PLAN REVIEW FOR FIRE SPRINKLER SYSTEMS
PLANS RECEIVED: March 26, 2017 APPROVED: April 5, 2018
REVIEWED BY: Javier Cervantes, ISFM Fire Plan Reviewer
PROJECT: Providence Square
STREET ADDRESS: 195 South 5th West CITY: Rexburg
AHJ: Madison Fire Department
SUBMITTAL TYPE: New SYSTEM TYPE: NFPA 13R
Wet
HEAD COUNT: 116 TOTAL SYSTEMS: 1 AREA SQUARE FOOTAGE: 10,140
OCCUPANCY CLASSIFICATION: Residential CONSTRUCTION TYPE: V-B
SCOPE OF WORK: New construction.
SPRINKLER CONTRACTOR: Phoenix Fire Protection
4130 Airport Road
Nampa, ID 83687
IDAHO LICENSE: FPSC-108
CONTACT NAME: Teri Cruikshank
teri@phoenixfp.com
PHONE NO: (208) 468-9115
SYSTEM DESIGNED BY: Damion Snodgrass
damion@phoenixfp.com
PHONE NO: (208) 258-5100
PLAN REVIEW COMMENTS:
Approved with the following comments:
1. 2016 NFPA 13R
2. Add a 4 way brace to top of riser
3. At least six spare sprinklers shall be provided. (NFPA 13R 11.1.1)
4. Clean up Nodes
Approval of shop drawings is not intended to imply waiver or modification of any
requirements of the Idaho State Statutes or Rules, International Fire Code, NFPA
Standards or any other applicable criteria.
It is acknowledged that backflow preventer is installed per the demand of the local
water purveyer. The State Fire Marshal’s Office and its personnel does not take any
responsibility for the back flow device.