HomeMy WebLinkAboutRESCHECK - 18-00293 - 1236 Bond Ave - Tooth TimeREScheck Software Version 4,6.5
Compliance Certificate
Project Tooth Time
Energy Code:
2015 IECC
Location:
Rexburg, Idaho
Construction Type:
Single-family
Project Type:
New Construction
Conditioned Floor Area:
4,252 ft2
Glazing Area
25%u
Climate Zone:
6 (8693 HDD)
Permit Date:
Permit Number:
Construction Site: Owner/Agent:
1236 Bond Ave Designer/Contractor:
Rexburg, ID 83440 tared Kay
J. B. Kay Construction, LLC
950 Vista Ave
Rexburg, 1D 83440
208-716-2374
jared@jbkayconstruction.com
Compliance: 38.9% Better Than Code
Maximum UA: 612 Your UA: 374
The % Better or Worse Than Code Index reflects how close to compliance the house is based on code trade-off rules.
It DOES NOT provide an estimate of energy use or cost relative to a minimum -code home.
Envelope Assemblies
4,t5t 50.0 48.0 0.011 47
Wall 1: Wood Frame, 16" o.c. 2,520 22.0 22.0 0.024 45
Window 1: Vinyl/Fiberglass Frame:Double Pane with Low -E 550
0.290 160
Door 1: Glass
84 0.290 24
Basement Wall 1: Solid Concrete or Masonry
Wall height: 9.0' 4,252 19.0 19.0 0.023 98
Depth below grade: 9.0 -
Insulation depth: 9.0'
Compliance Statement. The proposed building design described here is consistent with the building plans, specifications, and other
calculations submitted with the permit application. The proposed building has been designed to meet the 2015 IECC requirements in
REScheck Version 4.6.5 and to comply with the mandatory requirements listed in the REScheck Inspection Checklist.
Name - Title Signature r)ate
Project Title: Tooth Time Report date: 05/31/18
Data filename: Untitled.rck Page 1 of 9
REScheck Software Version 4.6.5
Inspection Checklist
Energy Code: 2015 IECC
Requirements: 39.0% were addressed directly in the REScheck software
Text in the "Comments/Assumptions" column is provided by the user in the REScheck Requirements screen. For each
requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception
is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided.
Section
#
& Req.lb
Pre-inspection/Plan Review
Plans Verified
Field Verified
Value
Value Complies? Comments/Assumptions
103.1,
Construction drawings and
103.2
[PR1]1
documentation demonstrate
energy code compliance for the
❑Complies Requirement will be met.
❑Does Not
building envelope. Thermal
envelope represented on
❑Not Observable
construction documents.
❑Not Applicable
103.1,
Construction drawings and
103.2,
documentation demonstrate
❑Complies
403.7
[PR3]1
energy code compliance for
❑Does Not
lighting and mechanical systems.
Systems serving multiple
❑Not Observable
dwelling units must demonstrate
❑Not Applicable
compliance with the IECC
Commercial Provisions,
302.1,
403.7
Heating and cooling equipment is
sized per ACCA Manual S based
Heating:
Heatin
g' ❑Complies
[PR2]2
on loads calculated per ACCA
Btu/hr
Btu/hr ❑Does Not
Manual J or other methods
Cooling: Btu/hr
Cooling: ❑Not Observable
approved by the code official.
Btu/hr
❑Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1)
Project Title: Tooth Time
Data filename: Untitled.rck
2 Medium Impact (Tier 2) 3 Low Impact (Tier 3)
Report date: 05/31/18
Page 2 of 9
Section
A protective covering is installed
[FO11]2
to protect exposed exterior
#
Foundation Inspection Plans Verified
Field Verified
minimum of 6 in, below grade.
& Req.ID
Value
Value Complies?
Comments/Assumptions
402.1.1
[F04]1
Conditioned basement wall R-
insulation R -value. Where interior
R -❑Complies
See the Envelope Assemblies
insulation is used, verification R-
R- ❑Does Not
table for values.
may need to occur during
❑Not Observable
Insulation Inspection. Not
[]Not Applicable
required in warm -humid locations
in Climate Zone 3.
303.2
[F05]1
Conditioned basement wall
insulation installed per
❑Complies
Requirement will be met.
manufacturer's instructions.
❑Does Not
402.2.9 Conditioned basement wall
[F06]1 insulation depth of burial or
distance from top of wall.
303.2.1
A protective covering is installed
[FO11]2
to protect exposed exterior
insulation and extends a
minimum of 6 in, below grade.
403.9
Snow- and ice -melting system
[FO12]2
controls installed.
Additional Comments/Assumptions:
1 High Impact (Tier 1)
Project Title: Tooth Time
Data filename: Untitled.rck
❑Not Observable
❑Not Applicable
ft ft ❑Complies
❑Does Not
❑Not Observable
❑Not Applicable
❑Complies
❑Does Not
❑Not Observable
❑Not Applicable
❑Complies
❑Does Not
❑Not Observable
❑Not Applicable
See the Envelope Assemblies
table for values.
Requirement will be met.
2 Medium Impact (Tier 2) 3 Low Impact (Tier 3)
Report date: 05/31/18
Page 3 of 9
Section
# Framing / Rough -in Inspection Plans Verified Field Verified
& Req.ID Value Value
402.1.1, Glazing U -factor (area -weighted U-
402.3.1, average). 0-
402.3.3,
402.5
[FR2]1
303.1.3 U -factors of fenestration products
[FR4]1 are determined in accordance
with the NFRC test procedure or
taken from the default table.
402.4.1.1 Air barrier and thermal barrier
[FR23]1 installed per manufacturer's
instructions.
402.4.3 Fenestration that is not site built
[FR20]1 is listed and labeled as meeting
AAMA /WDMA/CSA 101/i.5.2/A440
or has infiltration rates per NFRC
400 that do not exceed code
limits.
402.4.5 IC -rated recessed lighting fixtures
[FR16]2 sealed at housing/interior finish
and labeled to indicate :52.0 cfm
leakage at 75 Pa.
403.3.1 Supply and return ducts in attics
[FR12]1 insulated >= R-8 where duct is
>= 3 inches in diameter and >_
R-6 where < 3 inches. Supply and
return ducts in other portions of
the building insulated >= R-6 for
diameter >= 3 inches and R-4.2
for < 3 inches in diameter.
403.3.5 Building cavities are not used as
[FR15]3 ducts or plenums.
403.4 HVAC piping conveying fluids R-
[FR17]z above 105 °F or chilled fluids R'
below 55 °F are insulated to 2oR-
3.
403.4.1 Protection of insulation on HVAC
[FR24]1 piping.
403.5.3 Hot water pipes are insulated to R-
[FR18]2 >_R-3. R
403.6 Automatic or gravity dampers are
[FR19]2 installed on all outdoor air
intakes and exhausts.
Additional Comments/Assumptions:
1 High Impact (Tier 1)
Complies?
❑Complies
❑Does Not
❑Not Observable
❑Not Applicable
❑Complies
❑Does Not
❑Not Observable
❑Not Applicable
❑Complies
❑Does Not
❑Not Observable
❑Not Applicable
❑Complies
❑Does Not
❑Not Observable
❑Not Applicable
❑Complies
❑Does Not
❑Not Observable
❑Not Applicable
❑Complies
❑Does Not
❑Not Observable
❑Not Applicable
❑Complies
❑Does Not
❑Not Observable
❑Not Applicable
❑Complies
❑Does Not
❑Not Observable
❑Not Applicable
❑Complies
❑Does Not
❑Not Observable
❑Not Applicable
❑Complies
❑Does Not
❑Not Observable
❑Not Applicable
❑Complies
❑Does Not
❑Not Observable
❑Not Applicable
Comments/Assumptions
See the Envelope Assemblies
table for values.
Requirement will be met.
Requirement will be met.
Requirement will be met.
Requirement will be met.
Requirement will be met.
2 Medium impact (Tier 2) 3 Low Impact (Tier 3)
Project Title: Tooth Time Report date: 05/31/18
Data filename: Untitled.rck Page 4 of 9
1 High Impact (Tier 1)
Project Title: Tooth Time
Data filename: Untitled.rck
2 Medium Impact (Tier 2) 3 Low Impact (Tier 3)
Report date: 05/31/18
Page 5 of 9
Section
#
Insulation Inspection
plans Verified Field Verified
& Req.ID
Value Value
Complies?
Comments/Assumptions
303.1
All installed insulation is labeled
[IN13]2
or the installed R -values
❑Complies
Requirement will be met.
provided.
❑Does Not
❑Nat Observable
402.1.1,
Wall insulation R -value. If this is a
R -❑Not
Applicable
402.2.5,
402.2.6
mass wall with at least 1/z of the
wall insulation on the wall
R
❑Wood El Wood
❑Complies
❑Does Not
See the Envelope Assemblies
table for values.
[IN3]1
exterior, the exterior insulation
Mass ❑ Mass
❑Not Observable
requirement applies (FR10).
Steel
❑ ❑ Steel
❑Not Applicable
303.2
[IN4]1
Wall insulation is installed per
manufacturer's instructions.
❑Complies
Requirement will be met.
❑Does Not
❑Not Observable
❑Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1) 2 Medium Impact (Tier 2) 3 Low Impact (Tier 3)
Project Title: Tooth Time Report date: 05/31/18
Data filename: Untitled.rck Page 6 of 9
Section
# Final Inspection Provisions
& Req.ID
402.1.1, Ceiling insulation R -value.
402.2.1,
402.2.2,
402.2.6
[FI1]1
303.1.1.1,
Ceiling insulation installed per
303.2
manufacturer's instructions.
[FI2]1
Blown insulation marked every
300 ft2.
402.2.3
Vented attics with air permeable
[F122]2
insulation include baffle adjacent
to soffit and eave vents that
403.3.3
extends over insulation.
402.2.4
Attic access hatch and door
[FI311
insulation >R -value of the
adjacent assembly.
402.4.1.2 Blower door test @ 50 Pa. <=5
[FI17]1 ach in Climate Zones 1-2, and
<=3 ach in Climate Zones 3-8,
403.3.4
Duct tightness test result of <=4
[FI4]1
cfm/100 ft2 across the system or
<=3 cfm/100 ft2 without air
handler @ 25 Pa. For rough -in
tests, verification may need to
occur during Framing Inspection.
403.3.3
Ducts are pressure tested to
[FI27]1
determine air leakage with
either: Rough -in test: Total
leakage measured with a
pressure differential of 0.1 inch
w.g, across the system including
the manufacturer's air handler
enclosure if installed at time of
test. Postconstruction test: Total
leakage measured with a
pressure differential of 0.1 inch
w.g. across the entire system
including the manufacturer's air
handler enclosure.
403.3.2.1
Air handler leakage designated
[FI24]1
by manufacturer at <=2% of
design air flow.
403.1.1 Programmable thermostats
[F19]2 installed for control of primary
heating and cooling systems and
initially set by manufacturer to
code specifications.
403.1.2 Heat pump thermostat installed
[FI10]2 on heat pumps.
403.5.1 Circulating service hot water
[FI 11]2 systems have automatic or
accessible manual controls.
1 High Impact (Tier 1)
Project Title: Tooth Time
Data filename: Untitled.rck
Pians Verified
Value
❑ Wood
❑ Steel
R-
ACH 50 =
cfm/100
ft2
cfm/100
ft2
Field Verified
Value
R-
E] Wood
❑ Steel
Lla
ACH 50 =
cfm/100
ft2
cfm/100
ft2
Complies?
❑Complies
❑Does Not
❑Not Observable
❑Not Applicable
❑Complies
❑Does Not
❑Not Observable
❑Not Applicable
❑Complies
❑Does Not
❑Not Observable
❑Not Applicable
❑Complies
❑Does Not
❑Not Observable
❑Not Applicable
❑Complies
❑Does Not
❑Not Observable
❑Not Applicable
❑Complies
❑Does Not
❑Not Observable
❑Not Applicable
❑Complies
❑Does Not
❑Not Observable
❑Not Applicable
❑Complies
❑Does Not
❑Not Observable
❑Not Applicable
❑Complies
❑Does Not
❑Not Observable
❑Not Applicable
❑Complies
❑Does Not
❑Not Observable
❑Not Applicable
❑Complies
❑Does Not
❑Not Observable
❑Not Applicable
Com ments/Assumptions
See the Envelope Assemblies
table for values.
Requirement will be met.
Requirement will be met.
Requirement will be met.
Requirement will be met,
2 Medium Impact (Tier 2) 3 Low Impact (Tier 3)
Report date: 05/31/18
Page 7 of 9
Section
#
Final inspection Provisions
& Req.ID
403.6.1
All mechanical ventilation system
[F125 12
fans not part of tested and listed
HVAC equipment meet efficacy
and air flow limits.
403.2
Hot water boilers supplying heat
[FI26]2
through one- or two -pipe heating
systems have outdoor setback
control to lower boiler water
temperature based on outdoor
temperature.
403.5.1.1 Heated water circulation systems
[FI28]2
have a circulation pump. The
system return pipe is a dedicated
return pipe or a cold water supply
pipe. Gravity and thermos -
syphon circulation systems are
not present. Controls for
circulating hot water system
Pumps start the pump with signal
for hot water demand within the
occupancy. Controls
automatically turn off the pump
when water is in circulation loop
is at set -point temperature and
no demand for hot water exists.
403.5.1.2
Electric heat trace systems
[FI29]2
comply with IEEE 515.1 or UL
515. Controls automatically
adjust the energy input to the
heat tracing to maintain the
desired water temperature in the
piping.
403.5.2
Water distribution systems that
[F130]2
have recirculation pumps that
pump water from a heated water
supply pipe back to the heated
water source through a cold
water supply pipe have a
demand recirculation water
system. Pumps have controls
that manage operation of the
pump and limit the temperature
of the water entering the cold
water piping to 104°F.
403.5.4
Drain water heat recovery units
[FI31]2
tested in accordance with CSA
855.1. Potable water -side
pressure loss of drain water heat
recovery units < 3 psi for
individual units connected to one
or two showers. Potable water-
side pressure loss of drain water
heat recovery units < 2 psi for
individual units connected to
three or more showers.
404.1
75% of lamps in permanent
[F16]1
fixtures or 75% of permanent
fixtures have high efficacy lamps.
Does not apply to low -voltage
lighting.
404.1.1
Fuel gas lighting systems have
[F123]3
no continuous pilot light.
1 High Impact (Tier 1)
Project Title: Tooth Time
Data filename: Untitled.rck
Plans Verified Field Verified
Value Value Complies?
❑Complies
[]Does Not
❑Not Observable
❑Not Applicable
❑Complies
❑Does Not
[]Not Observable
❑Not Applicable
❑Complies
[]Does Not
❑Not Observable
❑Not Applicable
❑Complies
❑Does Not
❑Not Observable
❑Not Applicable
❑Complies
❑Does Not
❑Not Observable
❑Not Applicable
❑Complies
❑Does Not
❑Not Observable
❑Not Applicable
❑Complies
❑Does Not
❑Not Observable
❑Not Applicable
❑Complies
❑Does Not
❑Not Observable
❑Not Applicable
2 Medium Impact (Tier 2) 3 Low Impact (Tier 3)
Comments/Assumptions
Report date: 05/31/18
Page 8 of 9
—serhan----
#
Final Inspection Provisions
plans Verified Field Verified
& Req.lD
Value Value Complies?
401.3
Compliance certificate posted.
--
[FI7]2
❑Complies
❑Does Not
❑Not Observable
303.3
Manufacturer manuals for
❑Not Applicable
[FI18]3
mechanical and water heating
❑Complies
systems have been provided.
f1Does Not
❑Not Observable
❑Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1)
Project Title: Tooth Time
Data filename: Untitled.rck
Comments/Assumptions
Requirement will be met.
2 Medium Impact (Tier 2) 3 Low Impact (Tier 3)
Report date: 05/31/18
Page 9 of 9
2015 iECC Energy
Efficiency Certificate
Above -Grade Wall
".00
Below -Grade Wall
38.00
Floor
0.00
Ceiling / Roof
98.00
Ductwork (unconditioned spaces):
Window
0.29
Door
0.29
, MR
Heating System:
Cooling System:
Water Heater:
Name: Date:
Comments