HomeMy WebLinkAboutTEST - 13-00337 - 125 E 2nd S - Windsor Manor, LLC - Site PlanHARPER-LEAVITT ENGINEERING. INC. PROFESSIONAL ENGINEERS & LAND SURVEYORS 985 N. Capital Ave. 800 W. Judicial St. Idaho Falls, ID 83405 Blackfoot, ID 83221 (208) 524-0212 (208) 785-297 ISPWC Water Line Pressure Test Location: Windsor Apartments Rexburg Type of Pipe: PVC Job No.: 2013.2654.1 Date: 20 Dec, 201; Pipe Location Dia. In. Length Ft. Req. Press PSI Gal. Per Hr. Allowed Gal. Meas. P / F Entire System 6 " 662 ft. 150 .78 Fail Comments: System continued to drop pressure through three attempts. Inspector: FSvkes HARPER-LEAVITT ENGINEERING, INC. PROFESSIONAL ENGINEERS & LAND SURVEYORS 985 N. Capital Ave. 800 W. Judicial St, Idaho Falls, ID 83405 Blackfoot, ID 83221 (208)524-0212 (208)785-2977 iSPWC Water Line Pressure Test Location: Windsor Apartments Rexbu Type of Pipe: PVC Job No.: 2013.2654.1 Date: 23 Dec, 2013 Pipe Location Dia. In. Length Ft. Req. Press PSI Gal. Per Hr. Allowed Gal. Meas. P / F Entire System 6 " 662 ft. 150 .78 .08 Pass Comments: Retest of failed 20 Dec. Test. Inspector: FSvkes