HomeMy WebLinkAboutCOMCHECK MECH - 18-00315 - Approx. 1000 N Yellowstone Hwy - The Grove at Thomson Farms - 30 Unit BldgCOMcheck Software Version 4.0.7.2 Review
A/ Mechanical Compliance Ce '
p rtificate
Project Information
Energy Code:
Project Title:
Location:
Climate Zone:
Project Type:
Construction Site:
472 N. Yellowstone Hwy
Rexburg, ID 83440
Additional Efficiency Package
Unspecified
Mechanical Systems List
Quantity System Type & Description
2015 IECC
Thomson Farms Apartments 3 Story Building
Rexburg, Idaho
6b
New Construction
Owner/Agent:
Stillwater Equity Partners
Designer/Contractor:
Dwayne Sudweeks
Engineered Systems Assoc., Inc.
1355 E. Center St,
Pocatello, ID 83201
208-233-0501
dcs@engsystems.com
27 HVAC System 1 (Single Zone):
Heating: 1 each - Duct Furnace, Gas, Capacity = 44 kBtu/h
Proposed Efficiency = 95.00% Ec, Required Efficiency = 80.00% Ec
Cooling: 1 each - Split System, Capacity = 24 kBtu/h, Air -Cooled Condenser, No Economizer, Economizer exception: Low Capacity
Residential
Proposed Efficiency = 13.00 SEER, Required Efficiency: 13.00 SEER
Fan System: FAN SYSTEM 1 — Compliance (Motor nameplate HP method) : Passes
Fans:
FAN 1 Supply, Constant Volume, 800 CFM, 0.3 motor nameplate hp, 0.8 fan efficiency grade
SYSTEM COMPLIANCE FAILS: Economizer requirements have not been met.
HVAC System 2 (Single Zone):
Heating: 1 each - Central Furnace. Gas, Capacity = 44 kBtu/h
Proposed Efficiency = 95.00% Et, Required Efficiency = 80.00% Et
Cooling: 1 each - Split System, Capacity = 30 kBtu/h, Air -Cooled Condenser, No Economizer, Economizer exception: Low Capacity
Residential
Proposed Efficiency = 13.00 SEER, Required Efficiency: 13.00 SEER
Fan System: FAN SYSTEM 2 — Compliance (Motor nameplate HP method) : Passes
Fans:
FAN 2 Supply, Constant Volume, 1000 CFM, 0.3 motor nameplate hp, 0.8 fan efficiency grade
30 Water Heater 1:
Gas Storage Water Heater, Capacity: 50 gallons, Input Rating: 40 kBtu/h
Proposed Efficiency: 0.90 EF, Required Efficiency: 0.58 EF
Mechanical Compliance Statement
Compliance Statement: The proposed mechanical design represented in this document is consistent with the building plans,
specifications, and other calculations submitted with this permit application. The proposed mechanical systems have been
designed to meet the 2015 IECC requirements in COMcheck Version 4.0.7.2 Review and to comply with any applicable
mandatory requirements listed in the Inspection Checklist,
Project Title: Thomson Farms Apartments 3 Story Building
Data filename: C:\Users\Dwayne 15\Documents\COMcheck\Thomson Farms 3 story.cck Report date: 06/26/18
Page 1 of 11
Name - Tit 5 � Signature "` 2i� ��
Date
Project Title: Thomson Farms Apartments 3 Story Building
Data filename: C:\Users\Dwayne 15\Documents\COmcheck\Thomson Farms 3 story.cck Report date: 06/26/18
Page 2 of 11
COMcheck Software Version 4.0.7.2 Review
Inspection Checklist
Energy Code: 2015 IECC
Requirements: 0.0% were addressed directly in the COMcheck software
Text in the "Comments/Assumptions" column is provided by the user in the COMcheck Requirements screen. For each
requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception
is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided.
section ��_ -
& Req
C103.2
[PR2]1
Pian Review I Complies?
Plans, specifications, and/or
calculations provide all information
with which compliance can be
determined for the mechanical
systems and equipment and
document where exceptions to the
standard are claimed. Load
calculations per acceptable
engineering standards and
handbooks.
❑Complies
❑Does Not
❑Not Observable
❑Not Applicable
Comments/Assumptions
C103.2
[PR3]1
Plans, specifications, and/or
calculations provide all information
❑Complies
❑Does Not
With which compliance can be
determined for the service water
❑Not Observable
heating systems and equipment and
❑Not Applicable
document where exceptions to the
standard are claimed. Hot water
system sized per manufacturer's
sizing guide.
C406
i[PR9]1
Plans, specifications, and/or
calculations provide all information
p
Complies --
[]Does Not
with which compliance can be
determined for the additional energy
efficiency
❑Not Observable
package options.
❑Not Applicable
Additional Comments/Assumptions:
—
1 ;High Impact (Tier 1)
2 Medium Impact (Tier 2
_— m p ) j 3 Low Impact (Tier 3)
Project Title:
Thomson Farms Apartments 3 Story Building
Data filename:
C:\Users\Dwayne 15\Documents\COMcheck\Thomson Farms 3 story.cck Report date: 06/26/18
Page 3 of 11
#I Footing / Foundation Inspection Complies?
& Req. ID
C403.2.4. Snow/ice melting system sensors for DComplies
5. future connection to controls. Freeze []Does Not
C403.2.4. protection systems have automatic
6 controls installed. E]Not Observable
[FO9]3 []Not Applicable
Additional Comments/Assumptions:
Comments/Assumptions
1 i High Impact (Tier 1) j 2 Medium Impact (Tier 2) i 3 1 low Impact (Tier 3)
Project Title: Thomson Farms Apartments 3 Story Building
Data filename: C:\Users\Dwayne 15\Documents\COMcheck\Thomson Farms 3 story.cck Report date: 06/26/18
Page 4 of 11
Section
#1 Plumbing Rough -In Inspection Complies?
& Req.l01—__ i
C404.5, Heated water supply piping conforms J❑Complies
C404.5.1, to pipe length and volume
C404.5.2 requirements. Refer to section details. ❑Does Not
[PL6]3 ❑Not Observable
❑Not Applicable
0404.5,
C404.5.1,
C404.5.2
[PL6]3
Heated water supply piping conforms ❑Complies
to pipe length and volume ❑Does Not
requirements. Refer to section dPt;4n�
❑Not Observable
❑Not Applicable
C404.5, Heated water supply piping conforms ❑Complies
C404.5.1, to pipe length and volume
C404.5.2 requirements. Refer to section details. ❑Does Not
[PL6]3 ❑Not Observable
❑Not Applicable
Comments/Assumptions
1 High Impact (Tier 1) 2 'Medium Impact (Tier 2) 3 Low Impact (Tier 3)
Project Title: Thomson Farms Apartments 3 Story Building
Data filename: CAUsers\Dwayne I5\Documents\COMcheck\Thomson Farms 3 Story.cck Report date: 06/26/18
Page 5 of 11
Pumps that circulate water between a
[]Complies
{0404.6.3
[PL7]3
heater and storage tank have controls ❑Does
that limit operation from startup to
Not
i
— 5 minutes after end of heating
❑Not Observable
cycle.
❑Not Applicable
C404.6.3
i [PL7]3
___
Pumps that circulate water between a
❑Complies — -"—
heater and storage tank have controls
❑Does Not
that limit operation from startup to
— 5 minutes after end of heating
[]Not Observable
_
cycle_
❑Not Applicable
C404.6.31
[PL7]3
Pumps that circulate water between a
❑Complies —�
heater and storage tank have controls
❑Does Not
that limit operation from startup to
<= 5 minutes after end of heating
❑Not Observable
cycle.
❑Not Applicable
0404.7
[PL8]3
Water distribution system that pumps
❑Complies
water from a heated -water supply
❑Does Not
pipe back to the heated -water source
through a cold -water supply pipe is a
❑Not Observable
demand recirculation water system.
❑Not Applicable
Pumps within this system have
controls that start the pump upon
receiving a signal from the action of a
user of a fixture or appliance and
limits the temperature of the water
entering the cold -water piping to
104°F.
4 7
PL8]3
Water distribution iri bution system that pumps
❑Complies
water from a heated -water supply
❑Does Not
pipe back to the heated -water source
through a cold -water supply pipe is a
❑Not Observable
demand recirculation water system.
❑Not Applicable
Pumps within this system have
controls that start the pump upon
receiving a signal from the action of a
user of a fixture or appliance and
limits the temperature of the water
entering the cold -water piping to
104°F.
1 High Impact (Tier 1) 2 'Medium Impact (Tier 2) 3 Low Impact (Tier 3)
Project Title: Thomson Farms Apartments 3 Story Building
Data filename: CAUsers\Dwayne I5\Documents\COMcheck\Thomson Farms 3 Story.cck Report date: 06/26/18
Page 5 of 11
---..r,..,. .
j 1 'High Impact (Tier 1) _`2 !Medium Impact (Tier 2)__1 3 : Low Impact (Tier 3)_
Project Title: Thomson Farms Apartments 3 Story Building '
Data filename: C:\Users\Dwayne 15\Docurnents\C0MCheck\Th0mson Farms 3 story.cck
Report date: 06/26/18
Page 6 of 11
# Plumbing Rough -in inspection
& Req.ID 1
Complies? i Comments/Assumptions
C404.7 Water distribution system that pumps
❑Complies ` —
IPLB13 water from a heated -water supply
❑Does Not
pipe back to the heated -water source
I through a cold -water supply pipe is a
ONot Observable
demand recirculation water system.
❑Not Applicable
Pumps within this system have
controls that start the pump upon
receiving a signal from the action of a
user of a fixture or appliance and
limits the temperature of the water
entering the cold -water piping to
104°F.
Additinnwl
---..r,..,. .
j 1 'High Impact (Tier 1) _`2 !Medium Impact (Tier 2)__1 3 : Low Impact (Tier 3)_
Project Title: Thomson Farms Apartments 3 Story Building '
Data filename: C:\Users\Dwayne 15\Docurnents\C0MCheck\Th0mson Farms 3 story.cck
Report date: 06/26/18
Page 6 of 11
.ID Mechanical Rough -In Inspection I Complies?
& Req
C402.2.6 Thermally ineffective panel surfaces of ❑Complies
[ME41]3 sensible heating panels have ❑Does Not
insulation >= R-3.5.
C403,2.13 Unenclosed spaces that are heated
[ME71]2 use only radiant heat.
C403.2.3 HVAC equipment efficiency verified
[ME55]Z
C403.2.6. Demand control ventilation provided
1 for spaces >500 ft2 and >25
[ME5931 people/1000 ft2 occupant density and
served by systems with air side
economizer, auto modulating outside
air damper control, or design airflow
>3,000 cfm.
❑Not Observable
❑Not Applicable
❑Complies
❑Does Not
❑Not Observable
❑Not Applicable
❑Complies
❑Does Not
❑Not Observable
❑Not Applicable
❑Complies
[]Does Not
❑Not Observable
❑Not Applicable
Com ments/Assumptions
See the Mechanical Systems list for values.
C403.2,6.
2
Enclosed parking garage ventilation
❑Complies
[ME115]3
has automatic contaminant detection
and capacity to stage or modulate
❑Does Not
C403.2.8
[ME116]3
fans to 50% or less of design capacity.
[]Not Observable
-----------__.___
_
❑Not Applicable
C403.2.7
[ME57]1
Exhaust air energy recovery on
❑Complies
❑Does Not
systems meeting Table C403.2.7(1)
❑Does Not
C403.2.9
[ME60]2
and C403.2.7(2).
❑Complies
❑Does Not
t
❑Not Observable
❑Not Observable
_.-_. _
.._ _
_
❑Not Applicable
C403.2.8
[ME116]3
Kitchen e xhaust systems comply with
replacement air and conditioned
❑Complies
❑Does Not
❑Not Observable
supply air limitations, and satisfy hood
Air economizers provided where
rating requirements and maximum
❑Not Observable
❑Does Not
exhaust rate criteria.
❑Not Applicable
C403.2.9
[ME60]2
HVAC ducts and plenums insulated.
Where ducts or plenums are installed
❑Complies
❑Does Not
outside air during operation.
in or under a slab, verification may
need to occur during Foundation
❑Not Observable
.__^.Inspection.
❑Not Applicable
;C403.2.9 Ducts and plenums sealed based on ❑Complies
[ME10]1 static pressure and location, ❑Does Not
❑Not Observable
❑Not Applicable
C403.2.9. Ductwork operating >3 in. water ❑Complies
1.3 column requires air leakage testing. ❑Does Not
[ME11]3
C403,2.9.
1.3
[ME11]3
C403.3
[ME62]1
Ll High Impact (Tier 1) 2 1 Medium Impact (Tier 2) 3 Low Impact (Tier 3)
Project Title: Thomson Farms Apartments 3 Story Building
Data filename: C:\Users\Dwayne 15\Documents\COMcheck\Thom5on Farms 3 story.cck Report date: 06/26/18
Page 7 of 11
❑Not Observable
❑Not Applicable
Ductwork operating >3 in. water
❑Complies
column requires air leakage testing,
❑Does Not
❑Not Observable
Air economizers provided where
___❑NotApplicable
❑Complies __
required, meet the requirements for
design capacity, control signal,
❑Does Not
ventilation controls, high -limit shut-off, ❑Not Observable
integrated economizer control, and
❑Not Applicable
provide a means to relieve excess
outside air during operation.
Ll High Impact (Tier 1) 2 1 Medium Impact (Tier 2) 3 Low Impact (Tier 3)
Project Title: Thomson Farms Apartments 3 Story Building
Data filename: C:\Users\Dwayne 15\Documents\COMcheck\Thom5on Farms 3 story.cck Report date: 06/26/18
Page 7 of 11
Section
----- --
❑Complies
#
Mechanical Rough -In Inspection
& Reg -IDI__
C403.4.4.
Multiple zone VAV systems with DDC
6
of individual zone boxes have static
[ME110]3
pressure setpoint reset controls.
C403.4.4. Multiple zone VAV systems with DDC
6 of individual zone boxes have static
[ME110]3 pressure setpoint reset controls.
C404.2.1
[MElll]2
C408.2.2
1
[ME53]3
Complies?
❑Does Not
❑Not Observable
❑Not Applicable
❑Does Not
❑Not Observable
❑Not Applicable
Gas-fired water -heating equipment
----- --
❑Complies
installed in new buildings: where a
❑Does Not
singular piece of water -heating
equipment >= 1,000 kBtu/h serves
❑Not Observable
the entire building, thermal efficiency
❑Not Applicable
>= 90 Et. Where multiple pieces of
water -heating equipment serve the
building with combined rating >=
1,000 kBtu/h, the combined input -
capacity -weighted -average thermal
efficiency >= 90 Et. Exclude input
rating of equipment in individual
dwelling units and equipment <= lo0
kBtu/h.
Air outlets and zone terminal devices❑Complies
have means for air balancing.
ID Not
❑Not Observable
❑Not Applicable
Additional Comments/Assumptions:
Comments/Assumptions
See the Mechanical Systems list for values.
See the Mechanical Systems list for values.
1 High impact (Tier 1) 2 , M ie ud m Impact (Tier 2) 3 1 Low Impact(Tier 3)
Project Title: Thomson Farms Apartments 3 Story Building
Data filename: CAUsers\Dwayne 15\Documents\COMchecklTh0mson Farms 3 story.cck Report date: 06/26/18
Page 8 of 11
# Final Inspection
& Req,ID
1 Comp Ices?
i Comments/Assumptions
i❑Complies
C303.3,
Furnished O&M manuals for HVAC
T
C408.2.5.
3
systems within 90 days of system
❑Does Not
[FI8]3
acceptance.
❑Not Observable
❑Not Applicable
2.3
[FI41]3
❑Not Applicable
C403.2.2
HVAC systems and equipment
❑Complies
[F127]3
capacity does not exceed calculated
❑Does Not
❑Does Not
loads.
controls using automatic time clock or
❑Does Not
[FI1113
❑Not Observable
❑Does Not
_ _
❑Not Applicable
C403,2.4.
_
Heating and cooling to each zone is
❑Complies
1
[FI47]3
controlled by a thermostat control.
Minimum one humidity control device
❑goes Not
❑Complies
per installed
❑Not Observable
❑Does Not
humidification/dehumidification
❑Not Applicable
C403.2.4.
Heating and cooling to each zone is
❑Complies
1
[FI4713
controlled by a thermostat control.
Minimum one humidity control device
❑Does Not
C403.2.4.
per installed
❑Not Observable
1.3
[F12013
humidification/dehumidification
❑Not Applicable
2.3
[FI41]3
system.
❑Not Observable
C403.2.4.
Thermostatic controls have a 5 °F�❑Com
plies
1.2
(FI38J3
deadband.
❑Does Not
"
Systems include optimum start
❑Not Observable
2.3
[F141]3
controls.
❑Not Applicable
C403.2.4.
Temperature controls have setpoint
❑Complies
1.3
[F12013
overlap restrictions.
❑Does Not
2.3
[FI41]3
controls.
❑Not Observable
_..
_._
❑Not Applicable
C403.2.4.
Each zone equipped with setback
❑Complies - —
2
(FI39]3
controls using automatic time clock or
❑Does Not
[FI1113
programmable control system.
❑Does Not
systems.
❑Not Observable
_
__. .
❑Not Applicable
C403.2.4.
Automatic Controls: Setback to 55°F
❑Complies
2.1,
(heat) and 85°F (cool); 7 -day clock, 2-
❑Does Not
C403.2.4.
hour occupant override, 10 -hour
2.2
backup
❑Not Observable
[F140]3
❑Not Applicable
❑Not Applicable
403.2.4.
Systems include optimum start
❑Complies —
2.3
[F141]3
controls.
El Not
❑Not Observable
403.2.4.
Systems include optimum start
❑Not Applicable
❑Complies
2.3
[FI41]3
controls.
❑Does Not
❑Not Observable
_
❑Not Applicable
-404.3
Heat traps installed on supply and
❑Complies
[FI1113
discharge piping of non -circulating
❑Does Not
systems.
❑Not Observable
❑Not Applicable
C404.4
_
Allp'p' g " m insulated in accordance with ❑Complies -- -
[F125 ]2
section details and Table C403.2.10.
❑Does Not
❑Not Observable
❑Not Applicable
1 High Impact (Tier 1) 2 ;Medium Impact (Tier 2) 3 Low Impact (Tie---- r 3) —1
Project Title: Thomson Farms Apartments 3 Story Building
Report date: 06/26/18
Data filename: C:\Users\Dwayne 15\Documents\CC)MCheck\Thomson Farms 3 sto cck
ry• Page 9 of 11
# Final Inspection
& Req.ID 1 --.----
C408.2.1 Commissioning plan developed by
[FI28)1 registered design professional or
approved agency.
C408.2.3
1
[FI31j1
C408.2.3
2
[FI10)1
C408.2.3.
3
[F13211
C408.2.4
[F]29)1
C408.2.5
1
[F17]3
C408.2.5
3
[F14311
C408.2.5
4
[F130)1
HVAC equipment has been tested to
Complies?
❑Complies
❑Does Not
❑Not Observable
❑Not Applicable
Comments/Assumptions
ensure proper operation.❑
_O,'.'N1Does Not;
❑Not Observable
_
❑Not Applicable
HVAC control systems have been
❑Complies
tested to ensure proper operation,
es
❑DoNot
calibration and adjustment of controls.
❑Not Observable
— — — —
❑Not Applicable
Economizers have been tested to
❑Complies
ensure proper operation.
❑Does Not
❑Not Observable
❑Not Applicable
Preliminary commissioning report i
❑Complies
completed and certified by registered
❑Does Not
design professional or approved
agency.
❑Not Observable
—_. __ _ _
❑Not Applicable
_
Furnished HVAC as -built drawings
❑Complies -"
submitted within 90 days of system
❑Does Not
acceptance.
❑Not Observable
_
❑Not Applicable
An air and/or h dronic system
— — --
❑Comp—lie~
balancing report is provided for HVAC
❑Does Not
systems.
❑Not Observable
__ _
❑Not Applicable
_
Final commissioning report due to
❑Complies ---
building owner within 90 days of
❑Does Not
receipt of certificate of occupancy.
❑Not Observable
❑Not Aoolicable
Additional Comments/Assumptions:
1 High Impact (Tier 1) 2 'Medium Impact (Tier 2) 3 Low Impact (Tier 3)
Project Title: Thomson Farms Apartments 3 Story Building
Data filename: C:\Users\Dwayne 15\Documents\COMcIIeCk\Thomson Farms 3 story,cck Report date: 06/26/18
Page 10 of 11
Project Title: Thomson Farms Apartments 3 Story Building
Data filename: C:\Users\Dwayne 15\Documents\COMcheck\Thomson Farms 3 story.cck Report date: 06/26/18
Page 11 of 11