Loading...
HomeMy WebLinkAboutPLAN REVIEW SPRINKLER SYSTEM - 17-00667-00682 - 430 W 2nd S - Providence Square #1-15 Providence Square – Rexburg 1 of 2 STATE FIRE MARSHAL STATE OF IDAHO IDAHO DEPARTMENT OF INSURANCE C.L. “Butch” Otter 700 W. State Street, 3rd Floor P.O. Box 83720 Boise, ID 83720-0043 (208) 334-4370 | www.doi.idaho.gov/sfm PLAN REVIEW FOR FIRE SPRINKLER SYSTEMS PLANS RECEIVED: March 26, 2017 APPROVED: April 5, 2018 REVIEWED BY: Javier Cervantes, ISFM Fire Plan Reviewer PROJECT: Providence Square STREET ADDRESS: 195 South 5th West CITY: Rexburg AHJ: Madison Fire Department SUBMITTAL TYPE: New SYSTEM TYPE: NFPA 13R Wet HEAD COUNT: 116 TOTAL SYSTEMS: 1 AREA SQUARE FOOTAGE: 10,140 OCCUPANCY CLASSIFICATION: Residential CONSTRUCTION TYPE: V-B SCOPE OF WORK: New construction. SPRINKLER CONTRACTOR: Phoenix Fire Protection 4130 Airport Road Nampa, ID 83687 IDAHO LICENSE: FPSC-108 CONTACT NAME: Teri Cruikshank teri@phoenixfp.com PHONE NO: (208) 468-9115 SYSTEM DESIGNED BY: Damion Snodgrass damion@phoenixfp.com PHONE NO: (208) 258-5100 PLAN REVIEW COMMENTS: Approved with the following comments: 1. 2016 NFPA 13R 2. Add a 4 way brace to top of riser 3. At least six spare sprinklers shall be provided. (NFPA 13R 11.1.1) 4. Clean up Nodes Approval of shop drawings is not intended to imply waiver or modification of any requirements of the Idaho State Statutes or Rules, International Fire Code, NFPA Standards or any other applicable criteria. It is acknowledged that backflow preventer is installed per the demand of the local water purveyer. The State Fire Marshal’s Office and its personnel does not take any responsibility for the back flow device.