Current Building Review Status: REVISIONS
Application Number: 18-00176Permit Details
Application Received Date: 04/04/2018
Multi-Family Residential
Application Approved Date:
Application Approved Status: ACCEPTED
06/27/2018
220 S 2nd W
Arbor Cove - Bldg #2 - 50 Units - New Dormitory Housing
Status of Plan Reviews Completed
06/07/2018Electrical Review COMPLETED
06/27/2018Building Review REVISIONS
Permit Review Status
Plan Reviews Still in Progress
Plumbing Review
HVAC Review
Planning and Zoning Review - Site Plan
Public Works Review - Site Plan
Fire Department Review - Site Plan
Building Review
DESCRIPTION COMMENTS STA TUS
*Please respond to "REVISIONS" status items, with appropriate comment/documentation as needed!
Rated doors and windows comply with Section
716
REVISIONSElevator equipment room shall be enclosed with
the same fire rated assemblies as the elevator
shaft - Door C103A should be 90 minute rated
for a 2 hour rated wall.
*Revisions Response :
Exit Enclosures meet the requirements of IBC
Section 1023
REVISIONSMechanical room cannot be accessed from
within the exit stair enclosure (1023.4)
*Revisions Response :
Toilets, Bathing Fac., Sinks, Kit. and Drink. Fount.
meet IBC Sec. 1109
REVISIONSType A units need a forward approach work
surface and sink in kitchen and at a type A
bathroom.
*Revisions Response :
Reviewed By: Quinton Owens
Review Date: 06/27/2018
Plan Review Details
quinton.owens@rexburg.org
Building Review Status: REVISIONS
Page 1 of 2
Approval of plans does not constitue approval of variance from code
Building Review (Continued)
D ESCRIPTIO N CO MMEN TS STATUS
Emergency Escape openings provided per IBC
1030 (R2 & R3 only)
REVISIONS
(Same note as on building 1 review) Window
notes call for device to limit opening such that a
4" sphere may not pass through. Emergency
egress windows are required in all sleeping
rooms. Fire sprinklers have not been an
exception to this requirement since the 2009
IBC. The clear opening width shall be 20"
minimum (opening area of 5.7 sf minimum).
*Revisions Response :
Exterior walls meet the requirements of IBC
Section 705
REVISIONS(Same note as on building 1 review) Opposing
walls of building 1 & 2 to be fire rated on
interior and exterior where less than 10 feet
apart. Only one needs be rated on interior and
exterior where walls are 10 - 20 feet apart.
Other walls only require fire rating for bearing
walls as per construction type V-A.Please
identify exterior wall types for fire rating.
*Revisions Response :
Exterior wall openings meet the requirements of
IBC Section 705.8
(Same note as on building 1 review) Where FSD
is 3 to less than 5 feet, 15% unprotected
opening allowance only applies to building 1
because of the required NFPA 13 system.
Building 2 requires at least 5 feet FSD to allow
up to 10% unprotected openings with a 13R
sprinkler system.
COMPLETED
Fire barriers meet the requirements of IBC
Section 707
Wall between elevator/equipment room and the
apartment is not identified. It shall be a 2 hour
fire barrier (same as apartment and equipment
separation wall in building 1) .
COMPLETED
Building complies with IECC (IBC 1301)No COMcheck found with application.
Prescriptive requirements of the IECC shall be
met.
COMPLETED
Elevators and Conveying Systems comply with
Chapter 30
Elevator shall comply with chapter 30, including
being able to accommodate a 24" x 84"
ambulance stretcher.
COMPLETED
Exit Lighting and Exit Signs comply with IBC 1008
& 1013
COMPLETED
Additional Inspector Comments:
Building 2 Review
Page 2 of 2
Approval of plans does not constitue approval of variance from code