3200.320 nene 24.3224.32 23.9123.91 0 0 0 0 25 0 608 598 .WW 15B19-0wc-615B19-0wc-6 0.0690.069 sese 3.933.93 0.060.06 0 0 0 0 0 0 0 0 1 1 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 sese 4.944.94 0.470.47 108 108 534 51 117 117 578 56 WW 15B19-0wc-615B19-0wc-6 0.0690.069 swsw 3.933.93 0.060.06 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 swsw 4.944.94 0.470.47 90 65 321 31 0 0 0 0 GG 61C61C 0.3200.320 swsw 24.3224.32 30.3930.39 25 0 608 760 0 0 0 0 DD metalmetal 0.1500.150 swsw 11.4011.40 2.782.78 0 0 0 0 0 0 0 0 WW 15B19-0wc-615B19-0wc-6 0.0690.069 nwnw 3.753.75 0.040.04 0 0 0 0 0 0 0 0 GG 61C61C 0.3200.320 nwnw 24.3224.32 23.9123.91 0 0 0 0 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nwnw 4.944.94 0.470.47 0 0 0 0 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.521.52 0.840.84 0 0 0 0 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.521.52 0.840.84 120 120 182 101 156 156 237 131 FF 19A-30bscp19A-30bscp 0.0340.034 --2.172.17 0.400.40 120 120 260 48 0 0 0 0 FF 21A-24c21A-24c 0.0250.025 --1.901.90 0.000.00 0 0 0 0 0 0 0 0 FF 21A-24c21A-24c 0.0250.025 --1.901.90 0.000.00 0 0 0 0 0 0 0 0 FF 21A-24c21A-24c 0.0250.025 --1.901.90 0.000.00 0 0 0 0 0 0 0 0 6 c) AED excursion 260 -43 Envelope loss/gain 1905 1251 1833 781 12 a)Infiltration 647 61 736 69 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)2553 1312 2569 850 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 2553 1312 2569 850 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 2553 1312 2569 850 Air required (cfm)Air required (cfm)62 107 63 69 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2018-Aug-02 07:04:28Right-Su ite® U niv er sal 20 18 18 .0.19 RSU2 0477 Page 6...are\Kartchner\FS5B5 princeton with basement.rup Calc = MJ8 House faces: SW FS5B5Job:Right-J® W or ksheet 8/2/18Date:Entire House Vince ByramBy:Modern Plumbing, Heating, and Electric P.O. Box 627, Rigby, Id 83442 Phone: 208-745-7021 Fax: 208-745-7329 Email: highcountryph@yahoo.com 1 Room name Room10 Room11 2 Exposed wall 75.0 ft 59.0 ft 3 Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft441.0x1.0 ft321.0x1.0 5 Room area 441.0 f t²321.0 f t² Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 15B19-0wc-615B19-0wc-6 0.0690.069 nene 3.933.93 0.060.06 117 117 459 7 216 216 848 13 .WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nene 4.944.94 0.470.47 0 0 0 0 0 0 0 0 .GG 61C61C 0.3200.320 nene 24.3224.32 23.9123.91 0 0 0 0 0 0 0 0 .WW 15B19-0wc-615B19-0wc-6 0.0690.069 sese 3.933.93 0.060.06 144 144 565 9 126 126 495 8 1 1 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 sese 4.944.94 0.470.47 0 0 0 0 0 0 0 0 WW 15B19-0wc-615B19-0wc-6 0.0690.069 swsw 3.933.93 0.060.06 153 153 601 9 180 180 707 11 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 swsw 4.944.94 0.470.47 0 0 0 0 0 0 0 0 GG 61C61C 0.3200.320 swsw 24.3224.32 30.3930.39 0 0 0 0 0 0 0 0 DD metalmetal 0.1500.150 swsw 11.4011.40 2.782.78 0 0 0 0 0 0 0 0 WW 15B19-0wc-615B19-0wc-6 0.0690.069 nwnw 3.753.75 0.040.04 261 229 857 10 9 9 35 1 GG 61C61C 0.3200.320 nwnw 24.3224.32 23.9123.91 32 0 778 765 0 0 0 0 WW Frm wall, vnl ext, 3 0.065Frm wall, vnl ext, 3 0.065 nwnw 4.944.94 0.470.47 0 0 0 0 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.521.52 0.840.84 45 45 68 38 0 0 0 0 CC 16B-50ad16B-50ad 0.0200.020 --1.521.52 0.840.84 0 0 0 0 0 0 0 0 FF 19A-30bscp19A-30bscp 0.0340.034 --2.172.17 0.400.40 0 0 0 0 0 0 0 0 FF 21A-24c21A-24c 0.0250.025 --1.901.90 0.000.00 441 441 838 0 321 321 610 0 FF 21A-24c21A-24c 0.0250.025 --1.901.90 0.000.00 0 0 0 0 0 0 0 0 FF 21A-24c21A-24c 0.0250.025 --1.901.90 0.000.00 0 0 0 0 0 0 0 0 6 c) AED excursion 272 -5 Envelope loss/gain 4167 1109 2695 27 12 a)Infiltration 736 69 579 55 b)Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)4903 1179 3274 82 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 4903 1179 3274 82 15 Duct loads -0%0%0 0 -0%0%0 0 Total room load 4903 1179 3274 82 Air required (cfm)Air required (cfm)120 96 80 7 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2018-Aug-02 07:04:28Right-Su ite® U niv er sal 20 18 18 .0.19 RSU2 0477 Page 7...are\Kartchner\FS5B5 princeton with basement.rup Calc = MJ8 House faces: SW FS5B5Job:Right-J® W or ksheet 8/2/18Date:Entire House Vince ByramBy:Modern Plumbing, Heating, and Electric P.O. Box 627, Rigby, Id 83442 Phone: 208-745-7021 Fax: 208-745-7329 Email: highcountryph@yahoo.com 1 Room name Room13 2 Exposed wall 5.0 ft 3 Room height 9.0 heat/coolft 4 Room dimensions ft5.0x5.0 5 Room area 25.0 f t² Ty Construction U-value Or HTM Area (f t²)Load Area Load number (Bt uh/f t²-°F)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 W 15B19-0wc-6 0.069 ne 3.93 0.06 0 0 0 0 .W Frm wall, vnl ext, 3 0.065 ne 4.94 0.47 45 45 222 21 .G 61C 0.320 ne 24.32 23.91 0 0 0 0 .W 15B19-0wc-6 0.069 se 3.93 0.06 0 0 0 0 1 1 W Frm wall, vnl ext, 3 0.065 se 4.94 0.47 0 0 0 0 W 15B19-0wc-6 0.069 sw 3.93 0.06 0 0 0 0 W Frm wall, vnl ext, 3 0.065 sw 4.94 0.47 0 0 0 0 G 61C 0.320 sw 24.32 30.39 0 0 0 0 D metal 0.150 sw 11.40 2.78 0 0 0 0 W 15B19-0wc-6 0.069 nw 3.75 0.04 0 0 0 0 G 61C 0.320 nw 24.32 23.91 0 0 0 0 W Frm wall, vnl ext, 3 0.065 nw 4.94 0.47 0 0 0 0 C 16B-50ad 0.020 -1.52 0.84 0 0 0 0 C 16B-50ad 0.020 -1.52 0.84 0 0 0 0 F 19A-30bscp 0.034 -2.17 0.40 0 0 0 0 F 21A-24c 0.025 -1.90 0.00 0 0 0 0 F 21A-24c 0.025 -1.90 0.00 0 0 0 0 F 21A-24c 0.025 -1.90 0.00 0 0 0 0 6 c) AED excursion -2 Envelope loss/gain 222 19 12 a)Infiltration 147 14 b)Room ventilation 0 0 13 Internal gains:Occupants @ 230 0 0 Appliances/other 0 Subtotal (lines 6 to 13)369 33 Less external load 0 0 Less transfer 0 0 Redistribution 0 0 14 Subtotal 369 33 15 Duct loads -0%0%0 0 Total room load 369 33 Air required (cfm)9 3 Job #: FS5B5 Performed by Vince Byram for: Cody Puzey 3758 Yellowstones Hwy Idaho Falls, Id 83401 Phone: 208-529-2116 Modern Plumbing, Heating, and Electric P.O. Box 627 Rigby, Id 83442 Phone: 208-745-7021 Fax: 208-745-7329 highcountryph@yahoo.com Scale: 1 : 85 Page 1 Ri ght -Sui te ® U ni versa l 20 18 18.0.19 RSU20477 2018-Aug-02 07:04:56 ...S5B5 princeton with basement.rup N 2nd Story Room3 Room4 Room5 Room6 Room7 Room8 Room9 65 cfm 51 cfm 65 cfm 106 cfm 106 cfm 74 cfm 69 cfm 69 cfm 69 cfm 13 cfm 107 cfm 107 cfm 153 cfm Job #: FS5B5 Performed by Vince Byram for: Cody Puzey 3758 Yellowstones Hwy Idaho Falls, Id 83401 Phone: 208-529-2116 Modern Plumbing, Heating, and Electric P.O. Box 627 Rigby, Id 83442 Phone: 208-745-7021 Fax: 208-745-7329 highcountryph@yahoo.com Scale: 1 : 85 Page 2 Ri ght -Sui te ® U ni versa l 20 18 18.0.19 RSU20477 2018-Aug-02 07:04:57 ...S5B5 princeton with basement.rup N Main Floor Room1 Room2 Room12 Room13 36'-0" 57 cfm 57 cfm 57 cfm 57 cfm 283 cfm 9 cfm 23 cfm 23 cfm Sup Riser 8 " Ret Riser 7 " 6 " 6 " 6 " 6 "6 " 6 " 6 " 6 "6 " 20 x 8 14x3.25 2-14x3.25 14x3.25 2-14x3.25 14x3.25 14x3.25 12 x 8 20 x 8 8 "12 x 8 6 "6 "6 " 6 "6 " 6 " 7 " 8 x 88 x 8 Job #: FS5B5 Performed by Vince Byram for: Cody Puzey 3758 Yellowstones Hwy Idaho Falls, Id 83401 Phone: 208-529-2116 Modern Plumbing, Heating, and Electric P.O. Box 627 Rigby, Id 83442 Phone: 208-745-7021 Fax: 208-745-7329 highcountryph@yahoo.com Scale: 1 : 85 Page 3 Ri ght -Sui te ® U ni versa l 20 18 18.0.19 RSU20477 2018-Aug-02 07:04:57 ...S5B5 princeton with basement.rup N basement Room10 Room11 60 cfm 60 cfm 80 cfm Sup Riser 8 " Ret Riser 7 "200 cfm 8 " 6 " 6 " 6 " 7 " 2018-Aug-02 07:04:28 Rig ht-Su ite® U niv er sal 20 18 18 .0.19 RSU2 0477 Page 1 ...are\Kartchner\FS5B5 princeton with basement.rup Calc = MJ8 House faces: SW FS5B5Job:Duct System Summary 8/2/18Date:Entire House Vince ByramBy: Modern Plumbing, Heating, and Electric P.O. Box 627, Rigby, Id 83442 Phone: 208-745-7021 Fax: 208-745-7329 Email: highcountryph@yahoo.com Project Information Cody PuzeyFor: 3758 Yellowstones Hwy, Idaho Falls, Id 83401 Phone: 208-529-2116 CoolingHeating External static pressure in H2O0.70in H2O0.70 Pressure losses in H2O0.29in H2O0.29 Available static pressure in H2O0.41in H2O0.41 Supply / return available pressure 0.226 / 0.184 in H2O in H2O0.226 / 0.184 Lowest friction rate in/100ft0.068in/100ft0.068 Actual air flow cfm850cfm850 Total effective length (TEL)ft605 Supply Branch Detail Table Design Htg Clg Design Diam H x W Duct Actual Ftg.Eqv Name (Btuh)(cfm)(cfm)FR (in)(in)Matl Ln (ft)Ln (ft)Trunk st1B235.037.0ShMt0x06.00.08355572322hRoom1 st1140.025.0ShMt0x06.00.13755572322hRoom1-A st1C285.049.0ShMt0x06.00.06855572322hRoom1-B st1A170.038.0ShMt0x06.00.10955572322hRoom1-C st2170.058.4ShMt0x06.00.09948602451hRoom10 st2170.051.4ShMt0x06.00.10248602451hRoom10-A st2180.035.4ShMt0x06.00.1057803274hRoom11 st1175.014.0ShMt0x06.00.12039369hRoom13 st1175.08.0ShMt0x06.00.124823953hRoom2 st1160.012.0ShMt0x06.00.132823953hRoom2-B st1B245.036.0ShMt0x06.00.08123512075hRoom3 st1A180.040.9ShMt0x06.00.1026539797cRoom4 st1A215.046.0ShMt0x06.00.0876539797cRoom4-A st1130.025.0ShMt0x06.00.1466949845cRoom5 st1175.012.0ShMt0x06.00.1216963850cRoom6 st1175.011.0ShMt0x06.00.122613523hRoom7 st1150.033.0ShMt0x06.00.124106511299cRoom8 st1165.025.0ShMt0x06.00.119107621312cRoom9 2018-Aug-02 07:04:28 Rig ht-Su ite® U niv er sal 20 18 18 .0.19 RSU2 0477 Page 2 ...are\Kartchner\FS5B5 princeton with basement.rup Calc = MJ8 House faces: SW Supply Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk st1A Peak AVF 300 317 0.068 476 9.7 12x8 ShtMetl st1 st2 Peak AVF 200 103 0.099 572 8.0 0x0 ShtMetl st1B Peak AVF 164 133 0.068 370 7.6 8x8 ShtMetl st1A st1 Peak AVF 650 747 0.068 673 13.4 20x8 ShtMetl st1C Peak AVF 57 55 0.068 128 5.1 8x8 ShtMetl st1B Return Branch Detail Table Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size (in)(cfm)(cfm)(ft)FR (fpm)(in)(in)Opening (in)Matl Trunk rb7 0x 2000 103 135.0 0.136 632 7.1 3.25x14 10x9 SJSp rb2 0x 630 69 96.1 0.191 219 4.5 3.25x14 10x9 SJSp rt2 rb3 0x 620 107 92.1 0.199 338 5.2 3.25x14 10x9 SJSp rt2 rb4 0x 510 106 99.1 0.185 335 5.3 3.25x14 10x9 SJSp rt2 rb6 0x 620 74 114.1 0.161 236 4.7 3.25x14 10x9 SJSp rt2 rb1 0x 2830 238 177.1 0.104 447 8.5 2-3.25x14 2-10x18 SJSp rt2 rb5 0x 1300 153 271.1 0.068 242 7.4 2-3.25x14 2-10x18 SJSp rt2A Return Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk rt2 Peak AVF 650 747 0.068 673 13.4 20x8 ShtMetl rt2A Peak AVF 130 153 0.068 229 7.4 12x8 ShtMetl rt2