PLAN REVIEW FOR FIRE SPRINKLER SYSTEMS
PLANS RECEIVED: February 12, 2017 APPROVED: February 20, 2018
REVIEWED BY: Javier Cervantes, ISFM Fire Plan Reviewer
PROJECT: Valley Wide Cooperation
STREET ADDRESS: 1175 W. Main Street CITY: Rexburg
AHJ: Madison Fire Department
SUBMITTAL TYPE: Tenant Improvement SYSTEM TYPE: NFPA 13
Wet & Dry
HEAD COUNT: 200 TOTAL SYSTEMS: 3 AREA SQUARE FOOTAGE: 24,487
OCCUPANCY CLASSIFICATION: Group M CONSTRUCTION TYPE: III B
SCOPE OF WORK: Existing building will be retrofitted with the new sprinkler system installed in
the 8,000 square foot addition.
SPRINKLER CONTRACTOR: Phoenix Fire Protection
4130 Airport Road
Nampa, ID 83687
IDAHO LICENSE: FPSC-108
CONTACT NAME: Teri Cruikshank
teri@phoenixfp.com
PHONE NO: (208) 468-9115
SYSTEM DESIGNED BY: Damion Snodgrass
damion@phoenixfp.com
PHONE NO: (208) 258-5100
PLAN REVIEW COMMENTS:
Approved with the following comments:
1. Automatic air maintenance required. (NFPA 13, 7.2.6.6)
2. Air Venting required. (NFPA 13, 7.1.5)
3. Working Plans per NFPA 13, 23.1.3(22)
Approval of shop drawings is not intended to imply waiver or modification of any
requirements of the Idaho State Statutes or Rules, International Fire Code, NFPA
Standards or any other applicable criteria.
It is acknowledged that backflow preventer is installed per the demand of the local
water purveyer. The State Fire Marshal’s Office and its personnel does not take any
responsibility for the back flow device.