HomeMy WebLinkAboutSTRUCTURAL CALCULATIONS - 18-00253 - 441 Twisted Willow - Solar PanelsSnap Nrack- 01a, ounting So ut ons 775 Fiero La ne, Suite 200 San Luis Obispo, CA 93401 Email: contact@snapnrack.com Phone Number: (877) 732-2860 SnapNrack Series 100 Roof Mount System COVER LETTER The loading criteria used in this report is from ASCE 7-10. For codes that reference ASCE 7-05, Appendix A is provided to convert the wind speeds in ASCE 7-05 to the wind speeds used in this report. Instructions for this conversion are provided in Appendix A. This report covers wind speeds (Vuh) to 190 MPH, ground snow to 120 PSF, building heights to 60 feet, and tilt angles to 60 degrees. The following codes are covered in this report: • IBC2015 • mc2012 • IBC 2009 • IBC2006 The mounting system structural submittal package shall consist of the following: • Pages 1-17 of the report (this includes this cover letter). • Applicable page from the following: o Cl -Cl5 for Oto 30 ft. Mean Roof Height an4 6063 alloy rail o Cl 7 -C32 for 31 to 60 ft. Mean Roof Height and 6063 alloy rail o C33 -C48 for Oto 30 ft. Mean Roof Height and 6005 alloy rail o C49 -C64 for 31 to 60 ft. Mean Roof Height and 6005 alloy rail • Appendix A (if applicable). • The applicable installation details (listed on page 17 of this report). This report provides structural engineering calculations and installation criteria for the mounting system only. It does not certify the capacity of the supporting members. The capacity of the sup- porting structure is to be certified by the licensed professional responsible for the building's structural certification. Please contact SnapNrack at (877) 732-2860, or Contact@snapnrack.com, for questions regard- ing this report. Norman Scheel , PE , SE Fellow ASCE Fellow SEAOC LEED AP BD+C , LEED AP HOMES E-mail : info@nsse.com Series 100 Structural Report and Calculations NSSE 5022 Sunrise Boulevard Fair Oaks CA 95628 (916) 536-9585 Page 2 Structural Report and Calculations Series 100 Roof Mount For SnapNrack 775 Fiero Lane, Suite 200 San Luis Obispo, CA 93401 Prepared By Norman Scheel Structural Engineer 5022 Sunrise Boulevard Fair Oaks, CA 95628 (916) 536-9585 July 6, 2016 Series 100 Structural Report and Calculations NSSE 5022 Sunrise Boulevard Fair Oaks CA 95628 (916) 536-9585 Page 3 Table of Contents Section Page Cover Letter 1 Summary Report 2 to 17 Building Department Support Calculations Calculations 0 to 30 ft. Mean Roof Height (6063 Rail) C1 to C15 Wind Calculations Velocity Pressures & MFRS C1 Component and Cladding C3 Seismic Calculations C7 Snow Loads C8 Rail Properties C9 65” PV Panel Connection to Rail C10 78” PV Panel Connection to Rail C11 Lag Bolt Connection to Roof C12 Rail Span Chart Tilt Angle 0-19 degrees C13 Rail Span Chart Tilt Angle 20-36 degrees C14 Rail Span Chart Tilt Angle 37-45 degrees C15 Rail Span Chart Tilt Angle 45-60 degrees C16 Building Department Support Calculations Calculations 31 to 60 ft. Mean Roof Height (6063 Rail) C17 to C32 Wind Calculations Velocity Pressures & MFRS C17 Component and Cladding C19 Seismic Calculations C23 Snow Loads C24 Rail Properties C25 65” PV Panel Connection to Rail C26 78” PV Panel Connection to Rail C27 Lag Bolt Connection to Roof C28 Rail Span Chart Tilt Angle 0-19 degrees C29 Rail Span Chart Tilt Angle 20-36 degrees C30 Rail Span Chart Tilt Angle 37-45 degrees C31 Rail Span Chart Tilt Angle 45-60 degrees C32 Series 100 Structural Report and Calculations NSSE 5022 Sunrise Boulevard Fair Oaks CA 95628 (916) 536-9585 Page 4 Building Department Support Calculations Calculations 0 to 30 ft. Mean Roof Height (6005 Rail) C33 to C48 Wind Calculations Velocity Pressures & MFRS C33 Component and Cladding C35 Seismic Calculations C39 Snow Loads C40 Rail Properties C41 65” PV Panel Connection to Rail C42 78” PV Panel Connection to Rail C43 Lag Bolt Connection to Roof C44 Rail Span Chart Tilt Angle 0-19 degrees C45 Rail Span Chart Tilt Angle 20-36 degrees C46 Rail Span Chart Tilt Angle 37-45 degrees C47 Rail Span Chart Tilt Angle 45-60 degrees C48 Building Department Support Calculations Calculations 31 to 60 ft. Mean Roof Height (6005 Rail) C49 to C64 Wind Calculations Velocity Pressures & MFRS C49 Component and Cladding C51 Seismic Calculations C55 Snow Loads C56 Rail Properties C57 65” PV Panel Connection to Rail C58 78” PV Panel Connection to Rail C59 Lag Bolt Connection to Roof C60 Rail Span Chart Tilt Angle 0-19 degrees C61 Rail Span Chart Tilt Angle 20-36 degrees C62 Rail Span Chart Tilt Angle 37-45 degrees C63 Rail Span Chart Tilt Angle 45-60 degrees C64 Appendix: ASCE-2010 to 2005 Conversion Sheet A1 Series 100 Structural Report and Calculations NSSE 5022 Sunrise Boulevard Fair Oaks CA 95628 (916) 536-9585 Page 5 Introduction This report describes, illustrates, and explains the Structural Calculation Packet for SnapNrack’s Series 100 Mounting System, dated 7/6/2016. The calculations have been performed in accordance with the codes referenced in the cover letter. The racking system has been designed to withstand code-prescribed forces due to its own weight, the weight of the solar panels, the snow loads, and both the wind and seismic forces. Rail Spans This report covers two different material options for the system rails. Although they are both aluminum, one rail option uses a 6063 alloy (25 ksi yield) and the other uses a 6005 alloy (35 ksi yield). Despite having different yield strengths, both types of rails support the PV panels. As for the rails themselves, they are supported by mounting hardware which attaches them to the roof structure with spans that are expressed in inches. Refer to the tables below for rail spans under varying conditions of rail alloy and roof height. Shaded cells require an edge zone adjustment (see details following charts). Notes for Tables 1A thru 2H 1. Determine the mean roof height, tilt angle, and rail alloy (if you are unsure, use the 6063 alloy values). For mean roof heights less than 30 feet, use Table 1A/2A for tilt angles less than 19 degrees, Table 1B/2B for tilt angles between 20 and 36 degrees, Table 1C/2C for tilt angles between 37 and 45 degrees, and Table 1D/2D for tilt angles between 46 and 60 degrees. For mean roof heights between 31 and 60 feet use Table 1E/2E for tilt angles less than 19 degrees, Table 1F/2F for tilt angles between 20 and 36 degrees, Table 1G/2G for tilt angles between 37 and 45 degrees, and Table 1H/2H for tilt angles between 46 and 60 degrees. 2. Determine the wind and snow load for the project site from the building department. Make certain to use 2015 IBC wind loads. Locate the wind load in the table across top rows and the snow load down the left columns to find corresponding maximum rail span. 3. For snow loads, column Pg equals the ground snow. 4. Shaded cells require application of an edge zone adjustment (details to follow). Series 100 Structural Report and Calculations NSSE 5022 Sunrise Boulevard Fair Oaks CA 95628 (916) 536-9585 Page 6 6063 Alloy Rail Tables 0-30 ft. Roof Height Table 1A: Rail Spans (in) for Roof Slopes and Tilt Angles 0˚ to 19˚   6063 Alloy Wind Load G r o u n d S n o w L o a d ( p s f ) Vult 110 115 120 125 130 135 140 145 150 155 160 170 180 190 qh 15.5 16.9 18.4 20.0 21.6 23.3 25.1 26.9 28.8 30.7 32.8 37.0 41.5 46.2 Pg Ps -10.7 -11.7 -12.7 -13.8 -14.9 -16.1 -17.3 -18.6 -19.9 -21.2 -22.6 -25.5 -28.6 -31.9 0 0 116 110 104 99 95 91 87 83 80 77 75 70 65 62 10 8 114 110 104 99 95 91 87 83 80 77 75 70 65 62 20 15 89 89 89 89 89 89 87 83 80 77 75 70 65 62 30 23 75 75 75 75 75 75 75 75 75 75 75 70 65 62 40 31 66 66 66 66 66 66 66 66 66 66 66 66 65 62 50 39 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 46 55 55 55 55 55 55 55 55 55 55 55 55 55 55 70 54 51 51 51 51 51 51 51 51 51 51 51 51 51 51 80 62 48 48 48 48 48 48 48 48 48 48 48 48 48 48 100 77 43 43 43 43 43 43 43 43 43 43 43 43 43 43 120 92 40 40 40 40 40 40 40 40 40 40 40 40 40 40 0-30 ft. Roof Height Table 1B: Rail Spans (in) for Roof Slopes and Tilt Angles 20˚ to 36˚   6063 Alloy Wind Load Gr o u n d S n o w L o a d ( p s f ) Vult 110 115 120 125 130 135 140 145 150 155 160 170 180 190 qh 15.5 16.9 18.4 20.0 21.6 23.3 25.1 26.9 28.8 30.7 32.8 37.0 41.5 46.2 Pg Ps -7.0 -7.6 -8.3 -9.0 -9.7 -10.5 -11.3 -12.1 -13.0 -13.8 -14.7 -16.6 -18.7 -20.8 0 0 120 120 120 120 120 118 112 108 103 99 95 89 83 78 10 8 112 111 110 109 108 107 105 104 103 99 95 89 83 78 20 15 89 89 89 89 89 89 88 88 87 87 86 85 83 78 30 23 75 75 75 75 75 75 75 75 75 75 75 75 74 73 40 31 66 66 66 66 66 66 66 66 66 66 66 66 66 66 50 39 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 46 55 55 55 55 55 55 55 55 55 55 55 55 55 55 70 54 51 51 51 51 51 51 51 51 51 51 51 51 51 51 80 62 48 48 48 48 48 48 48 48 48 48 48 48 48 48 100 77 43 43 43 43 43 43 43 43 43 43 43 43 43 43 120 92 40 40 40 40 40 40 40 40 40 40 40 40 40 40   Series 100 Structural Report and Calculations NSSE 5022 Sunrise Boulevard Fair Oaks CA 95628 (916) 536-9585 Page 7 0-30 ft. Roof Height   Table 1C: Rail Spans (in) for Roof Slopes and Tilt Angles 37˚ to 45˚   6063 Alloy Wind Load Gr o u n d S n o w L o a d ( p s f ) Vult 110 115 120 125 130 135 140 145 150 155 160 170 180 190 qh 15.5 16.9 18.4 20.0 21.6 23.3 25.1 26.9 28.8 30.7 32.8 37.0 41.5 46.2 Pg Ps -6.7 -7.3 -7.9 -8.6 -9.3 -10.0 -10.8 -11.6 -12.4 -13.2 -14.1 -15.9 -17.8 -19.9 0 0 120 120 120 120 120 120 116 111 106 102 98 91 85 80 10 8 112 111 110 109 108 107 105 104 103 102 98 91 85 80 20 15 89 89 89 89 89 89 88 88 87 87 86 85 83 80 30 23 75 75 75 75 75 75 75 75 75 75 75 75 74 73 40 31 66 66 66 66 66 66 66 66 66 66 66 66 66 66 50 39 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 46 55 55 55 55 55 55 55 55 55 55 55 55 55 55 70 54 51 51 51 51 51 51 51 51 51 51 51 51 51 51 80 62 48 48 48 48 48 48 48 48 48 48 48 48 48 48 100 77 43 43 43 43 43 43 43 43 43 43 43 43 43 43 120 92 40 40 40 40 40 40 40 40 40 40 40 40 40 40 0-30 ft. Roof Height Table 1D: Rail Spans (in) for Roof Slopes and Tilt Angles 46˚ to 60˚   6063 Alloy Wind Load Gr o u n d S n o w L o a d ( p s f ) Vult 110 115 120 125 130 135 140 145 150 155 160 170 180 190 qh 15.5 16.9 18.4 20.0 21.6 23.3 25.1 26.9 28.8 30.7 32.8 37.0 41.5 46.2 Pg Ps -6.3 -6.9 -7.6 -8.2 -8.9 -9.6 -10.3 -11.0 -11.8 -12.6 -13.4 -15.2 -17.0 -18.9 0 0 120 120 120 120 118 115 113 110 107 105 101 94 88 82 10 8 106 105 104 102 101 100 98 97 96 94 93 90 88 82 20 15 89 88 87 87 86 85 84 83 82 82 81 79 77 76 30 23 75 75 75 75 75 75 75 74 74 73 72 71 70 69 40 31 66 66 66 66 66 66 66 66 66 66 66 65 64 63 50 39 60 60 60 60 60 60 60 60 60 60 60 60 60 59 60 46 55 55 55 55 55 55 55 55 55 55 55 55 55 55 70 54 51 51 51 51 51 51 51 51 51 51 51 51 51 51 80 62 48 48 48 48 48 48 48 48 48 48 48 48 48 48 100 77 43 43 43 43 43 43 43 43 43 43 43 43 43 43 120 92 40 40 40 40 40 40 40 40 40 40 40 40 40 40 Series 100 Structural Report and Calculations NSSE 5022 Sunrise Boulevard Fair Oaks CA 95628 (916) 536-9585 Page 8 31-60 ft. Roof Height   Table 1E: Rail Spans (in) for Roof Slopes and Tilt Angles 0˚ to 19˚   6063 Alloy  Wind Load Gr o u n d S n o w L o a d ( p s f ) Vult 110 115 120 125 130 135 140 145 150 155 160 170 180 190 qh 17.9 19.5 21.2 23.1 24.9 26.9 28.9 31.0 33.2 35.4 37.8 42.6 47.8 53.3 Pg Ps -12.3 -13.5 -14.7 -15.9 -17.2 -18.6 -20.0 -21.4 -22.9 -24.5 -26.1 -29.4 -33.0 -36.7 0 0 106 101 96 91 87 83 80 77 74 71 69 64 61 57 10 8 106 101 96 91 87 83 80 77 74 71 69 64 61 57 20 15 89 89 89 89 87 83 80 77 74 71 69 64 61 57 30 23 75 75 75 75 75 75 75 75 74 71 69 64 61 57 40 31 66 66 66 66 66 66 66 66 66 66 66 64 61 57 50 39 60 60 60 60 60 60 60 60 60 60 60 60 60 57 60 46 55 55 55 55 55 55 55 55 55 55 55 55 55 55 70 54 51 51 51 51 51 51 51 51 51 51 51 51 51 51 80 62 48 48 48 48 48 48 48 48 48 48 48 48 48 48 100 77 43 43 43 43 43 43 43 43 43 43 43 43 43 43 120 92 40 40 40 40 40 40 40 40 40 40 40 40 40 40 31-60 ft. Roof Height    Table 1F: Rail Spans (in) for Roof Slopes and Tilt Angles 20˚ to 36˚   6063 Alloy Wind Load Gr o u n d S n o w L o a d ( p s f ) Vult 110 115 120 125 130 135 140 145 150 155 160 170 180 190 qh 17.9 19.5 21.2 23.1 24.9 26.9 28.9 31.0 33.2 35.4 37.8 42.6 47.8 53.3 Pg Ps -8.0 -8.8 -9.6 -10.4 -11.2 -12.1 -13.0 -14.0 -14.9 -16.0 -17.0 -19.2 -21.5 -24.0 0 0 120 120 120 119 113 108 103 99 95 91 88 82 77 72 10 8 110 109 108 107 106 104 103 99 95 91 88 82 77 72 20 15 89 89 89 89 89 88 87 86 86 85 84 82 77 72 30 23 75 75 75 75 75 75 75 75 75 75 75 74 73 72 40 31 66 66 66 66 66 66 66 66 66 66 66 66 66 66 50 39 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 46 55 55 55 55 55 55 55 55 55 55 55 55 55 55 70 54 51 51 51 51 51 51 51 51 51 51 51 51 51 51 80 62 48 48 48 48 48 48 48 48 48 48 48 48 48 48 100 77 43 43 43 43 43 43 43 43 43 43 43 43 43 43 120 92 40 40 40 40 40 40 40 40 40 40 40 40 40 40   Series 100 Structural Report and Calculations NSSE 5022 Sunrise Boulevard Fair Oaks CA 95628 (916) 536-9585 Page 9 31-60 ft. Roof Height   Table 1G: Rail Spans (in) for Roof Slopes and Tilt Angles 37˚ to 45˚   6063 Alloy Wind Load Gr o u n d S n o w L o a d ( p s f ) Vult 110 115 120 125 130 135 140 145 150 155 160 170 180 190 qh 17.9 19.5 21.2 23.1 24.9 26.9 28.9 31.0 33.2 35.4 37.8 42.6 47.8 53.3 Pg Ps -7.7 -8.4 -9.1 -9.9 -10.7 -11.6 -12.4 -13.3 -14.3 -15.2 -16.2 -18.3 -20.6 -22.9 0 0 120 120 120 120 116 111 106 101 97 93 90 84 79 74 10 8 110 109 108 107 106 104 103 101 97 93 90 84 79 74 20 15 89 89 89 89 89 88 87 86 86 85 84 83 79 74 30 23 75 75 75 75 75 75 75 75 75 75 75 74 73 72 40 31 66 66 66 66 66 66 66 66 66 66 66 66 66 66 50 39 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 46 55 55 55 55 55 55 55 55 55 55 55 55 55 55 70 54 51 51 51 51 51 51 51 51 51 51 51 51 51 51 80 62 48 48 48 48 48 48 48 48 48 48 48 48 48 48 100 77 43 43 43 43 43 43 43 43 43 43 43 43 43 43 120 92 40 40 40 40 40 40 40 40 40 40 40 40 40 40 31-60 ft. Roof Height Table 1H: Rail Spans (in) for Roof Slopes and Tilt Angles 46˚ to 60˚   6063 Alloy  Wind Load Gr o u n d S n o w L o a d ( p s f ) Vult 110 115 120 125 130 135 140 145 150 155 160 170 180 190 qh 17.9 19.5 21.2 23.1 24.9 26.9 28.9 31.0 33.2 35.4 37.8 42.6 47.8 53.3 Pg Ps -7.3 -8.0 -8.7 -9.5 -10.2 -11.0 -11.9 -12.7 -13.6 -14.5 -15.5 -17.5 -19.6 -21.8 0 0 120 120 119 116 113 110 107 104 100 96 93 86 81 76 10 8 104 103 101 100 98 97 96 94 93 91 90 86 81 76 20 15 88 87 86 85 84 83 82 81 81 80 79 77 75 73 30 23 75 75 75 75 75 74 73 73 72 72 71 70 68 67 40 31 66 66 66 66 66 66 66 66 66 65 65 64 63 62 50 39 60 60 60 60 60 60 60 60 60 60 60 60 59 58 60 46 55 55 55 55 55 55 55 55 55 55 55 55 55 54 70 54 51 51 51 51 51 51 51 51 51 51 51 51 51 51 80 62 48 48 48 48 48 48 48 48 48 48 48 48 48 48 100 77 43 43 43 43 43 43 43 43 43 43 43 43 43 43 120 92 40 40 40 40 40 40 40 40 40 40 40 40 40 40 Series 100 Structural Report and Calculations NSSE 5022 Sunrise Boulevard Fair Oaks CA 95628 (916) 536-9585 Page 10 6005 Alloy Rail Tables 0-30 ft. Roof Height Table 2A: Rail Spans (in) for Roof Slopes and Tilt Angles 0˚ to 19˚  6005 Alloy  Wind Load Gr o u n d S n o w L o a d ( p s f ) Vult 110 115 120 125 130 135 140 145 150 155 160 170 180 190 qh 15.5 16.9 18.4 20.0 21.6 23.3 25.1 26.9 28.8 30.7 32.8 37.0 41.5 46.2 Pg Ps -10.7 -11.7 -12.7 -13.8 -14.9 -16.1 -17.3 -18.6 -19.9 -21.2 -22.6 -25.5 -28.6 -31.9 0 0 140 132 125 119 114 109 104 100 96 93 89 84 79 74 10 8 137 132 125 119 114 109 104 100 96 93 89 84 79 74 20 15 106 106 106 106 106 106 104 100 96 93 89 84 79 74 30 23 90 90 90 90 90 90 90 90 90 90 89 84 79 74 40 31 79 79 79 79 79 79 79 79 79 79 79 79 79 74 50 39 72 72 72 72 72 72 72 72 72 72 72 72 72 72 60 46 66 66 66 66 66 66 66 66 66 66 66 66 66 66 70 54 62 62 62 62 62 62 62 62 62 62 62 62 62 62 80 62 58 58 58 58 58 58 58 58 58 58 58 58 58 58 100 77 52 52 52 52 52 52 52 52 52 52 52 52 52 52 120 92 48 48 48 48 48 48 48 48 48 48 48 48 48 48 0-30 ft. Roof Height   Table 2B: Rail Spans (in) for Roof Slopes and Tilt Angles 20˚ to 36˚   6005 Alloy  Wind Load Gr o u n d S n o w L o a d ( p s f ) Vult 110 115 120 125 130 135 140 145 150 155 160 170 180 190 qh 15.5 16.9 18.4 20.0 21.6 23.3 25.1 26.9 28.8 30.7 32.8 37.0 41.5 46.2 Pg Ps -7.0 -7.6 -8.3 -9.0 -9.7 -10.5 -11.3 -12.1 -13.0 -13.8 -14.7 -16.6 -18.7 -20.8 0 0 144 144 144 144 144 141 135 129 124 119 114 107 100 94 10 8 134 133 132 130 129 128 127 125 124 119 114 107 100 94 20 15 106 106 106 106 106 106 106 105 105 104 103 101 100 94 30 23 90 90 90 90 90 90 90 90 90 90 90 90 89 88 40 31 79 79 79 79 79 79 79 79 79 79 79 79 79 79 50 39 72 72 72 72 72 72 72 72 72 72 72 72 72 72 60 46 66 66 66 66 66 66 66 66 66 66 66 66 66 66 70 54 62 62 62 62 62 62 62 62 62 62 62 62 62 62 80 62 58 58 58 58 58 58 58 58 58 58 58 58 58 58 100 77 52 52 52 52 52 52 52 52 52 52 52 52 52 52 120 92 48 48 48 48 48 48 48 48 48 48 48 48 48 48 Series 100 Structural Report and Calculations NSSE 5022 Sunrise Boulevard Fair Oaks CA 95628 (916) 536-9585 Page 11 0-30 ft. Roof Height Table 2C: Rail Spans (in) for Roof Slopes and Tilt Angles 37˚ to 45˚   6005 Alloy Wind Load Gr o u n d S n o w L o a d ( p s f ) Vult 110 115 120 125 130 135 140 145 150 155 160 170 180 190 qh 15.5 16.9 18.4 20.0 21.6 23.3 25.1 26.9 28.8 30.7 32.8 37.0 41.5 46.2 Pg Ps -6.7 -7.3 -7.9 -8.6 -9.3 -10.0 -10.8 -11.6 -12.4 -13.2 -14.1 -15.9 -17.8 -19.9 0 0 144 144 144 144 144 144 139 133 127 122 118 109 102 96 10 8 134 133 132 130 129 128 127 125 124 122 118 109 102 96 20 15 106 106 106 106 106 106 106 105 105 104 103 101 100 96 30 23 90 90 90 90 90 90 90 90 90 90 90 90 89 88 40 31 79 79 79 79 79 79 79 79 79 79 79 79 79 79 50 39 72 72 72 72 72 72 72 72 72 72 72 72 72 72 60 46 66 66 66 66 66 66 66 66 66 66 66 66 66 66 70 54 62 62 62 62 62 62 62 62 62 62 62 62 62 62 80 62 58 58 58 58 58 58 58 58 58 58 58 58 58 58 100 77 52 52 52 52 52 52 52 52 52 52 52 52 52 52 120 92 48 48 48 48 48 48 48 48 48 48 48 48 48 48 0-30 ft. Roof Height   Table 2D: Rail Spans (in) for Roof Slopes and Tilt Angles 46˚ to 60˚   6005 Alloy  Wind Load Gr o u n d S n o w L o a d ( p s f ) Vult 110 115 120 125 130 135 140 145 150 155 160 170 180 190 qh 15.5 16.9 18.4 20.0 21.6 23.3 25.1 26.9 28.8 30.7 32.8 37.0 41.5 46.2 Pg Ps -6.3 -6.9 -7.6 -8.2 -8.9 -9.6 -10.3 -11.0 -11.8 -12.6 -13.4 -15.2 -17.0 -18.9 0 0 144 144 144 144 142 139 135 132 129 126 121 113 105 99 10 8 128 126 124 123 121 120 118 116 115 113 112 109 105 99 20 15 106 106 105 104 103 102 101 100 99 98 97 95 93 91 30 23 90 90 90 90 90 90 90 89 88 88 87 85 84 82 40 31 79 79 79 79 79 79 79 79 79 79 79 78 77 76 50 39 72 72 72 72 72 72 72 72 72 72 72 72 72 71 60 46 66 66 66 66 66 66 66 66 66 66 66 66 66 66 70 54 62 62 62 62 62 62 62 62 62 62 62 62 62 62 80 62 58 58 58 58 58 58 58 58 58 58 58 58 58 58 100 77 52 52 52 52 52 52 52 52 52 52 52 52 52 52 120 92 48 48 48 48 48 48 48 48 48 48 48 48 48 48 Series 100 Structural Report and Calculations NSSE 5022 Sunrise Boulevard Fair Oaks CA 95628 (916) 536-9585 Page 12 31-60 ft. Roof Height Table 2E: Rail Spans (in) for Roof Slopes and Tilt Angles 0˚ to 19˚   6005 Alloy Wind Load Gr o u n d S n o w L o a d ( p s f ) Vult 110 115 120 125 130 135 140 145 150 155 160 170 180 190 qh 17.9 19.5 21.2 23.1 24.9 26.9 28.9 31.0 33.2 35.4 37.8 42.6 47.8 53.3 Pg Ps -12.3 -13.5 -14.7 -15.9 -17.2 -18.6 -20.0 -21.4 -22.9 -24.5 -26.1 -29.4 -33.0 -36.7 0 0 128 121 115 109 105 100 96 92 89 86 83 77 73 69 10 8 128 121 115 109 105 100 96 92 89 86 83 77 73 69 20 15 106 106 106 106 105 100 96 92 89 86 83 77 73 69 30 23 90 90 90 90 90 90 90 90 89 86 83 77 73 69 40 31 79 79 79 79 79 79 79 79 79 79 79 77 73 69 50 39 72 72 72 72 72 72 72 72 72 72 72 72 72 69 60 46 66 66 66 66 66 66 66 66 66 66 66 66 66 66 70 54 62 62 62 62 62 62 62 62 62 62 62 62 62 62 80 62 58 58 58 58 58 58 58 58 58 58 58 58 58 58 100 77 52 52 52 52 52 52 52 52 52 52 52 52 52 52 120 92 48 48 48 48 48 48 48 48 48 48 48 48 48 48 31-60 ft. Roof Height Table 2F: Rail Spans (in) for Roof Slopes and Tilt Angles 20˚ to 36˚   6005 Alloy Wind Load Gr o u n d S n o w L o a d ( p s f ) Vult 110 115 120 125 130 135 140 145 150 155 160 170 180 190 qh 17.9 19.5 21.2 23.1 24.9 26.9 28.9 31.0 33.2 35.4 37.8 42.6 47.8 53.3 Pg Ps -8.0 -8.8 -9.6 -10.4 -11.2 -12.1 -13.0 -14.0 -14.9 -16.0 -17.0 -19.2 -21.5 -24.0 0 0 144 144 144 142 135 129 123 118 114 109 105 98 92 87 10 8 132 131 129 128 127 125 123 118 114 109 105 98 92 87 20 15 106 106 106 106 106 105 105 104 103 102 101 98 92 87 30 23 90 90 90 90 90 90 90 90 90 90 90 89 87 86 40 31 79 79 79 79 79 79 79 79 79 79 79 79 79 79 50 39 72 72 72 72 72 72 72 72 72 72 72 72 72 72 60 46 66 66 66 66 66 66 66 66 66 66 66 66 66 66 70 54 62 62 62 62 62 62 62 62 62 62 62 62 62 62 80 62 58 58 58 58 58 58 58 58 58 58 58 58 58 58 100 77 52 52 52 52 52 52 52 52 52 52 52 52 52 52 120 92 48 48 48 48 48 48 48 48 48 48 48 48 48 48 Series 100 Structural Report and Calculations NSSE 5022 Sunrise Boulevard Fair Oaks CA 95628 (916) 536-9585 Page 13 31-60 ft. Roof Height Table 2G: Rail Spans (in) for Roof Slopes and Tilt Angles 37˚ to 45˚   6005 Alloy Wind Load Gr o u n d S n o w L o a d ( p s f ) Vult 110 115 120 125 130 135 140 145 150 155 160 170 180 190 qh 17.9 19.5 21.2 23.1 24.9 26.9 28.9 31.0 33.2 35.4 37.8 42.6 47.8 53.3 Pg Ps -7.7 -8.4 -9.1 -9.9 -10.7 -11.6 -12.4 -13.3 -14.3 -15.2 -16.2 -18.3 -20.6 -22.9 0 0 144 144 144 144 139 133 127 122 117 112 108 101 94 89 10 8 132 131 129 128 127 125 124 122 117 112 108 101 94 89 20 15 106 106 106 106 106 105 105 104 103 102 101 99 94 89 30 23 90 90 90 90 90 90 90 90 90 90 90 89 87 86 40 31 79 79 79 79 79 79 79 79 79 79 79 79 79 79 50 39 72 72 72 72 72 72 72 72 72 72 72 72 72 72 60 46 66 66 66 66 66 66 66 66 66 66 66 66 66 66 70 54 62 62 62 62 62 62 62 62 62 62 62 62 62 62 80 62 58 58 58 58 58 58 58 58 58 58 58 58 58 58 100 77 52 52 52 52 52 52 52 52 52 52 52 52 52 52 120 92 48 48 48 48 48 48 48 48 48 48 48 48 48 48 31-60 ft. Roof Height Table 2H: Rail Spans (in) for Roof Slopes and Tilt Angles 46˚ to 60˚   6005 Alloy Wind Load Gr o u n d S n o w L o a d ( p s f ) Vult 110 115 120 125 130 135 140 145 150 155 160 170 180 190 qh 17.9 19.5 21.2 23.1 24.9 26.9 28.9 31.0 33.2 35.4 37.8 42.6 47.8 53.3 Pg Ps -7.3 -8.0 -8.7 -9.5 -10.2 -11.0 -11.9 -12.7 -13.6 -14.5 -15.5 -17.5 -19.6 -21.8 0 0 144 144 143 139 136 132 129 125 120 115 111 104 97 91 10 8 125 123 122 120 118 116 115 113 111 110 108 104 97 91 20 15 105 104 103 102 101 100 99 98 97 96 95 92 90 88 30 23 90 90 90 90 90 89 88 87 87 86 85 83 82 80 40 31 79 79 79 79 79 79 79 79 79 79 78 77 76 74 50 39 72 72 72 72 72 72 72 72 72 72 72 71 70 69 60 46 66 66 66 66 66 66 66 66 66 66 66 66 66 65 70 54 62 62 62 62 62 62 62 62 62 62 62 62 62 62 80 62 58 58 58 58 58 58 58 58 58 58 58 58 58 58 100 77 52 52 52 52 52 52 52 52 52 52 52 52 52 52 120 92 48 48 48 48 48 48 48 48 48 48 48 48 48 48 Series 100 Structural Report and Calculations NSSE 5022 Sunrise Boulevard Fair Oaks CA 95628 (916) 536-9585 Page 14 Rail Testing The aluminum rails have been designed in accordance with the 2015 Aluminum Design Manual (ADM) as referenced in the IBC. Testing was conducted per the standards set forth by the IBC Section 1715; Preconstruction Load Test. The results of this testing procedure were used in comparison with the calculated values to establish the maximum uplift load allowed for the rails. Racking Connections to the Existing Roof Contained within the calculation packet are calculations for the connection of the rails to the roof framing. Using the sizes provided by SnapNrack, we have calculated the maximum forces that will be resisted based on the withdrawal value of the lag screws, and the strength of the aluminum components which are involved in transferring these forces from the rail to the roof framing. These components consist of the flashed L-foot (SnapNrack Drawing PEN-D01), Standoff (PEN-D02, D03), Seam Clamp (PEN-D04), Corrugated Block (PEN-D05), Metal Roof Base (PEN-D09, D10, D11, D12) and Hanger Bolt (PEN-D06). All (6) options are acceptable under the parameters shown in SnapNrack’s plans. The results from our analysis have been integrated into the summary charts. The connection of the PV racking system to the roof will use a 5/16” diameter Lag Bolt installed with a minimum 2 ½” embedment into the framing member. Bolts shall be installed to a rafter or blocking capable of supporting both wind and seismic loads along with the weight of the PV system. When PEN-D07 is involved, use minimum quantity 2 ¼-20 lag bolts with minimum 1.25” embedment. In addition, SnapNrack’s Tile Roof Hooks (Drawing PEN-D13, D14) are also acceptable attachment components when the following limitations are followed: 1. tile roof hooks have been reviewed up to 120 mph, Design Wind Speed 2. rail span is limited to 6 feet with tile roof hooks Series 100 Structural Report and Calculations NSSE 5022 Sunrise Boulevard Fair Oaks CA 95628 (916) 536-9585 Page 15 Summary Charts and Topographic Factors The attached pages of this summary contain some of the most common building configurations with varying wind speeds. These charts serve as quick references for looking up maximum rail spans based on the building and site conditions. However, it must be noted that for any building where a topographic factor is applied (e.g. hills, mesas, seashore), the rail span lengths given might exceed what is allowed for the given site condition. In that case, a registered structural engineer shall evaluate the exact topographic conditions for the specific site. End Zone and Edge Distances The edge zones and/or end zones of the roof area shall be determined based on the building’s least horizontal dimension (LDH). The edge zone, “a”, is equal to 10% of the LDH where a = .1 * LDH. It should be noted that if the solar panels installed cross two different roof sections, the smaller LDH shall be used. Rail spans in the corner zone shall be a maximum of 24 inches and this restriction will only apply to the rail attachments located in the end and edge zones (does not apply to modulus or rails that overhang into the zone). Furthermore, all edge zones requiring an adjustment (shaded cells in chart) shall be reduced by 24 inches to a minimum of 32 inches. Detail 1 roof end /edge and corner zones Series 100 Structural Report and Calculations NSSE 5022 Sunrise Boulevard Fair Oaks CA 95628 (916) 536-9585 Page 16 Site – Specific Analysis A site-specific analysis is required if the location of the solar panel installation corresponds to any of the following criteria:  The total pitch of the solar panel (solar panel pitch & roof pitch) is greater than 60 degrees above the horizontal.  A topographic factor applied to a location. Generally, topographic factors are applied when the structure is on a hill, mesa or bluff, or is adjacent to a large body of water. For complete descriptions of topographic factors, please refer to ASCE 7-10 section 26.8  The mean roof height of the structure that the solar panels will be installed on is greater than 60 ft. above grade.  A combination of loads and/or site conditions applied that is not addressed in the attached rail span charts. If one or more of these factors corresponds to the project location, please contact NSSE, and we will analyze the site conditions and recommend standoff spacing for each specific site. Existing Building Limitations This summary letter addresses the structural adequacy of the solar racking system only and does not investigate or validate the adequacy of the structure the racking system is being placed upon. It does not address the ability of the existing roofing or roof framing to support the new loads imposed upon them by the new system, nor does it address the new localized forces between the roofing and the roof framing which might be imposed by the new standoff connections. It also does not address the additional lateral forces imposed upon the building due to the seismic and wind forces that the new system will add to the existing roof. These various building-specific issues need to be evaluated by the appropriate registered professional(s) prior to the addition of the photovoltaic and racking systems. NSSE may be consulted for building-specific structural evaluation. NSSE assumes the systems will be installed to the specifications presented here and the installer will use good structural judgment. Series 100 Structural Report and Calculations NSSE 5022 Sunrise Boulevard Fair Oaks CA 95628 (916) 536-9585 Page 17 Please note that all sizes, materials specifications, and weights have been provided by SnapNrack. Installation must be in accordance with SnapNrack drawings as noted: Drawing Title Revision S100-D01 F S100-D02 F S100-D03 F S100-D03 F S100-D04 F S100-D05 F S100-D06 F S100-D07 F S100-D08 F S100-D09 F S100-D10 F S100-D11 F PEN-D01 F PEN-D02 F PEN-D03 F PEN-D04 F PEN-D05 F PEN-D06 F PEN-DO7 F PEN-D08 F PEN-D09 F PEN-D10 F PEN-D11 F PEN-D12 F PEN D13 F PEN D14 F Please see SnapNrack plans for limits on the bolt parameters. Torque all 5/16” diameter hardware as specified in SnapNrack’s plans (10-16 ft-lbs for Silver Stainless Steel and 7- 9ft –lbs for black Stainless Steel, unless otherwise noted). All waterproofing, roofing and drainage issues are the responsibility of SnapNrack’s customer(s) otherwise known as the contractor(s) or the professional solar installer(s). Please let us know if you have any questions. Norman Scheel PE, SE LEED-AP BD+C, LEED-AP Homes Fellow SEAOC Fellow A.S.C.E. Series 100   Structural Report and Calculations NSSE 5022 Sunrise Boulevard Fair Oaks CA 95628 (916) 536-9585 Page A1   Appendix A: ASCE-2010 to 2005 conversion sheet The 100 Series report’s results have been calculated according to the ASCE-2010 guidelines. If the results would rather be examined in terms of the ASCE-2005 codes, the following conversions must be applied for the two codes’ results to be of equivalence. This appendix also applies for converting to different years for IBC codes. For 2006 and 2009 IBC, use the ASCE-2005 codes, and for the 2012 and 2015 IBC, use the ASCE-2010 codes. Factors specific to this report 1) The roof-mounted solar panels are in terms of Risk Category II 2) The importance factor for the ASCE-2005 code is I = 1.0 3) The ASCE-2010 code has no importance factor for the wind loads 4) The snow load’s importance factor remains the same for both the 2005 and 2010 codes 5) Thus, calculations that utilize wind loads are the ONLY ones that need conversions Velocity Equivalence (mph) V3-sec (ASCE7-05) Vult. (ASCE7-10) 85 100 90 116 100 129 110 142 120 155 130 168 140 181 150 194 The following velocities listed in the graph refer to some V2005 being equal to some V2010. In other words, use the following velocities in accordance with either ASCE-2005 or ASCE-2010. DESCRIPTION:PART NUMBER:SCALE:DESIGNER: APPROVED BY: REVISION: MAINSTREAM ENERGY CORP. 775 FIERO LANE, SUITE 200 Ɣ SAN LUIS OBISPO, CA 93401 USA PHONE (805) 528-9705 Ɣ FAX (805) 528-9701 THE INFORMATION IN THIS DRAWING IS CONFIDENTIAL AND PROPRIETARY. ANY REPRODUCTION, DISCLOSURE, OR USE THEREOF IS PROHIBITED WITHOUT THE WRITTEN CONSENT OF MAINSTREAM ENERGY CORPORATION. SERIES 100 OVERVIEW, ON FLASHED L-FEETS100 D01D Ryan REV FDATE: DNS 120113 DRAFTER: G McPheeters SNAPNRACK SERIES 100 ON FLASHED L-FEET FLASHED L-FEET ARE OPTIMIZED FOR QUICK AND ROBUST INSTALLATION ON STANDARD COMPOSITION SHINGLE ROOF SURFACES FOR OTHER ROOF TYPES STANDOFFS ARE RECOMMENDED SNAPNRACK STANDARD RAIL ROOF RAFTER TYP (ROOF ATTACHMENTS SHOULD ALWAYS BE EMBEDDED INTO ROOF RAFTERS OR STRUCTURAL MEMBERS SUCH AS STEEL PURLINS)ROOF SHEATHING, UNDERLAYMENT, AND ROOFING MATERIAL, TYP. SNAPNRACK FLASHED L-FOOT SNAPNRACK MODULE ATTACHMENT HARDWARE DESCRIPTION:PART NUMBER:SCALE:DESIGNER: APPROVED BY: REVISION: MAINSTREAM ENERGY CORP. 775 FIERO LANE, SUITE 200 Ɣ SAN LUIS OBISPO, CA 93401 USA PHONE (805) 528-9705 Ɣ FAX (805) 528-9701 THE INFORMATION IN THIS DRAWING IS CONFIDENTIAL AND PROPRIETARY. ANY REPRODUCTION, DISCLOSURE, OR USE THEREOF IS PROHIBITED WITHOUT THE WRITTEN CONSENT OF MAINSTREAM ENERGY CORPORATION. SERIES 100 OVERVIEW, ON STANDOFFSS100 D02D Ryan REV FDATE: DNS 120113 DRAFTER: G McPheeters SNAPNRACK MODULE ATTACHMENT HARDWARE SNAPNRACK STANDARD RAIL ROOF RAFTER TYP (ROOF ATTACHMENTS SHOULD ALWAYS BE EMBEDDED INTO ROOF RAFTERS OR STRUCTURAL MEMBERS SUCH AS STEEL PURLINS ROOF SHEATHING, UNDERLAYMENT, AND ROOFING MATERIAL, TYP. SNAPNRACK STANDOFF WITH CONE FLASHING, TYP. DESCRIPTION:PART NUMBER:SCALE:DESIGNER: APPROVED BY: REVISION: MAINSTREAM ENERGY CORP. 775 FIERO LANE, SUITE 200 Ɣ SAN LUIS OBISPO, CA 93401 USA PHONE (805) 528-9705 Ɣ FAX (805) 528-9701 THE INFORMATION IN THIS DRAWING IS CONFIDENTIAL AND PROPRIETARY. ANY REPRODUCTION, DISCLOSURE, OR USE THEREOF IS PROHIBITED WITHOUT THE WRITTEN CONSENT OF MAINSTREAM ENERGY CORPORATION. SERIES 100 ASSEMBLY DETAILS UECS100 D03D Ryan REV FDATE: DNS 120113 DRAFTER: G McPheeters SNAPNRACK SERIES 100 RACKING SYSTEM SHOWN MOUNTED ON STANDOFFS WITH UNIVERSAL END CLAMPS NOTES: - STANDARD LAG BOLT SPEC ASSUMES 5/16" LAG BOLTS WITH 2.5" EMBEDMENT IN ROOF STRUCTURAL MEMBERS/RAFTERS - TORQUE ALL 5 16" HARDWARE TO THE FOLLOWING: - SILVER S.S. 10-16 FT-LBS - BLACK S.S. 7-9 FT-LBS RAIL CAN MOUNT TO EITHER SIDE OF POST (UPSLOPE vs. DOWNSLOPE) - FOR UNEVEN ROOF SURFACES, USE UP TO TWO LEVELING SPACERS PER L FOOT OR STANDOFF. SEE DRAWING "STANDARD RAIL LEVELING" FOR DETAILS AND LIMITATIONS ASSEMBLED SYSTEM (SOLAR PANELS NOT SHOWN) SYSTEM SHOWN WITH STANDOFF MOUNTING COMPATIBLE WITH ALL ROOF TYPES USE FLASHED L FOOT FOR FASTER INSTALLATION ON COMPOSITION SHINGLE ROOFS 5 16" X 2.75" (TYP.) S.S. BOLT WITH SPLIT LOCK WASHER SNAPNRACK UNIVERSAL END CLAMP ASSEMBLY SNAPNRACK CHANNEL NUT 5 16" X 1" S.S. BOLT WITH SPLIT LOCK WASHER SNAPNRACK STANDARD RAIL SNAPNRACK STANDARD RAIL SPLICE BASE 5 16" X 3 4" S.S. BOLTS WITH SPLIT LOCK WASHERS (3 PER SPLICE) SNAPNRACK STANDOFF CLAMP 5 16" X 2" TYP. (OR 1.5") S.S. BOLT WITH SPLIT LOCK WASHER SNAPNRACK STANDOFF SHAFT (VARIOUS LENGTHS)5 16" LAG BOLT WITH WASHER SNAPNRACK STANDOFF BASE STANDARD 1-HOLE GAP RAILS 0.1"-0.2" FOR THERMAL EXPANSION AT SPLICES SNAPNRACK MID CLAMP ASSEMBLY SNAPNRACK STANDARD RAIL SPLICE INSERT SNAPNRACK RUBBER RAIN COLLAR DESCRIPTION:PART NUMBER:SCALE:DESIGNER: APPROVED BY: REVISION: MAINSTREAM ENERGY CORP. 775 FIERO LANE, SUITE 200 Ɣ SAN LUIS OBISPO, CA 93401 USA PHONE (805) 528-9705 Ɣ FAX (805) 528-9701 THE INFORMATION IN THIS DRAWING IS CONFIDENTIAL AND PROPRIETARY. ANY REPRODUCTION, DISCLOSURE, OR USE THEREOF IS PROHIBITED WITHOUT THE WRITTEN CONSENT OF MAINSTREAM ENERGY CORPORATION. SERIES 100 TILT KITS 0-15 DEGS100 D04D.Ryan F 12/02/15 REV FDATE: DNS 12/02/15 DRAFTER: G.McPheeters G.McPheeters SNAPNRACK SERIES 100 RACKING SYSTEM SHOWN MOUNTED ON STANDOFFS WITH TOP MOUNT END CLAMP NOTES: - STANDARD LAG BOLT SPEC ASSUMES 5/16" LAG BOLTS WITH 2.5" EMBEDMENT IN ROOF STRUCTURAL MEMBERS/RAFTERS - TORQUE ALL 5 16" HARDWARE TO THE FOLLOWING: - SILVER S.S. 10-16 FT-LBS - BLACK S.S. 7-9 FT-LBS RAIL CAN MOUNT TO EITHER SIDE OF POST (UPSLOPE vs. DOWNSLOPE) - FOR UNEVEN ROOF SURFACES, USE UP TO TWO LEVELING SPACERS PER L FOOT OR STANDOFF. SEE DRAWING "STANDARD RAIL LEVELING" FOR DETAILS AND LIMITATIONS ASSEMBLED SYSTEM (SOLAR MODUELS NOT SHOWN) SYSTEM SHOWN WITH STANDOFF MOUNTING COMPATIBLE WITH ALL ROOF TYPES USE FLASHED L FOOT FOR FASTER INSTALLATION ON COMPOSITION SHINGLE ROOFS SNAPNRACK RAIL STANDARD SNAPNRACK STANDARD RAIL SPLICE BASE SNAPNRACK STANDOFF CLAMP SNAPNRACK STANDOFF SHAFT (VARIOUS SIZES) 5 16" LAG BOLT WITH WASHER SNAPNRACK STANDOFF BASE STANDARD 1-HOLE GAP RAILS 0.1"-0.15" FOR THERMAL EXPANSION AT SPLICES SNAPNRACK CHANNEL NUTS SNAPNRACK STANDARD RAIL SPLICE INSERT SNAPNRACK MID CLAMP ASSEMBLY SNAPNRACK RUBBER RAIN COLLAR CENTER SPLICE ON RAIL GAP “ 1/4" DESCRIPTION:PART NUMBER:SCALE:DESIGNER: APPROVED BY: REVISION: MAINSTREAM ENERGY CORP. 775 FIERO LANE, SUITE 200 Ɣ SAN LUIS OBISPO, CA 93401 USA PHONE (805) 528-9705 Ɣ FAX (805) 528-9701 THE INFORMATION IN THIS DRAWING IS CONFIDENTIAL AND PROPRIETARY. ANY REPRODUCTION, DISCLOSURE, OR USE THEREOF IS PROHIBITED WITHOUT THE WRITTEN CONSENT OF MAINSTREAM ENERGY CORPORATION. SERIES 100 TYPICAL LAYOUTS100 D05D Ryan REV FDATE: DNS 120113 DRAFTER: G McPheeters NOTES: - STANDARD LAG BOLT SPEC ASSUMES 5/16" LAG BOLTS WITH 2.5" EMBEDMENT IN ROOF STRUCTURAL MEMBERS/RAFTERS - TORQUE ALL 5 16" HARDWARE TO THE FOLLOWING: - SILVER S.S. 10-16 FT-LBS - BLACK S.S. 7-9 FT-LBS RAIL CAN MOUNT TO EITHER SIDE OF POST (UPSLOPE vs. DOWNSLOPE) - FOR UNEVEN ROOF SURFACES, USE UP TO TWO LEVELING SPACERS PER L FOOT OR STANDOFF. SEE DRAWING "STANDARD RAIL LEVELING" FOR DETAILS AND LIMITATIONS SNAPNRACK SERIES 100 RACKING SYSTEM TYPICAL ROOF LAYOUT STANDOFFS ARE BOLTED INTO ROOF RAFTERS OR STRUCTURAL MEMBER ROOF RAFTERS OR STRUCTURAL MEMBERS SNAPNRACK MODULE MID CLAMPS "RAIL SPAN" DISTANCE BETWEEN ROOF ATTACHMENTS "RAIL END OVERHANG" (NOT TO EXCEED 34% OF ACCEPTABLE RAIL SPAN) MODULE OVERHANG MODULE OVERHANG (NOT TO EXCEED 30% OR MANUFACTURER'S RECOMMENDATIONS) DETAIL A SCALE 5:8 A DESCRIPTION:PART NUMBER:SCALE:DESIGNER: APPROVED BY: REVISION: MAINSTREAM ENERGY CORP. 775 FIERO LANE, SUITE 200 Ɣ SAN LUIS OBISPO, CA 93401 USA PHONE (805) 528-9705 Ɣ FAX (805) 528-9701 THE INFORMATION IN THIS DRAWING IS CONFIDENTIAL AND PROPRIETARY. ANY REPRODUCTION, DISCLOSURE, OR USE THEREOF IS PROHIBITED WITHOUT THE WRITTEN CONSENT OF MAINSTREAM ENERGY CORPORATION. SERIES 100 RAIL LEVELINGS100 D06D Ryan REV FDATE: DNS 120113 DRAFTER: G McPheeters STANDARD SERIES 100 ATTACHMENTS FEATURE 3" OF VERTICAL ADJUSTABILITY ON ALL MOUNTING POINTS WITH THE USE OF 1" LEVELING SPACERS THE FIRST INCH OF ADJUSTABILITY IS ACCOMPLISHED WITH SLIDING FEATURES BUILT INTO BOTH L FOOT AND STANDOFF CLAMP COMPONENTS FOR AN ADDITIONAL INCH OF HEIGHT ADJUSTMENT, ADD ONE LEVELING SPACER. USE OF SINGLE LEVELING SPACER NOT TO EXCEED 30% OF ATTACHMENT POINTS ON L-FEET OR 10" STANDOFFS. FOR A SECOND ADDITIONAL INCH OF HEIGHT ADJUSTMENT, ADD ANOTHER LEVELING SPACER. USE OF TWO LEVELING SPACERS NOT TO EXCEED 10% OF ATTACHMENT POINTS ON L-FEET OR 10" STANDOFFS. RAIL HEIGHT =3.4" ABOVE ROOF SURFACE ONE L FOOT RAIL HEIGHT =4.4" ABOVE ROOF SURFACE ONE L FOOT RAIL HEIGHT =5.4" ABOVE ROOF SURFACE ONE L FOOT PLUS ONE SPACER UNDER L FOOT RAIL HEIGHT =6.4" ABOVE ROOF SURFACE ONE L FOOT PLUS TWO SPACERS UNDER L FOOT RAIL HEIGHT =7.5" ABOVE ROOF SURFACE 7" STANDOFF RAIL HEIGHT =8.5" ABOVE ROOF SURFACE 7" STANDOFF RAIL HEIGHT =9.5" ABOVE ROOF SURFACE 7" STANDOFF PLUS ONE SPACER ON TOP OF STANDOFF RAIL HEIGHT =10.5" ABOVE ROOF SURFACE 7" STANDOFF PLUS TWO SPACERS ON TOP OF STANDOFF 3.4 4.4 5.4 6.4 7.5 8.5 9.5 10.5 USE CARE DURING INSTALLATION TO ENSURE THAT THE SET SCREW IS ROUGHLY CENTERED BETWEEN THE TWO PIECES BEING JOINED - 1X SNAPNRACK LEVELING SPACER - 1X 5 16"-18 X 1" LONG SET SCREW - 2X SNAPNRACK LEVELING SPACER - 2X 5 16"-18 X 1" LONG SET SCREW DESCRIPTION:PART NUMBER:SCALE:DESIGNER: APPROVED BY: REVISION: MAINSTREAM ENERGY CORP. 775 FIERO LANE, SUITE 200 Ɣ SAN LUIS OBISPO, CA 93401 USA PHONE (805) 528-9705 Ɣ FAX (805) 528-9701 THE INFORMATION IN THIS DRAWING IS CONFIDENTIAL AND PROPRIETARY. ANY REPRODUCTION, DISCLOSURE, OR USE THEREOF IS PROHIBITED WITHOUT THE WRITTEN CONSENT OF MAINSTREAM ENERGY CORPORATION. SERIES 100 RAIL LEVELING HD STANDOFFS100 D07D Ryan REV FDATE: DNS 120113 DRAFTER: G McPheeters STANDARD SERIES 100 ATTACHMENTS FEATURE 3" OF VERTICAL ADJUSTABILITY ON ALL MOUNTING POINTS WITH THE USE OF 1" LEVELING SPACERS THE FIRST INCH OF ADJUSTABILITY IS ACCOMPLISHED WITH SLIDING FEATURES BUILT INTO BOTH L FOOT AND STANDOFF CLAMP COMPONENTS FOR AN ADDITIONAL INCH OF HEIGHT ADJUSTMENT, ADD ONE LEVELING SPACER. USE OF SINGLE LEVELING SPACER NOT TO EXCEED 30% OF ATTACHMENT POINTS. FOR A SECOND ADDITIONAL INCH OF HEIGHT ADJUSTMENT, ADD ANOTHER LEVELING SPACER. USE OF TWO LEVELING SPACERS NOT TO EXCEED 10% OF ATTACHMENT POINTS. THE LIMITS ABOVE APPLY WHEN YOU ARE AT THE MAXIMUM STANDOFF HEIGHT DEPENDING ON THE STANDOFF BASE BEING USED. FOR HD STANDOFFS ON HD STANDOFF BASES, THE MAXIMUM STANDOFF HEIGHT (BEFORE APPLYING THE LIMITATIONS ABOVE) IS 12". 12.2 13.2 14.2 15.2 RAIL HEIGHT =12.2" ABOVE ROOF SURFACE 12" HD STANDOFF RAIL HEIGHT =13.2" ABOVE ROOF SURFACE 12" HD STANDOFF RAIL HEIGHT =14.2" ABOVE ROOF SURFACE 12" HD STANDOFF PLUS ONE SPACER ON TOP OF STANDOFF RAIL HEIGHT =15.2" ABOVE ROOF SURFACE 12" HD STANDOFF PLUS TWO SPACERS ON TOP OF STANDOFF USE CARE DURING INSTALLATION TO ENSURE THAT THE SET SCREW IS ROUGHLY CENTERED BETWEEN THE TWO PIECES BEING JOINED - 1X SNAPNRACK LEVELING SPACER - 1X 5 16"-18 X 1" LONG SET SCREW - 2X SNAPNRACK LEVELING SPACER - 2X 5 16"-18 X 1" LONG SET SCREW DESCRIPTION:PART NUMBER:SCALE:DESIGNER: APPROVED BY: REVISION: MAINSTREAM ENERGY CORP. 775 FIERO LANE, SUITE 200 Ɣ SAN LUIS OBISPO, CA 93401 USA PHONE (805) 528-9705 Ɣ FAX (805) 528-9701 THE INFORMATION IN THIS DRAWING IS CONFIDENTIAL AND PROPRIETARY. ANY REPRODUCTION, DISCLOSURE, OR USE THEREOF IS PROHIBITED WITHOUT THE WRITTEN CONSENT OF MAINSTREAM ENERGY CORPORATION. SERIES 100 TILT KITS 0-15 DEGS100 D08D Ryan F 12/02/15 REV FDATE: DNS 12/02/15 DRAFTER: G McPheeters G McPheeters USE TILT KIT OPTION FOR INSTALLATIONS THAT REQUIRE MODULES TO BE TILTED ABOVE THE EXISTING ROOF SLOPE LOW TILT SYSTEM SHOWN IS DESIGNED FOR TILT ANGLES FROM 0 TO 15 DEGREES ABOVE ROOF SURFACE NOTES: - TORQUE 5 16" HARDWARE TO THE FOLLOWING UNLESS OTHERWISE NOTED: - SILVER S.S. 10-16 FT-LBS - BLACK S.S. 7-9 FT-LBS - REFER TO ENGINEERING CHARTS FOR RAIL SPAN BASED ON MODULE TILT ANGLE, WIND SPEED, AND SNOW LOAD - FOR HIGHER TILT APPLICATIONS SEE "SERIES 100 TILT KIT 10-45 DEG" SNAPNRACK RAIL STANDARD SNAPNRACK CHANNEL NUT SNAPNRACK L FOOT ALL-PURPOSE OR L FOOT COMPOSITION 5 16" FLANGE NUT, USE ANTI-SEIZE COMPOUND TO PREVENT STAINLESS TO STAINLESS GALLING SNAPNRACK STANDOFF CLAMP 5 16" X 2" S.S. BOLT WITH SPLIT LOCK WASHER STANDOFF ASSEMBLY (THIS TILT-UP CONFIGURATION IS ALSO COMPATIBLE WITH THE FLASHED L FOOT MOUNTING OPTION) MAX. REAR STANDOFF HEIGHT: 18 INCHES USE SHORTEST POSSIBLE FRONT STANDOFF TO MEET FLASHING REQUIREMENTS SNAPNRACK MID CLAMP ASSEMBLY USE OF ANTI-SEIZE ON TILT HARDWARE IS RECOMMENDED (PARTICULARLY FOR STAINLESS TO STAINLESS HARDWARE) TO PREVENT GALLING DESCRIPTION:PART NUMBER:SCALE:DESIGNER: APPROVED BY: REVISION: MAINSTREAM ENERGY CORP. 775 FIERO LANE, SUITE 200 Ɣ SAN LUIS OBISPO, CA 93401 USA PHONE (805) 528-9705 Ɣ FAX (805) 528-9701 THE INFORMATION IN THIS DRAWING IS CONFIDENTIAL AND PROPRIETARY. ANY REPRODUCTION, DISCLOSURE, OR USE THEREOF IS PROHIBITED WITHOUT THE WRITTEN CONSENT OF MAINSTREAM ENERGY CORPORATION. SERIES 100 TILT KITS 10-45 DEGS100 D09D Ryan REV FDATE: DNS 120113 DRAFTER: G McPheeters USE TILT KIT OPTION FOR INSTALLATIONS THAT REQUIRE MODULES TO BE TILTED ABOVE THE EXISTING ROOF SLOPE SYSTEM SHOWN IS DESIGNED FOR TILT ANGLES FROM 10 TO 45 DEGREES ABOVE ROOF SURFACE USE OF ANTI-SEIZE ON TILT HARDWARE IS RECOMMENDED (PARTICULARLY FOR STAINLESS TO STAINLESS HARDWARE) REFER TO S100 TKT SERIES 170 TILT KIT TOOL FOR A SIMPLE TOOL THAT DRAMATICALLY SIMPLIFIES TILT KIT INSTALLATION BY SUPPORTING THE UPPER RAIL AHEAD OF MODULE INSTALLATION NOTES: - TORQUE 5 16" HARDWARE TO THE FOLLOWING UNLESS OTHERWISE NOTED: - SILVER S.S. 10-16 FT-LBS - BLACK S.S. 7-9 FT-LBS - REFER TO ENGINEERING CHARTS FOR RAIL SPAN BASED ON MODULE TILT ANGLE, WIND SPEED, AND NOW LOAD - BACK SUPPORT "LEG" IS FABRICATED FROM A SCRAP OF RAIL. CALCULATE REQUIRED TILT LEG LENGTH AND CUT RAIL TO LENGTH - FOR LOWER TILT APPLICATIONS SEE "SERIES 100 TILT KIT 0-15 DEG" - SNAPNRACK RAIL COVER CAN BE USED TO COVER CHANNEL IN REAR TILT LEG SNAPNRACK RAIL STANDARD 5 16" X 3 4" (OR 1") S.S. BOLT WITH SPLIT LOCK WASHER SNAPNRACK RAIL STANDARD SNAPNRACK L FOOT ALL-PURPOSE OR L FOOT COMPOSITION 5 16" X 1" (OR 1.25") S.S. BOLT WITH SPLIT LOCK WASHER CUT REAR TILT LEG FROM SCRAP OF STANDARD RAIL SNAPNRACK STANDOFF CLAMP 5 16" X 2" (OR 1.5") S.S. BOLT WITH SPLIT LOCK WASHER SNAPNRACK STANDOFF CLAMP SNAPNRACK L FOOT ALL-PURPOSE OR L FOOT COMPOSITION 5 16" FLANGE NUT 5 16" X 1" (OR 1.25") S.S. BOLT WITH SPLIT LOCK WASHER STANDOFF ASSEMBLY (THIS CONFIGURATION ALSO COMPATIBLE WITH FLASHED L FOOT MOUNTING SNAPNRACK MID CLAMP ASSEMBLY MAX LENGTH: 48" WITH STANDARD ENGINEERING SNAPNRACK CHANNEL NUTS, TORQUE TO 10-16 FT-LBS WHEN USING WEEBS. WHEN USING SNAPNRACK BONDING CHANNEL NUTS, TORQUE TO 14-16 FT-LBS. WEEBS ARE NOT REQUIRED WITH BONDING CHANNEL NUTS. DESCRIPTION:PART NUMBER:SCALE:DESIGNER: APPROVED BY: REVISION: MAINSTREAM ENERGY CORP. 775 FIERO LANE, SUITE 200 Ɣ SAN LUIS OBISPO, CA 93401 USA PHONE (805) 528-9705 Ɣ FAX (805) 528-9701 THE INFORMATION IN THIS DRAWING IS CONFIDENTIAL AND PROPRIETARY. ANY REPRODUCTION, DISCLOSURE, OR USE THEREOF IS PROHIBITED WITHOUT THE WRITTEN CONSENT OF MAINSTREAM ENERGY CORPORATION. SERIES 100 TILT KITS 10-45 DEG WITH L FOOT MOUNTS100 D10D Ryan REV FDATE: DNS 120113 DRAFTER: G McPheeters USE TILT KIT OPTION FOR INSTALLATIONS THAT REQUIRE MODULES TO BE TILTED ABOVE THE EXISTING ROOF SLOPE SYSTEM SHOWN IS DESIGNED FOR TILT ANGLES FROM 10 TO 45 DEGREES ABOVE ROOF SURFACE USE OF ANTI-SEIZE ON TILT HARDWARE IS RECOMMENDED (PARTICULARLY FOR STAINLESS TO STAINLESS HARDWARE) REFER TO S100 TKT SERIES 170 TILT KIT TOOL FOR A SIMPLE TOOL THAT DRAMATICALLY SIMPLIFIES TILT KIT INSTALLATION BY SUPPORTING THE UPPER RAIL AHEAD OF MODULE INSTALLATION NOTES: - TORQUE 5 16" HARDWARE TO THE FOLLOWING UNLESS OTHERWISE NOTED: - SILVER S.S. 10-16 FT-LBS - BLACK S.S. 7-9 FT-LBS - REFER TO ENGINEERING CHARTS FOR RAIL SPAN BASED ON MODULE TILT ANGLE, WIND SPEED, AND SNOW LOAD - BACK SUPPORT "LEG" IS FABRICATED FROM A SCRAP OF RAIL. CALCULATE REQUIRED TILT LEG LENGTH. USE WEEB GROUNDING WASHERS AT JOINTS BETWEEN L-FEET AND SNAPNRACK STANDARD RAIL SCRAP PIECE - FOR LOWER TILT APPLICATIONS SEE "SERIES 100 TILT KIT 0-15 DEG" - SNAPNRACK RAIL COVER CAN BE USED TO COVER CHANNEL IN REAR TILT LEG SNAPNRACK L-FOOT ALL-PURPOSE OR L-FOOT COMPOSITION SNAPNRACK RAIL STANDARD 5 16" X 1" (OR 1.25") S.S. BOLT WITH SPLIT LOCK WASHER CUT REAR TILT LEG FROM SCRAP OF STANDARD RAIL SNAPNRACK MID CLAMP ASSEMBLY MAX LENGTH: 48" WITH STANDARD ENGINEERING SNAPNRACK CHANNEL NUTS, TORQUE TO 10-16 FT-LBS WHEN USING WEEBS. WHEN USING SNAPNRACK BONDING CHANNEL NUTS, TORQUE TO 14-16 FT-LBS. WEEBS ARE NOT REQUIRED WITH BONDING CHANNEL NUTS. DESCRIPTION:PART NUMBER:SCALE:DESIGNER: APPROVED BY: REVISION: MAINSTREAM ENERGY CORP. 775 FIERO LANE, SUITE 200 Ɣ SAN LUIS OBISPO, CA 93401 USA PHONE (805) 528-9705 Ɣ FAX (805) 528-9701 THE INFORMATION IN THIS DRAWING IS CONFIDENTIAL AND PROPRIETARY. ANY REPRODUCTION, DISCLOSURE, OR USE THEREOF IS PROHIBITED WITHOUT THE WRITTEN CONSENT OF MAINSTREAM ENERGY CORPORATION. SERIES 100 TILT KITS 10-45 DEG SEAM CLAMP MOUNTS100 D11D Ryan REV FDATE: DNS 042514 DRAFTER: G McPheeters USE TILT KIT OPTION FOR INSTALLATIONS THAT REQUIRE MODULES TO BE TILTED ABOVE THE EXISTING ROOF SLOPE SYSTEM SHOWN IS DESIGNED FOR TILT ANGLES FROM 10 TO 45 DEGREES ABOVE ROOF SURFACE ON STANDING SEAM METAL ROOFS USE OF ANTI-SEIZE ON TILT HARDWARE IS RECOMMENDED (PARTICULARLY FOR STAINLESS TO STAINLESS HARDWARE) REFER TO S100 TKT SERIES 170 TILT KIT TOOL FOR A SIMPLE TOOL THAT DRAMATICALLY SIMPLIFIES TILT KIT INSTALLATION BY SUPPORTING THE UPPER RAIL AHEAD OF MODULE INSTALLATION NOTES: - TORQUE 5 16" HARDWARE TO THE FOLLOWING UNLESS OTHERWISE NOTED: - SILVER S.S. 10-16 FT-LBS - BLACK S.S. 7-9 FT-LBS - REFER TO ENGINEERING CHARTS FOR RAIL SPAN BASED ON MODULE TILT ANGLE, WIND SPEED, AND SNOW LOAD - BACK SUPPORT "LEG" IS FABRICATED FROM A SCRAP OF RAIL. CALCULATE REQUIRED TILT LEG LENGTH AND CUT RAIL TO LENGTH - FOR LOWER TILT APPLICATIONS SEE "SERIES 100 TILT KIT 0-15 DEG" - SNAPNRACK RAIL COVER CAN BE USED TO COVER CHANNEL IN REAR TILT LEG CUT REAR TILT LEG FROM SCRAP OF STANDARD RAIL SNAPNRACK RAIL STANDARD SNAPNRACK CHANNEL NUT SNAPNRACK SEAM CLAMP WIDE OR STANDARD BASE 5 16" X 1" (OR 1.25") S.S. BOLTS WITH SPLIT LOCK WASHERS 5 16" FLANGE NUT 5 16" X 1" (OR 1.25") S.S. BOLT WITH SPLIT LOCK WASHER 5 16" X 1" S.S. BOLT WITH SPLIT LOCK WASHER SNAPNRACK SEAM CLAMP WIDE OR STANDARD BASE SNAPNRACK L FOOT ALL-PURPOSE OR L FOOT COMPOSITION SNAPNRACK MID CLAMP ASSEMBLY MAX LENGTH: 48" WITH STANDARD ENGINEERING SNAPNRACK CHANNEL NUTS, TORQUE TO 10-16 FT-LBS WHEN USING WEEBS. WHEN USING SNAPNRACK BONDING CHANNEL NUTS, TORQUE TO 14-16 FT-LBS. WEEBS ARE NOT REQUIRED WITH BONDING CHANNEL NUTS. SECTION A-A SCALE 1 / 4 A A DESCRIPTION:PART NUMBER:SCALE:DESIGNER: APPROVED BY: REVISION: MAINSTREAM ENERGY CORP. 775 FIERO LANE, SUITE 200 Ɣ SAN LUIS OBISPO, CA 93401 USA PHONE (805) 528-9705 Ɣ FAX (805) 528-9701 THE INFORMATION IN THIS DRAWING IS CONFIDENTIAL AND PROPRIETARY. ANY REPRODUCTION, DISCLOSURE, OR USE THEREOF IS PROHIBITED WITHOUT THE WRITTEN CONSENT OF MAINSTREAM ENERGY CORPORATION. SERIES 100 FLASHING DETAIL, STANDOFF WITH FLAT TILES100 D12D Ryan REV FDATE: DNS 120113 DRAFTER: G McPheeters SNAPNRACK STANDOFF SHAFT SNAPNRACK STANDOFF BASE, 1 HOLE ROOF SHEATHING TYP. RAFTER TYP. S-TILE STANDOFFATTACHMENTTOP VIEW STEP 1: REMOVE TILE AND IDENTIFY RAFTER LOCATION WITH A PILOT DRILL. MOUNT STANDOFF ASSEMBLY TO ROOF SHEATHING WITH A 5/16IN LAG BOLT MINIMUM 2.5" EMBEDMENT TYP. BE SURE LAG BOLT IS FULLY SEATED STEP 2: SLIDE FLASHING OVER POST, UNDER UPPER LAYER OF TILE STEP 3: USE CORING BIT OR OTHER METHOD TO DRILL CLEARANCE HOLE IN TILE TO ALLOW IT TO BE REPLACED IN ORIGINAL LOCATION PLACE SEALANT AROUND LAG BOLT AND UNDER STANDOFF BASE FLAT ROOF TILE TYP. STEP 4: REPLACE TILES SEAL TOP OF CONE FLASHING WITH RUBBER RAIN COLLAR, ALUMINUM TAPE, OR ALTERNATE METHOD FLASHING BASE SECTION A-A SCALE 1 / 4 A A DESCRIPTION:PART NUMBER:SCALE:DESIGNER: APPROVED BY: REVISION: MAINSTREAM ENERGY CORP. 775 FIERO LANE, SUITE 200 Ɣ SAN LUIS OBISPO, CA 93401 USA PHONE (805) 528-9705 Ɣ FAX (805) 528-9701 THE INFORMATION IN THIS DRAWING IS CONFIDENTIAL AND PROPRIETARY. ANY REPRODUCTION, DISCLOSURE, OR USE THEREOF IS PROHIBITED WITHOUT THE WRITTEN CONSENT OF MAINSTREAM ENERGY CORPORATION. SERIES 100 FLASHING DETAIL, STANDOFF ON S-TILE ROOFS100 D13D Ryan REV FDATE: DNS 120113 DRAFTER: G McPheeters DEADPAN ALUMINUM SOLAR FLASHING. BEND FLASHING TO MATCH CONTOUR OF S-TILES SNAPNRACK STANDOFF SHAFT SNAPNRACK STANDOFF BASE, 1 HOLE ROOF SHEATHING TYP. RAFTER TYP. TOP OF CONE FLASHING MAY BE SEALED WITH SNAPNRACK RUBBER RAIN COLLAR OR ALUMINUM TAPE S-TILE STANDOFFATTACHMENTTOP VIEW STEP 1: REMOVE TILE AND IDENTIFY RAFTER LOCATION WITH A PILOT DRILL. MOUNT STANDOFF ASSEMBLY TO ROOF SHEATHING WITH A 5/16IN LAG BOLT MINIMUM 2IN EMBEDMENT TYP. BE SURE LAG BOLT IS FULLY SEATED STEP 2: SLIDE FLASHING OVER POST, UNDER UPPER LAYER OF TILE, AND FORM FLASHING TO MATCH CONTOUR OF TILES STEP 3: USE CORING BIT TO DRILL 2.5" HOLE IN TILE TO ALLOW IT TO BE REPLACED IN ORIGINAL LOCATION PLACE SEALANT AROUND LAG BOLT AND UNDER STANDOFF BASE S-TILE TYP. DESCRIPTION:PART NUMBER:SCALE:DESIGNER: APPROVED BY: REVISION: MAINSTREAM ENERGY CORP. 775 FIERO LANE, SUITE 200 Ɣ SAN LUIS OBISPO, CA 93401 USA PHONE (805) 528-9705 Ɣ FAX (805) 528-9701 THE INFORMATION IN THIS DRAWING IS CONFIDENTIAL AND PROPRIETARY. ANY REPRODUCTION, DISCLOSURE, OR USE THEREOF IS PROHIBITED WITHOUT THE WRITTEN CONSENT OF MAINSTREAM ENERGY CORPORATION. PEN DETAIL 01, FLASHED L FOOT TO RAFTERS100 PEN D01D Ryan REV FDATE: DNS 120113 DRAFTER: G McPheeters 5 16 X 1" (OR 1.25") S.S. BOLT AND SPLIT WASHER 5 16 S.S. FLANGE NUT SNAPNRACK COMPOSITION ROOF FLASHING SNAPNRACK STANDARD RAIL SNAPNRACK CHANNEL NUT SNAPNRACK COMPOSITION L FOOT CAN BE MOUNTED IN ANY ORIENTATION SNAPNRACK L FOOT BASE 5 16" S.S. LAG SCREW WITH FLAT WASHER 2.5" MINIMUM EMBEDMENT IS STANDARD FLASHED L FOOT MOUNTING POINT FOR USE ON COMPOSITION ROOF SURFACES WITH LOW TO MODERATE TILT RAILS CAN BE LEVELED UP TO 3" USING UP TO TWO LEVELING SPACERS AS SHOWN IN "SERIES 100 RAIL LEVELING" RAFTER TYP. ROOF DECKING TYP. STEP 3: PLACE L FOOT ON TOP OF FLASHING AND TIGHTEN NUT STEP 2: SLIP FLASHING OVER L FOOT BASE AND UNDER ROW OF SHINGLES ABOVE ROOF DECKING TYP. NOTES: - 5/16" LAG BOLTS MUST EMBED 2.5" INTO ROOF STRUCTURAL MEMBERS/RAFTERS - TORQUE ALL 5/16" HARDWARE TO THE FOLLOWING: - SILVER S.S. 10-16 FT-LBS - BLACK S.S. 7-9 FT-LBS - RAILS CAN MOUNT TO EITHER SIDE OF L FOOT (UPSLOPE VS DOWNSLOPE) STEP 1: BOLT L FOOT BASE TO ROOF WITH LAG BOLT COMPLETED INSTALLATION DESCRIPTION:PART NUMBER:SCALE:DESIGNER: APPROVED BY: REVISION: MAINSTREAM ENERGY CORP. 775 FIERO LANE, SUITE 200 Ɣ SAN LUIS OBISPO, CA 93401 USA PHONE (805) 528-9705 Ɣ FAX (805) 528-9701 THE INFORMATION IN THIS DRAWING IS CONFIDENTIAL AND PROPRIETARY. ANY REPRODUCTION, DISCLOSURE, OR USE THEREOF IS PROHIBITED WITHOUT THE WRITTEN CONSENT OF MAINSTREAM ENERGY CORPORATION. PEN DETAIL 02, STANDOFF TO RAFTERS100 PEN D02D Ryan REV FDATE: DNS 120113 DRAFTER: G McPheeters NOTES: - 5/16" LAG BOLTS MUST EMBED 2.5" INTO ROOF STRUCTURAL MEMBERS/RAFTERS - TORQUE ALL 5 16" HARDWARE TO THE FOLLOWING: - SILVER S.S. 10-16 FT-LBS - BLACK S.S. 7-9 FT-LBS - RAILS CAN MOUNT TO EITHER SIDE OF POST (UPSLOPE VS. DOWNSLOPE) - RAILS CAN BE LEVELED UP TO 3" USING UP TO TWO LEVELING SPACERS AS SHOWN IN "SERIES 100 RAIL LEVELING" * A POURED SEALANT-STYLE FLASHING MAY BE USED WITH SNAPNRACK STANDOFFS AS AN ALTERNATIVE TO A TYPICAL CONE FLASHING WHEN INSTALLED PER MANUFACTURER'S INSTRUCTIONS ON LOW-SLOPE ROOF SURFACES SNAPNRACK STANDARD RAIL SNAPNRACK CHANNEL NUT SNAPNRACK STANDOFF CLAMP 5 16" X 2" S.S. BOLT AND 5 16" S.S. SPLIT WASHER 5 16" S.S. LAG SCREW WITH FLAT WASHER. 2.5" MINIMUM EMBEDMENT IS STANDARD ROOF RAFTER OR STRUCTURAL MEMBER ROOF DECKING TYP. SEAL PENETRATION AND UNDER BASE WITH APPROPRIATE ROOF SEALANT SNAPNRACK STANDOFF BASE STD 1-HOLE 5 16" X 1" S.S. BOLT AND 5 16" S.S. SPLIT WASHER INSTALLED FROM BACK SIDE OF STANDOFF BASE PRIOR TO INSTALLATION ON ROOF SNAPNRACK STANDOFF SHAFT, STANDARD (VARIOUS SIZES) SNAPNRACK RUBBER RAIN COLLAR INSTALLS OVER TOP OF FLASHING COMPLETE INSTALLATION (SHOWN WITH FLASHING IN PLACE) FLASH POST WITH STANDARD GALVANIZED STEEL OR DEAD SOFT ALUMINUM ROOF FLASHING FOR 1" DIAMETER VENT PIPE* DESCRIPTION:PART NUMBER:SCALE:DESIGNER: APPROVED BY: REVISION: MAINSTREAM ENERGY CORP. 775 FIERO LANE, SUITE 200 Ɣ SAN LUIS OBISPO, CA 93401 USA PHONE (805) 528-9705 Ɣ FAX (805) 528-9701 THE INFORMATION IN THIS DRAWING IS CONFIDENTIAL AND PROPRIETARY. ANY REPRODUCTION, DISCLOSURE, OR USE THEREOF IS PROHIBITED WITHOUT THE WRITTEN CONSENT OF MAINSTREAM ENERGY CORPORATION. PEN DETAIL 03, STANDOFF TO PURLINS100 PEN D03D Ryan REV FDATE: DNS 120113 DRAFTER: G McPheeters NOTES: - TEK SCREWS MUST EMBED IN ROOF STRUCTURAL MEMBERS/PURLINS - TORQUE ALL 5 16" HARDWARE TO THE FOLLOWING: - SILVER S.S. 10-16 FT-LBS - BLACK S.S. 7-9 FT-LBS - RAILS CAN MOUNT TO EITHER SIDE OF POST (UPSLOPE VS. DOWNSLOPE) - RAILS CAN BE LEVELED UP TO 3" USING UP TO TWO LEVELING SPACERS AS SHOWN IN "SERIES 100 RAIL LEVELING" * A POURED SEALANT-STYLE FLASHING MAY BE USED WITH SNAPNRACK STANDOFFS AS AN ALTERNATIVE TO A TYPICAL CONE FLASHING WHEN INSTALLED PER MANUFACTURER'S INSTRUCTIONS ON LOW-SLOPE ROOF SURFACES SNAPNRACK STANDARD RAIL SNAPNRACK CHANNEL NUTSNAPNRACK STANDOFF CLAMP 5 16" X 2" S.S. BOLT AND 5 16" S.S. SPLIT WASHER 1 4" TEK SCREW IS TYPICAL FOR SECURING STANDOFFS TO ROOF PURLINS. PULLOUT AND PULLOVER VALUES ARE DEPENDENT ON SCREW SIZE AND MANUFACTURER AS WELL AS GAUGE OF METAL PURLIN ROOF DECKING TYP. SEAL PENETRATION AND UNDER BASE WITH APPROPRIATE ROOF SEALANT SNAPNRACK STANDOFF BASE STD 1-HOLE 5 16" X 1" S.S. BOLT AND 5 16" S.S. SPLIT WASHER INSTALLED FROM BACK SIDE OF STANDOFF BASE PRIOR TO INSTALLATION ON ROOF SNAPNRACK STANDOFF SHAFT, STANDARD (VARIOUS SIZES) SNAPNRACK RUBBER RAIN COLLAR INSTALLS OVER TOP OF FLASHING COMPLETE INSTALLATION (SHOWN WITH FLASHING IN PLACE) ROLL FORMED STEEL PURLIN OR STRUCTURAL MEMBER FLASH POST WITH STANDARD GALVANIZED STEEL ROOF FLASHING FOR 1" DIAMETER VENT PIPE * DESCRIPTION:PART NUMBER:SCALE:DESIGNER: APPROVED BY: REVISION: MAINSTREAM ENERGY CORP. 775 FIERO LANE, SUITE 200 Ɣ SAN LUIS OBISPO, CA 93401 USA PHONE (805) 528-9705 Ɣ FAX (805) 528-9701 THE INFORMATION IN THIS DRAWING IS CONFIDENTIAL AND PROPRIETARY. ANY REPRODUCTION, DISCLOSURE, OR USE THEREOF IS PROHIBITED WITHOUT THE WRITTEN CONSENT OF MAINSTREAM ENERGY CORPORATION. PEN DETAIL 04, SEAM CLAMPS100 PEN D04D Ryan REV FDATE: DNS 120113 DRAFTER: G McPheeters CAMMING SEAM CLAMPS ARE SPECIFIED WITH A BLACK OXIDE STAINLESS STEEL BOLT. IT IS IMPORTANT TO USE THE PROVIDED BOLT AND TO TIGHTEN TO 16 FT-LBS FOR FULL LOAD CAPABILITY L FOOT OR SIMILAR TILT BRACKETS CAN BE ATTACHED TO THE TOP OF THE CLAMP AND PROVIDE A MOUNTING POINT FOR RAILS OR OTHER STRUCTURAL MEMBERS CLAMP CAN BE USED TO SECURE RAILS OR DIRECTLY SUPPORT SOLAR MODULES WITH MODULE CLAMPS SEAM CLAMP BASE (STD BASE SHOWN BUT INSTALLATION OF WIDE BASE IS IDENTICAL) 1: INSTALLATION STARTS WITH CLAMP IN OPEN POSITION WITH BOLT LOOSE SEAM CLAMP CAM SEAM CLAMP THREAD INSERT 2: OPEN CLAMP GETS LOWERED ONTO SEAM 3: BOLT IS TIGHTENED, SECURING CLAMP AND L FOOT AT THE SAME TIME TO DETERMINE BOLT SIZE ADD 1.17" TO THE "STACK" ON TOP OF THE CLAMP (X) AND ROUND UP TO NEAREST 1 4" BOLT SIZE 4: TORQUE BOLT TO 10-16 FT-LBS 1 2 3 4 .5 TYP. .9 "X" DESCRIPTION:PART NUMBER:SCALE:DESIGNER: APPROVED BY: REVISION: MAINSTREAM ENERGY CORP. 775 FIERO LANE, SUITE 200 Ɣ SAN LUIS OBISPO, CA 93401 USA PHONE (805) 528-9705 Ɣ FAX (805) 528-9701 THE INFORMATION IN THIS DRAWING IS CONFIDENTIAL AND PROPRIETARY. ANY REPRODUCTION, DISCLOSURE, OR USE THEREOF IS PROHIBITED WITHOUT THE WRITTEN CONSENT OF MAINSTREAM ENERGY CORPORATION. PEN DETAIL 05, CORRUGATED ROOF BLOCKS100 PEN D05D Ryan REV FDATE: DNS 120113 DRAFTER: G McPheeters USE THE SNAPNRACK CORRUGATED ROOF BLOCK TO STRADDLE THE RAISED PORTIONS OF CORRUGATED METAL ROOFING MATERIALS. THIS ALLOWS AN L FOOT TO BE MOUNTED WITH THE PENETRATION AT THE HIGH POINT OF THE ROOFING MATERIAL WITHOUT CRUSHING THE ROOF PROFILE. SHOWN WITH A TEK SCREW ATTACHMENT TYPICAL OF A METAL PURLIN STRUCTURE, BUT THE SYSTEM WORKS WELL WITH A LAG BOLT INTO A WOOD RAFTER AS WELL. BE SURE TO USE PROPER SEALANT TO SEAL UP THE HOLE IN THE METAL ROOFING MATERIAL SNAPNRACK STANDARD RAIL TEK SCREW SECURES L FOOT TO ROOF PURLINS TEK SCREW SHOULD PENETRATE ROOF PROFILE SNAPNRACK CORRUGATED ROOF BLOCK SNAPNRACK L FOOT CORRUGATED METAL ROOFING (DETAILS OF PROFILE VARY SIGNIFICANTLY) TOP FLANGE OF ROOF PURLINS (OR RAFTER) CORRUGATED METAL ROOF (TYPICAL 25 8" X 7 8" PROFILE SHOWN) CORRUGATED METAL ROOF (TYPICAL 25 8" X 1 2" PROFILE SHOWN) PART DIMENSIONS 1.34 .90 1.21 2.42 2.67 ATTACHMENT HOLE SHOULD BE DRILLED AT HIGH POINT AND BE SEALED WITH AN APPROPRIATE SEALANT AS SHOWN MIN 3 FULL THREADS SHOULD CLEAR IF FASTENING TO STEEL ROLL FORMS DESCRIPTION:PART NUMBER:SCALE:DESIGNER: APPROVED BY: REVISION: MAINSTREAM ENERGY CORP. 775 FIERO LANE, SUITE 200 Ɣ SAN LUIS OBISPO, CA 93401 USA PHONE (805) 528-9705 Ɣ FAX (805) 528-9701 THE INFORMATION IN THIS DRAWING IS CONFIDENTIAL AND PROPRIETARY. ANY REPRODUCTION, DISCLOSURE, OR USE THEREOF IS PROHIBITED WITHOUT THE WRITTEN CONSENT OF MAINSTREAM ENERGY CORPORATION. PEN DETAIL 06 L HANGER BOLTS100 PEN D06D Ryan REV FDATE: DNS 120113 DRAFTER: G McPheeters HANGER BOLT CLAMPS HAVE BEEN DESIGNED FOR USE WITH STANDARD 3 8" STAINLESS HANGER BOLTS. THEY ARE COMPATIBLE WITH ANY 3 8" STAINLESS BOLT OR THREADED ROD. THE CLAMPS ARE 1.5" TALL AND ENGINEERED TO HAVE A MINIMUM OF 1.25" OF THREAD IN THE CLAMP AT ALL TIMES. MAXIMUM DESIGN LOAD IS 1,000 LBS (AXIAL) OR 250 LBS IF A FACTOR OF SAFETY OF 4 IS APPLIED. - TORQUE ALL 5 16" HARDWARE TO THE FOLLOWING: - SILVER S.S. 10-16 FT-LBS - BLACK S.S. 7-9 FT-LBS SNAPNRACK STANDARD RAIL 5 16"x 1.25-1.5" S.S. BOLT W SPLIT LOCK WASHER SNAPNRACK HANGER BOLT CLAMP USE TWO PIECES "BACK TO BACK" PER CLAMP ASSEMBLY, MINIMUM OF 1.25" OF THREADS CLAMPED 3 8" STAINLESS HANGER BOLT 8" TYPICAL BUT SHORTER SIZES MAY BE USED SO LONG AS 1.25" OF THREADS ARE ENGAGED IN THE BOLT TO RAIL CLAMP ASSEMBLED UNIT SNAPNRACK CHANNEL NUT DESCRIPTION:PART NUMBER:SCALE:DESIGNER: APPROVED BY: REVISION: MAINSTREAM ENERGY CORP. 775 FIERO LANE, SUITE 200 Ɣ SAN LUIS OBISPO, CA 93401 USA PHONE (805) 528-9705 Ɣ FAX (805) 528-9701 THE INFORMATION IN THIS DRAWING IS CONFIDENTIAL AND PROPRIETARY. ANY REPRODUCTION, DISCLOSURE, OR USE THEREOF IS PROHIBITED WITHOUT THE WRITTEN CONSENT OF MAINSTREAM ENERGY CORPORATION. PEN DETAIL 07, STANDOFF TO JOISTS100 PEN D07D Ryan F 12/02/15 REV FDATE: DNS 12/02/15 DRAFTER: G McPheeters G McPheeters COMPLETED INSTALLATION (SHOWN WITH FLASHING IN PLACE) NOTES: - WOOD SCREWS MUST EMBED IN ROOF STRUCTURAL MEMBERS/JOISTS. TYPICAL DESIGN UPLIFT LOAD REQUIREMENT IS 340 LBS PER ATTACHMENT - TORQUE ALL 5 16" HARDWARE TO THE FOLLOWING: - SILVER S.S. 10-16 FT-LBS - BLACK S.S. 7-9 FT-LBS - RAILS CAN MOUNT TO EITHER SIDE OF POST (UPSLOPE VS. DOWNSLOPE) - RAILS CAN BE LEVELED UP TO 3" USING UP TO TWO LEVELING SPACERS AS SHOWN IN "SERIES 100 RAIL LEVELING" SNAPNRACK STANDARD RAIL SNAPNRACK CHANNEL NUT SNAPNRACK STANDOFF CLAMP 5 16" X 2" S.S. BOLT AND 5 16" S.S. SPLIT WASHER UP TO QTY (4) 1/4-20 LAG SCREWS CAN BE USED TO SECURE THE STANDOFF BASE TO ROOF JOIST. THE HOLE PATTERN ENSURES THAT THE BASE CAN BE ORIENTED TO AVOID RUNNING A LARGE LAG BOLT INTO THE WEB OF A COMPOSITE WOOD JOIST AND CRACKING IT. COMPOSITE WOOD ROOF JOIST OR SIMILAR STRUCTURAL MEMBER NOTE: THE 4 HOLE HAS BEEN DESIGNED TO ALLOW THE INSTALLER TO AVOID SPLITTING THE WEB OF THE JOIST WITH A SINGLE LARGE LAG BOLT. ROOF DECKING TYP. SEAL PENETRATION AND UNDER BASE WITH APPROPRIATE ROOF SEALANT SNAPNRACK STANDOFF BASE STD 4-HOLE SNAPNRACK STANDOFF SHAFT STD (VARIOUS SIZES) SNAPNRACK RUBBER RAIN COLLAR INSTALLS OVER TOP OF FLASHING FLASH POST WITH STANDARD GALVANIZED STEEL OR DEAD SOFT ALUMINUM ROOF FLASHING FOR 1" DIAMETER VENT PIPE. A POURED SEALANT-STYLE FLASHING MAY BE USED WITH SNAPNRACK STANDOFFS AS AN ALTERNATIVE TO A TYPICAL CONE FLASHING WHEN INSTALLED PER MANUFACTURER'S INSTRUCTIONS ON LOW-SLOPE ROOF SURFACES QTY (2 TO 4) 1/4-20 LAG SCREWS, 1.25" MIN. EMBEDMENT, TYP. IF 2 SCREWS ARE USED, LOCATE SCREWS AT OPPOSITE DIAGONAL CORNERS OF STANDOOF BASE DESCRIPTION:PART NUMBER:SCALE:DESIGNER: APPROVED BY: REVISION: MAINSTREAM ENERGY CORP. 775 FIERO LANE, SUITE 200 Ɣ SAN LUIS OBISPO, CA 93401 USA PHONE (805) 528-9705 Ɣ FAX (805) 528-9701 THE INFORMATION IN THIS DRAWING IS CONFIDENTIAL AND PROPRIETARY. ANY REPRODUCTION, DISCLOSURE, OR USE THEREOF IS PROHIBITED WITHOUT THE WRITTEN CONSENT OF MAINSTREAM ENERGY CORPORATION. PEN DETAIL 08, HD STANDOFFS100 PEN D08D Ryan F 12/02/15 REV FDATE: DNS 12/02/15 DRAFTER: G McPheeters G McPheeters SNAPNRACK STANDARD RAIL SNAPNRACK CHANNEL NUTSNAPNRACK STANDOFF CLAMP 5 16" LAG SCREW IS TYPICAL FOR SECURING STANDOFF BASE TO ROOF RAFTER, 2.5" MIN EMBEDMENT INTO RAFTER TYP. SNAPNRACK RUBBER RAIN COLLAR INSTALLS OVER TOP OF FLASHING SNAPNRACK STANDOFF SHAFT HD (VARIOUS SIZES INCLUDING 7, 9.5, 12, AND 18" SHAFTS) SNAPNRACK STANDOFF BASE HD, 6-HOLE SEAL PENETRATION AND UNDER BASE WITH APPROPRIATE ROOF SEALANT ROOF RAFTER OR STRUCTURAL MEMBER ROOF DECKING TYP. SNAPNRACK STANDOFF MOUNTING POINT FOR USE ON ALL ROOF SURFACES NOTES: - LAG BOLTS MUST EMBED IN ROOF STRUCTURAL MEMBERS/RAFTERS - TORQUE ALL 5 16" HARDWARE TO THE FOLLOWING: - SILVER S.S. 10-16 FT-LBS - BLACK S.S. 7-9 FT-LBS - RAILS CAN MOUNT TO EITHER SIDE OF POST (UPSLOPE VS. DOWNSLOPE) - RAILS CAN BE LEVELED UP TO 3" USING UP TO TWO LEVELING SPACERS AS SHOWN IN DRAWING S100 D07 "SERIES 100 HD STANDOFF LEVELING" HD STANDOFFS ARE OFTEN USED WITH FOAM ROOF INSULATION FLASH POST WITH STANDARD GALVANIZED STEEL OR DEAD SOFT ALUMINUM ROOF FLASHING FOR 1" DIAMETER VENT PIPE. A POURED SEALANT-STYLE FLASHING MAY BE USED WITH SNAPNRACK STANDOFFS AS AN ALTERNATIVE TO A TYPICAL CONE FLASHING WHEN INSTALLED PER MANUFACTURER'S INSTRUCTIONS ON LOW-SLOPE ROOF SURFACES FOAM INSULATION, TYP. IF 2 LAG SCREWS ARE USED, LOCATE SCREWS IN OPPOSITE CENTER HOLES ON BASE SECTION A-A SCALE 3:4 AA DESCRIPTION:PART NUMBER:SCALE:DESIGNER: APPROVED BY: REVISION: MAINSTREAM ENERGY CORP. 775 FIERO LANE, SUITE 200 Ɣ SAN LUIS OBISPO, CA 93401 USA PHONE (805) 528-9705 Ɣ FAX (805) 528-9701 THE INFORMATION IN THIS DRAWING IS CONFIDENTIAL AND PROPRIETARY. ANY REPRODUCTION, DISCLOSURE, OR USE THEREOF IS PROHIBITED WITHOUT THE WRITTEN CONSENT OF MAINSTREAM ENERGY CORPORATION. PEN DETAIL 09, METAL ROOF BASE TO RAFTERS100 PEN D09DRyan REV FDATE: DNS 120113 DRAFTER: GMcPHEETERS SNAPNRACK STANDARD RAIL METAL ROOF DECK SHEATHING, TYPICAL RAFTER, TYPICAL SNAPNRACK L FOOT SNAPNRACK METAL ROOF BASE CAP 5 16-18 STAINLESS FLANGE NUT TORQUE 10-16 FT-LBS 5 16" X 3 4" STAINLESS WASHER SNAPNRACK METAL ROOF BASE BOTTOM 5 16" LAG BOLT WITH MIN 2.5" EMBEDMENT TYP. ENSURE LAG BOLT IS FULLY SEATED TO METAL ROOF BASE BOTTOM STEP 1: DRILL 3/16" PILOT HOLE IN RAFTER. ENSURE AREA SURROUNDING HOLE IS FREE FROM METAL SHAVINGS AND DEBRIS. STEP 2: ATTACH METAL ROOF BASE TO RAFTER WITH 5/16IN LAG BOLT. TORQUE TO 10-16 FT LBS. STEP 3: THREAD METAL ROOF BASE CAP ONTO METAL ROOF BASE BOTTOM. TAKE CARE TO ENSURE THE BASE DOES NOT TWIST WHEN CAP IS TIGHTENED. ENSURE CAP IS FULLY SEATED TO BASE. STEP 4: ATTACH L-FOOT TO STUD IN METAL ROOF BASE CAP WITH FLANGE NUT. SNAPNRACK STANDARD RAIL SNAPNRACK L-FOOT SNAPNRACK METAL ROOF BASE CAP SNAPNRACK METAL ROOF BASE BOTTOM 5/16" LAG BOLT WITH 3/4" WASHER UPPER SEALING WASHER SEALS METAL ROOF BASE CAP TO BOTTOM LOWER SEALING WASHER SEALS METAL ROOF BASE BOTTOM TO ROOF SURFACE SHEATHING, TYPICAL RAFTER, TYPICAL METAL ROOF PANEL, TYPICAL 2.5" MINIMUM EMBEDMENT INTO RAFTER 5 16 -18 X 1" (OR 1.25") S.S. BOLT AND SPLIT WASHER 5 16 -18 X 1" (OR 1.25") S.S. BOLT AND SPLIT WASHER SECTION A-A SCALE 3:4 AA DESCRIPTION:PART NUMBER:SCALE:DESIGNER: APPROVED BY: REVISION: MAINSTREAM ENERGY CORP. 775 FIERO LANE, SUITE 200 Ɣ SAN LUIS OBISPO, CA 93401 USA PHONE (805) 528-9705 Ɣ FAX (805) 528-9701 THE INFORMATION IN THIS DRAWING IS CONFIDENTIAL AND PROPRIETARY. ANY REPRODUCTION, DISCLOSURE, OR USE THEREOF IS PROHIBITED WITHOUT THE WRITTEN CONSENT OF MAINSTREAM ENERGY CORPORATION. PEN DETAIL 10, METAL ROOF BASE TO PURLINS100 PEN D10DRyan REV FDATE: DNS 120113 DRAFTER: GMcPHEETERS SNAPNRACK STANDARD RAIL METAL ROOF DECK SNAPNRACK L-FOOT SNAPNRACK METAL ROOF BASE CAP 5 16-18 STAINLESS FLANGE NUT TORQUE 10-16 FT-LBS SNAPNRACK METAL ROOF BASE BOTTOM STEP 1: DRILL 3/16" PILOT HOLE IN PURLIN. ENSURE AREA SURROUNDING HOLE IS FREE FROM METAL SHAVINGS AND DEBRIS. STEP 2: ATTACH METAL ROOF BASE TO PURLIN WITH 1 4" TEK OR EQUIVALENT SELF DRILLING FASTENER. TORQUE TO MANUFACTURER SPECIFICATIONS. STEP 3: THREAD METAL ROOF BASE CAP ONTO METAL ROOF BASE BOTTOM. TAKE CARE TO ENSURE THE BASE DOES NOT TWIST WHEN CAP IS TIGHTENED. ENSURE CAP IS FULLY SEATED TO BASE. STEP 4: ATTACH L-FOOT TO STUD IN METAL ROOF BASE CAP WITH FLANGE NUT. STEEL PURLIN, TYPICAL 1 4-20 TEK OR EQUIVALENT SELF DRILLING FASTENER. TORQUE TO MANUFACTURER SPECIFICATIONS SNAPNRACK STANDARD RAIL SNAPNRACK L FOOT SNAPNRACK METAL ROOF BASE CAP SNAPNRACK METAL ROOF BASE BOTTOM ATTACHMENT FASTENER 1 4" TEK SCREW TYPICAL, INTO ROOF PURLINS. SELECT FASTENER FOR A MINIMUM 350LB DESIGN UPLIFT STEEL PURLIN FLANGE, TYP. UPPER SEALING WASHER SEALS METAL ROOF BASE CAP TO BOTTOM LOWER SEALING WASHER SEALS METAL ROOF BASE BOTTOM TO ROOF SURFACE METAL ROOF PANEL, TYPICAL SECTION A-A SCALE 3:4 AA DESCRIPTION:PART NUMBER:SCALE:DESIGNER: APPROVED BY: REVISION: MAINSTREAM ENERGY CORP. 775 FIERO LANE, SUITE 200 Ɣ SAN LUIS OBISPO, CA 93401 USA PHONE (805) 528-9705 Ɣ FAX (805) 528-9701 THE INFORMATION IN THIS DRAWING IS CONFIDENTIAL AND PROPRIETARY. ANY REPRODUCTION, DISCLOSURE, OR USE THEREOF IS PROHIBITED WITHOUT THE WRITTEN CONSENT OF MAINSTREAM ENERGY CORPORATION. PEN DETAIL 11, METAL ROOF BASE WITH STANDOFF TO RAFTERS100 PEN D11DRyan REV FDATE: DNS 120113 DRAFTER: GMcPHEETERS SNAPNRACK STANDARD RAIL METAL ROOF DECK SHEATHING, TYPICAL RAFTER, TYPICAL SNAPNRACK METAL ROOF BASE CAP 5 16" X 3 4" STAINLESS WASHER SNAPNRACK METAL ROOF BASE BOTTOM 5 16" LAG BOLT WITH MIN 2.5" EMBEDMENT. ENSURE LAG BOLT IS FULLY SEATED TO METAL ROOF BASE BOTTOM STEP 1: DRILL 3/16" PILOT HOLE IN RAFTER. ENSURE AREA SURROUNDING HOLE IS FREE FROM METAL SHAVINGS AND DEBRIS. STEP 2: ATTACH METAL ROOF BASE TO RAFTER WITH 5/16IN LAG BOLT. TORQUE TO 10-16 FT LBS. STEP 3: THREAD METAL ROOF BASE CAP ONTO METAL ROOF BASE BOTTOM. TAKE CARE TO ENSURE THE BASE DOES NOT TWIST WHEN CAP IS TIGHTENED. ENSURE CAP IS FULLY SEATED TO BASE. STEP 4: ATTACH STANDOFF TO METAL ROOF BASE CAP. STANDOFFS UP TO 7" IN LENGTH MAY BE USED. SNAPNRACK STANDARD RAIL SNAPNRACK METAL ROOF BASE CAP 5 16" LAG BOLT WITH 3 4" WASHER UPPER SEALING WASHER SEALS METAL ROOF BASE CAP TO BOTTOM LOWER SEALING WASHER SEALS METAL ROOF BASE BOTTOM TO ROOF SURFACE METAL ROOF PANEL, TYPICAL SNAPNRACK METAL ROOF BASE BOTTOM SHEATHING, TYPICAL RAFTER, TYPICAL SNAPNRACK STANDOFF SNAPNRACK STANDOFF CLAMP WITH CHANNEL NUT AND HARDWARE SNAPNRACK STANDOFF CLAMP WITH CHANNEL NUT AND HARDWARE SNAPNRACK STANDOFF MAX HEIGHT: 7" 2.5" MINIMUM EMBEDMENT INTO RAFTER TYP. SECTION A-A SCALE 3:4 AA DESCRIPTION:PART NUMBER:SCALE:DESIGNER: APPROVED BY: REVISION: MAINSTREAM ENERGY CORP. 775 FIERO LANE, SUITE 200 Ɣ SAN LUIS OBISPO, CA 93401 USA PHONE (805) 528-9705 Ɣ FAX (805) 528-9701 THE INFORMATION IN THIS DRAWING IS CONFIDENTIAL AND PROPRIETARY. ANY REPRODUCTION, DISCLOSURE, OR USE THEREOF IS PROHIBITED WITHOUT THE WRITTEN CONSENT OF MAINSTREAM ENERGY CORPORATION. PEN DETAIL 12, METAL ROOF BASE WITH STANDOFF TO PURLINS100 PEN D12DRyan REV FDATE: DNS 120113 DRAFTER: GMcPHEETERS SNAPNRACK STANDARD RAIL METAL ROOF DECK SNAPNRACK METAL ROOF BASE CAP SNAPNRACK METAL ROOF BASE BOTTOM STEP 1: DRILL 3/16" PILOT HOLE IN PURLIN. ENSURE AREA SURROUNDING HOLE IS FREE FROM METAL SHAVINGS AND DEBRIS. STEP 2: ATTACH METAL ROOF BASE TO PURLIN WITH 1/4" TEK OR EQUIVALENT SELF DRILLING FASTENER. TORQUE TO MANUFACTURER SPECIFICATIONS. STEP 3: THREAD METAL ROOF BASE CAP ONTO METAL ROOF BASE BOTTOM. TAKE CARE TO ENSURE THE BASE DOES NOT TWIST WHEN CAP IS TIGHTENED. ENSURE CAP IS FULLY SEATED TO BASE. STEP 4: ATTACH STANDOFF TO METAL ROOF BASE CAP. STANDOFFS UP TO 7" IN LENGTH MAY BE USED. STEEL PURLIN, TYPICAL 1/4-20 TEK OR EQUIVALENT SELF DRILLING FASTENER. TORQUE TO MANUFACTURER SPECIFICATIONS SNAPNRACK STANDARD RAIL SNAPNRACK METAL ROOF BASE CAP SNAPNRACK METAL ROOF BASE BOTTOM ATTACHMENT FASTENER 1 4" TEK SCREW TYPICAL, INTO ROOF PURLINS. SELECT FASTENER FOR MINIMUM 350LB DESIGN UPLIFT STEEL PURLIN FLANGE, TYP. UPPER SEALING WASHER SEALS METAL ROOF BASE CAP TO BOTTOM LOWER SEALING WASHER SEALS METAL ROOF BASE BOTTOM TO ROOF SURFACE METAL ROOF PANEL, TYPICAL SNAPNRACK STANDOFF MAX HEIGHT: 7" SNAPNRACK STANDOFF CLAMP WITH CHANNEL NUT AND HARDWARE SNAPNRACK STANDOFF SNAPNRACK STANDOFF CLAMP WITH CHANNEL NUT AND HARDWARE SECTION B-B SCALE 1 / 3 BB DESCRIPTION:PART NUMBER:SCALE:DESIGNER: APPROVED BY: REVISION: MAINSTREAM ENERGY CORP. 775 FIERO LANE, SUITE 200 Ɣ SAN LUIS OBISPO, CA 93401 USA PHONE (805) 528-9705 Ɣ FAX (805) 528-9701 THE INFORMATION IN THIS DRAWING IS CONFIDENTIAL AND PROPRIETARY. ANY REPRODUCTION, DISCLOSURE, OR USE THEREOF IS PROHIBITED WITHOUT THE WRITTEN CONSENT OF MAINSTREAM ENERGY CORPORATION. SERIES 100 PEN DETAIL 13, TILE HOOK WITH FLAT TILES100 PEN D13D Ryan REV FDATE: DNS 031615 DRAFTER: G McPheeters SNAPNRACK STANDARD RAIL SNAPNRACK BONDING CHANNEL NUT SNAPNRACK TILE HOOK 5 16 -18 X 1.25" STAINLESS FLANGE BOLT 2 QTY. 5 16" LAG BOLTS WITH 3 4" WASHERS. ENSURE 2.5" MINIMUM EMBEDMENT INTO RAFTER NOTES: - INSTALLATIONS OF SNAPNRACK TILE HOOKS ARE LIMMITED TO A MAXIMUM WIND SPEED OF 120MPH (IBC2012) AND MAXIMUM ATTACHMENT SPAN OF 6FT. - 5/16" LAG BOLTS MUST EMBED 2.5" INTO ROOF STRUCTURAL MEMBERS / RAFTERS - TORQUE ALL 5 16" HARDWARE TO 10-16 FT-LBS - RAILS CAN MOUNT TO EITHER SIDE OF TILE HOOK (UPSLOPE VS. DOWNSLOPE) - RAILS CAN BE LEVELED UP TO 1.25" USING THE SLOT IN THE TILE HOOK RAFTER OR STRUCTURAL ROOF MEMBER ROOF DECKING, TYP. COMPLETED INSTALLATION SEAL PENETRATIONS AND UNDER BASE WITH APPROPRIATE ROOF SEALANT ROOF DECKING, TYP. RAFTER OR STRUCTURAL ROOF MEMBER FLAT ROOF TILE, TYP. 2.5" MINIMUM EMBEDMENT INTO RAFTER SNAPNRACK STANDARD RAIL SNAPNRACK CHANNEL NUT 5 16 -18 X 1.25" STAINLESS FLANGE BOLT 2 QTY. 5 16" LAG BOLTS WITH 3 4" WASHERS. ENSURE 2.5" MINIMUM EMBEDMENT INTO RAFTER SNAPNRACK TILE HOOK SEAL PENETRATIONS AND UNDER BASE WITH APPROPRIATE ROOF SEALANT FLAT TILE, TYP. RAFTER, TYP. ROOF DECKING, TYP. SECTION A-A SCALE 1 / 4 SECTION C-C SCALE 7:24 DETAIL E SCALE 1 /3 DETAIL F SCALE 1 /4 A ACC E F DESCRIPTION:PART NUMBER:SCALE:DESIGNER: APPROVED BY: REVISION: MAINSTREAM ENERGY CORP. 775 FIERO LANE, SUITE 200 Ɣ SAN LUIS OBISPO, CA 93401 USA PHONE (805) 528-9705 Ɣ FAX (805) 528-9701 THE INFORMATION IN THIS DRAWING IS CONFIDENTIAL AND PROPRIETARY. ANY REPRODUCTION, DISCLOSURE, OR USE THEREOF IS PROHIBITED WITHOUT THE WRITTEN CONSENT OF MAINSTREAM ENERGY CORPORATION. SERIES 100 PEN DETAIL 14, S-TILE HOOKS100 PEN D14D Ryan REV FDATE: DNS 031613 DRAFTER: G McPheeters S-TILE STANDOFFATTACHMENTTOP VIEW STEP 1: REMOVE TILES TO EXPOSE ROOF DECKING. S-TILE, TYP. ENSURE 2.5" MINIMUM EMBEDMENT INTO RAFTER, TYP. SNAPNRACK BONDING CHANNEL NUT SNAPNRACK BONDING CHANNEL NUT RAFTER OR OTHER STRUCTURAL ROOF MEMBER, TYP. ROOF DECKING, TYP. ROOF DECKING, TYP. SNAPNRACK STANDARD RAIL 5 16" LAG BOLTS WITH FLAT WASHERS SNAPNRACK STANDARD RAIL STEP 3: SLIDE THE S-TILE HOOK ARM INTO THE HOOK ON THE BASE AND ROTATE THE ARM TOWARDS THE BASE TO SNAP THE CHANNEL NUT INTO THE CAHNNEL. TIGHTEN FLANGE BOLT HAND TIGHT. ALIGN THE ARM WITH THE NEAREST VALLEY IN THE TILES AND TIGHTEN BOLT TO 10-16 FT-LBS STEP 2: DRILL TWO 3 16" PILOT HOLES INTO RAFTER. SEAL ROOF PENETRATIONS WITH APPROPRIATE SELANT. FASTEN BASE TO ROOF WITH QTY. (2) 5 16" LAG BOLTS WITH FLAT WASHERS. 5 16" LAG BOLTS WITH FLAT WASHERS TILE BATTEN, TYP. SNAPNRACK S-TILE HOOK BASE SNAPNRACK S-TILE HOOK ARM RAFTER OR OTHER STRUCTURAL ROOF MEMBER, TYP. HOOK CAN BE OFFSET FROM RAFTER UP TO 5" IN EITHER DIRECTION TO LINE UP WITH LOW POINT IN S-TILES. 5 16" LAG BOLTS WITH FLAT WASHERS THE SNAPNRACK S TILE ROOF HOOK OFFERS A QUICK, COST EFFECTIVE SOLUTION FOR MOUNTING ON S-TILE ROOFTOPS. THE SIMPLE DESIGN HAS BEEN OPTIMIZED FOR SNAPNRACK AND THE HOOKS ARE BUILT INTO OUR SYSTEM ENGINEERING AND UL LISTING. ONCE A TILE HAS BEEN REMOVED, THE BASE PIECE IS BOLTED DOWN TO A RAFTER. ONCE THE BASE IS IN PLACE, THE TILE HOOK ARM IS INSERTED INTO THE HOOK FEATURE IN THE BASE AND ROTATED DOWN TOWARDS THE TRACK SO THAT THE BONDING CHANNEL NUT SNAPS INTO THE CHANNEL. ONCE THE ARM IS ATTACHED TO THE BASE, SLIDE IT ON THE BASE SO THAT IT ALIGNS WITH A LOW POINT IN THE S-TILES, SIMPLY TIGHTEN IT IN PLACE AND REPLACE THE TILE THAT WAS REMOVED. WITH SOME TYPES OF TILE YOU MAY WANT TO DO A LITTLE GRINDING TO HELP EVERYTHING FIT BACK TOGETHER SMOOTHLY, BUT IN MANY CASES NO GRINDING IS REQUIRED. INSTALLATIONS OF SNAPNRACK S TILE ROOF HOOKS ARE LIMITTED TO A MAXIMUM WIND SPEED OF 120MPH (IBC 2012) AND A MAXIMUM ATTACHMENT SPAN OF 6FT. SNAPNRACK S-TILE HOOK ARM SNAPNRACK S-TILE HOOK BASE SNAPNRACK STANDARD RAIL 5 16" - 18 X 1.25" STAINLESS STEEL FLANGE BOLT