HomeMy WebLinkAboutPROJECT INFORMATION 1 - 18-00271 - 251 Baldwin Dr - New SFRa Load Short Form Job: FS5B7 1��i`Ighs1 L Date: 5/17/18 Entire House By: Vince Byram Modern Plumbing, Heating, and Electric P.O. Box 627, Rigby, Id 83442 Phone: 208-745-7021 Fax: 208-745-7329 Email: highcountryph@yahoo.com For: Cody Puzey Trade 3758 Yellowstones Hwy, Idaho Falls, Id 83401 Model Phone: 208-529-2116 AHRI ref Design Information AHRI ref Htg Clg Infiltration Outside db (°F) -6 89 Method Simplified Inside db ('F) 70 75 Construction quality Average Design TD (°F) 76 14 Fireplaces Daily range - H Inside humidity (%) 50 50 Moisture difference (gr/Ib) 62 -31 HEATING EQUIPMENT Make Goodman Mfg. Trade GOODMAN Model GMH950703BX AHRI ref 2002183 Efficiency Heating input Heating output Temperature rise Actual air flow Air flow factor Static pressure Space thermostat COOLING EQUIPMENT Make Goodman Mfg. Trade GOODMAN, JANITROL, AMANA DISTI Cond GSX130241C* Coil Capf303Obx AHRI ref 4765510 95 AFUE Btuh Efficiency 69000 Btuh Sensible cooling 52440 Btuh Latent cooling 67 °F Total cooling 850 cfm Actual air flow 0.024 cfm/Btuh Air flow factor 0.70 in H2O Static pressure 264 51 Load sensible heat ratio 11.0 EER, 13 SEER 16100 Btuh 6900 Btuh 23000 Btuh 850 cfm 0.087 cfm/Btuh 0.70 in H2O 1.00 116 ROOM NAME Area (I`2) Htg load (Btuh) Clg load (Btuh) Htg AVF (cfm) Clg AVF (cfm) Room1 604 9289 2577 228 225 Room2 116 1905 188 47 16 Room3 150 2075 264 51 23 Room4 250 3232 1243 79 109 Room5 242 2001 1007 49 88 Room? 45 523 64 13 6 Room8 154 2046 949 50 83 Room9 120 2520 973 62 85 Room6 156 2569 1011 63 88 Room10 441 4903 1349 120 118 Room11 321 3274 75 80 7 Room13 9F, '�01o 04 _ Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. .ti w ri to htgf t' � Right-Suite®Universal 2017 17.0.10 RSU20477 2018 -May -18 09:33:45 ...tware\Roberts\FS5B7 princeton with basement.rup Calc = MJ8 House faces: SE Page 1 Entire House d 2624 34706 9731 850 850 Other equip loads 3121 575 Equip. @ 0.94 RSM 9687 Latent cooling 0 TOTA1 C 1 0-707-7 1 Ac.' I I LvcT OtUG/ ZIU0I ODU 05U Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. Vti/C! f ItS+�J 2018 -May -18 09:33:45 Right -Suite® Universal 2017 17.0.10 RSU20477 Page t JQ4 ...tware\Roberts\FS5B7 princeton with basement.rup Calc = MJ8 House faces: SE wrlghtsoft Buildin Analysis Job: Date: FS5B7 5/17/18 Cooling Entire House By: Vince Byram 70 Modern Plumbing, Heating, and Electric Elevation: 4741 ft 15.6 P.O. Box 627, Rigby, Id 83442 Phone: 208-745-7021 Fax: 208-745-7329 Email: highcounlryph@yahoo.com For: Cody Puzey 3758 Yellowstones Hwy, Idaho Falls, Id 83401 Phone: 208-529-2116 Location: Btuh/F Indoor: Heating Cooling Idaho Falls, ID, US 15150 Ind oor temperature (°F) 70 75 Elevation: 4741 ft 15.6 Design TD (°F) 76 14 Latitude: 44°N Ceilings Relative humidity (%) 50 50 Outdoor: Heating Cooling Moisture difference (gr/Ib) 61.5 -31.5 Dry buIb(T) -6 89 Infiltration: Ducts Dailyrange (°F) - 34 ( H ) Method Simplified 0 Wet bulb (T) - 60 Construction quality Average 0 Wind speed (mph) 15.0 7.5 Fireplaces 0 Adjustments Component Btuh/F Btuh % of load Walls 4.6 15150 40.1 Glazing 24.3 5894 15.6 Doors 11.4 472 1.2 Ceilings 1.5 1800 4.8 Floors 1.9 2250 5.9 Infiltration 3.3 9140 24.2 Ducts 0 0 Piping 0 0 Humidification 0 0 Ventilation 3121 8.3 Adjustments 0 Total 37827 100.0 Component Btuh/ft2 Btuh % of load Walls 0.3 1083 10.5 Glazing 27.5 6676 64.8 Doors 2.8 115 1.1 Ceilings 0.8 995 9.7 Floors 0 0 0 Infiltration 0.3 862 8.4 Ducts 0 0 Ventilation 575 5.6 Internal gains 0 0 Blower 0 0 Adjustments 0 Total 10305 100.0 Latent Cooling Load = 0 Btuh Overall U -value =0.055 Btuh/ftp °F Data entries checked. 2018 -May -18 09:33:45 �— 'uWrightSOft Rig ht -Su ite@ Universal201717.0.10 RSU20477 Page 1 ...(ware\Roberts\FS5B7 princeton with basement.rup Calc = MJ8 House faces: SE Component Constructions Job: FS5B7 Wf ightsoft Component Date: 5/17/18 Entire House By: Vince Byram Modern Plumbing, Heating, and Electric P.O. Box 627, Rigby, Id 83442 Phone: 208-745-7021 Fax: 208-745-7329 Email: highcountryph@yahoo.com For: Cody Puzey 3758 Yellowstones Hwy, Idaho Falls, Id 83401 Phone: 208-529-2116 Location: Or Indoor: Heating Cooling Idaho Falls, ID, US Loss Indoor temperature (°F) 70 75 Elevation: 4741 ft ft' Design TD (°F) 76 14 Latitude: 44°N Btuh/ft' Relative humidity (%) 50 50 Outdoor: Heating Cooling Moisture difference (gr/Ib) 61.5 -31.5 Dry buIb(T) -6 89 Infiltration: ne 558 Dailyrange (°F) - 34 ( H ) Method Simplified 0.47 Wet bulb(°F) - 60 Construction quality Average 0.065 Wind speed (mph) 15.0 7.5 Fireplaces 0 217 Construction descriptions Or Area U -value Insul R Htg HTM Loss Clg HTM Gain 32 0.320 ft' Btuh/ft''F ft'-'F/Btuh BtuhV Btuh Btuh/ft' Btuh Walls 0 24.3 2586 23.9 2542 all 242 0.320 12F-Osw: Frm wall, vnl ext, 3/8" wood shth, r-21 cav ins, 1/2" gypsum ne 558 0.065 21.0 4.94 2757 0.47 265 board int fnsh, 2"x6" wood frm, 16" o.c. stud se 458 0.065 21.0 4.94 2260 0.47 217 68 sw 585 0.065 21.0 4.94 2890 0.47 278 0.84 nw 542 0.065 21.0 4.94 2676 0.47 257 0 all 2142 0.065 21.0 4.94 10583 0.47 1016 15B19-Owc-6: Bg wall, heavy dry or light damp soil, 2"x6" wood int frm, ne 270 0.043 19.0 3.93 1060 0.06 16 concrete wall, r-19 cav ins, 8" thk, 1/2" gypsum board int fnsh se 333 0.043 19.0 3.93 1308 0.06 20 sw 238 0.043 19.0 3.75 892 0.04 10 nw 333 0.043 19.0 3.93 1308 0.06 20 all 1174 0.043 19.0 3.89 4568 0.06 66 Partitions (none) Windows 61 C: 61 C; 6.67 ft head ht Doors metal: Door, mtl pur core type Ceilings 16B-50ad: Attic ceiling, asphalt shingles roof mat, r-50 ceil ins, 1/2" gypsum board int fnsh 1613-50ad: Attic ceiling, asphalt shingles roof mat, r-50 ceil ins, 5/8" gypsum board int fnsh Floors 21 A -24c: Bg floor, heavy dry or light damp soil, 6' depth, carpet flr fnsh se 104 0.320 0 24.3 2529 30.4 3161 sw 32 0.320 0 24.3 778 30.4 973 nw 106 0.320 0 24.3 2586 23.9 2542 all 242 0.320 0 24.3 5894 27.5 6676 se 41 0.150 6.7 11.4 472 2.77 115 45 0.020 50.0 1.52 68 0.84 38 1139 0.020 50.0 1.52 1731 0.84 957 762 0.025 0 1.90 1448 0 0 43 0.025 0 1.90 82 0 0 379 0.025 0 1.90 720 0 0 all 1184 0.025 0 1.90 2250 0 0 2018 -May -18 09:33:45 49 WriightSoft Right -Suite@ Universal 2017 17.0.10 RSU20477 ACGX Page 1 ...tware\Roberts\FS5B7 Princeton with basement.rup Calc = MJS House faces: SE 1Ai!'Iqf1tS(){ Right Suite®Universa12017 17.0.10 RSU20477 2018-May-18 09:33:45 Page 2 ...tware\Roberts\FS587 Princeton with basement.rup Calc = MJS House faces: SE wrrightsoft Project Summar y Entire House Job: Date: By: FS5B7 5/17/18 Vince Byram 262�f Modern Plumbing, Heating, and Electric Volume (ft) 19044 P.O. Box 627, Rigby, Id 83442 Phone: 208-745-7021 Fax: 208-745-7329 Email: highcountryph@yahoo.com For: Cody Puzey 3758 Yellowstones Hwy, Idaho Falls, Id 83401 Phone: 208-529-2116 Notes: Weather: Winter Design Conditions Outside db Inside db Design TD Idaho Falls, ID, US Summer Design Conditions -6 °F Outside db 70 °F Inside db 76 °F Design TD Daily range Relative humidity Moisture difference Heating Summary Structure 34706 Btuh Ducts 0 Btuh Central vent (44 cfm) 3121 Btuh Humidification 0 Btuh Piping 0 Btuh Equipment load 37827 Btuh Infiltration Method Construction quality Fireplaces Simplified Average 0 89 °F 75 °F 14 °F H 50 % -31 gr/Ib Sensible Cooling Equipment Load Sizing Structure Heating Cooling Area (ft2) 262�f 2624 Volume (ft) 19044 19044 Air changes/hour 0.41 0.21 Equiv. AVF (cfm) 130 67 Heating Equipment Summary Make Goodman Mfg. Equipment sensible load 9687 Trade GOODMAN cfm/Btuh Air flow factor Model GMH950703BX 0.70 in H2O AHRI ref 2002183 Space thermostat 89 °F 75 °F 14 °F H 50 % -31 gr/Ib Sensible Cooling Equipment Load Sizing Structure 9731 Btuh Ducts 0 Btuh Central vent (44 cfm) 575 Btuh Blower 0 Btuh Use manufacturer's data n 4765510 Rate/swing multiplier 0.94 cfm Equipment sensible load 9687 Btuh Latent Cooling Equipment Load Sizing Structure -1199 Btuh Ducts 0 Btuh Central vent (44 cfm) -799 Btuh Equipment latent load 0 Btuh Equipment total load 9687 Btuh Req. total capacity at 0.70 SHR 1.2 ton Heating input Cooling Equipment Summary Make Goodman Mfg. Trade GOODMAN, JANITROL, AMANA DISTI... Cond GSX130241C* Coil Capf303Obx AHRI ref 4765510 Efficiency 95 AFUE Efficiency Heating input 69000 Btuh Sensible cooling Heating output 52440 Btuh Latent cooling Temperature rise 67 °F Total cooling Actual air flow 850 cfm Actual air flow Air flow factor 0.024 cfm/Btuh Air flow factor Static pressure 0.70 in H2O Static pressure Space thermostat Load sensible heat ratio 11.0 EER, 13 SEER 16100 Btuh 6900 Btuh 23000 Btuh 850 cfm 0.087 cfm/Btuh 0.70 in H2O 1.00 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. '1 WI"1 iitSCift 2018 -May -1809:33:45 Right-Suite@Universal201717.0.10 RSU20477 Pagel ACCX tware\Roberts\FS5B7 princeton with basement.rup Calc = MJ8 House faces: SE - - wrightsoft AED Assessment Entire House Modern Plumbing, Heating, and Electric P.O. Box 627, Rigby, Id 83442 Phone: 208-745-7021 Fax: 208-745-7329 Email: highcountryph@yahoo.com For: Location: Idaho Falls, ID, US Elevation: 4741 ft Latitude: 44°N Outdoor: Dry bulb (°F) Dailyrange (°F) Wet bulb (°F) Wind speed (mph) Cody Puzey 3758 Yellowstones Hwy, Idaho Falls, Id 83401 Phone: 208-529-2116 Heating Cooling -6 89 - 34 ( H ) - 60 15.0 7.5 Job: FS5B7 Date: 5/17/18 By: Vince Byram Indoor: Heating Cooling Indoor temperature (°F) 70 75 Design TD (°F) 76 14 Relative humidity (%) 50 50 Moisture difference (gr/Ib) 61.5 -31.5 Infiltration: Hai M.y / Ag / AED limit Maximum hourly glazing load exceeds average by 22.1%. House has adequate exposure diversity (AED), based on AED limit of 30%. AED excursion: 0 Btuh W I'1 �lt[ltft 2018 -May -18 09:33:45 Right -Suite® Universal 2017 17.0.10 RSU20477 Page 1 ...tware\Roberts\FS5B7 princeton with basement.rup Calc = MJ8 House faces: SE wrightsoft Right -J® Worksheet Entire House Modern Plumbing, Heating, and Electric P.O. Box 627, Rigby, Id 83442 Phone: 208-745-7021 Fax: 208-745-7329 Email: highcountryph@yahoo.com Job: FS5B7 Date: 5/17118 By: Vince Byram 1 Room name Entire House Rooml 2 Exposed wall 400.0 It 101.0 ft 3 Room height 9.0 ft d 9.0 ft heat/cool 4 Room dimensions 1.0 x 604.0 ft 5 Room area 2624.0 ftz 604.0 ft' T Y Construction U -value Or HTM Area ft' () Load I Area ft' () Load number (Btuh/ft'-°F (Bt uh/f t') or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat I Cool Gross N/P/S Heat Cool Gross N/PIS Heat Cool 6 W 12F-Osw 0.065 ne 4.94 0.47 558 558 2757 265 180 180 889 85 W 15619-Owc-6 0.069 no 3.93 0.06 270 270 1060 16 0 0 0 0 12F-Osw 0.065 se 4.94 0.47 603 458 2260 217 216 170 840 81 61C 0.320 se 24.32 30.39 104 0 2529 3161 25 0 608 760 11 Lo metal 0.150 se 11.40 2.78 41 41 472 115 21 21 239 58 W 15819-Owc-6 0.069 se 3.93 0.06 333 333 1308 20 0 0 0 0 W 12F-0sw 0.065 sw 4.94 0.47 585 585 2890 278 297 297 1467 141 V� 15619-Owc-6 0.069 sw 3.75 0.04 270 238 892 10 0 0 0 0 G61C 0.320 sw 24.32 30.39 32 0 778 973 0 0 0 0 12F-0sw 0.065 nw 4.94 0.47 648 542 2676 257 216 160 789 76 61C 0.320 nw 24.32 23.91 106 0 2586 2542 56 0 1370 1347 W 15819-Owc-6 0.069 nw 3.93 0.06 333 333 1308 20 0 0 0 0 C 1613-50ad 0.020 1.52 0.84 45 45 68 38 0 0 0 0 C 168-50ad 0.020 1.52 0.84 1139 1139 1731 957 22 22 33 18 F 21A -24c 0.025 1.90 0.00 762 762 1448 0 0 0 0 0 F 21A -24c 0.025 1.90 0.00 43 43 82 0 43 43 82 0 F 21A -24c 0.025 1.90 0.00 379 379 720 0 0 0 0 0 6 c) AED excursion 10 -269 Envelope loss/gain 1 25565 8868 1 1 6317 2297 12 a) Infiltration 9140 862 2972 280 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13) 34706 9731 9289 2577 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 34706 9731 9289 2577 15 Duct loads 0% 0% 0 0 -0% 0% 0 0 Total room load I 34706 9731 9289 2577 Air required (cfm) I 8501 850 I I 228 2251 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed wrigh#soft Right -Suite@ Universal 2017 17.0.10 RSU20477 2018 -May -1809:33:45 ...tware\Roberts\FS5137 princeton with basement.rup Calc = MJ8 House faces: SE Page 1 wrightsoft- Right -M Worksheet Entire House Modern Plumbing, Heating, and Electric P.O. Box 627, Rigby, Id 83442 Phone: 208-745-7021 Fax: 208-745-7329 Email: highcountryph@yahoo.com Job: FS5B7 Date: 5/17/18 By: Vince Byram 1 Room name Room2 Room3 2 Exposed wall 24.0 ft 25.0 ft 3 Room height 9.0 ft heat/cool 9.0 ft heaUcool 4 Room dimensions 1.0 x 116.0 ft 10.0 x 15.0 ft 5 Room area 116.0 ft' 150.0 ft' Ty Construction U -value Or HTM Area (ft') I Load I Area (ft2) I Load number (Btuh/ft'-°F (Btuh/f t') or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 W 12F-Osw 0.065 ne 4.94 0.47 90 90 445 43 0 0 0 0 W 15619-0wc-6 0.069 ne 3.93 0.06 0 0 0 0 0 0 0 0 12F-0sw 0.065 se 4.94 0.47 63 43 210 20 0 0 0 0 61C 0.320 se 24.32 30.39 0 0 0 0 0 0 0 0 11 metal 0.150 se 11.40 2.78 20 20 233 57 0 0 0 0 W 15819-0wc-6 0.069 se 3.93 0.06 0 0 0 0 0 0 0 0 W 12F-Osw 0.065 sw 4.94 0.47 0 0 0 0 135 135 667 64 15819-0wc-6 0.069 sw 3.75 0.04 0 0 0 0 0 0 0 0 61C 0.320 sw 24.32 30.39 0 0 0 0 0 0 0 0 12F-Osw 0.065 nw 4.94 0.47 63 63 311 30 90 90 445 43 61C 0.320 nw 24.32 23.91 0 0 0 0 0 0 0 0 W 15B19-0wc-6 0.069 nw 3.93 0.06 0 0 0 0 0 0 0 0 C 16B-50ad 0.020 1.52 0.84 0 0 0 0 0 0 0 0 C 16B-50ad 0.020 1.52 0.84 0 0 0 0 150 150 228 126 F 21A -24c 0.025 1.90 0.00 0 0 0 0 0 0 0 0 F 21A -24c 0.025 1.90 0.00 0 0 0 0 0 0 0 0 F 21A -24c 0.025 1.90 0.00 0 0 0 0 0 0 0 0 61 c) AED excursion -28 1-39 Envelope loss/gain 1199 122 1 1 1339 194 12 a) Infiltration 706 67 736 69 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13) 1905 188 2075 264 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 1905 188 2075 264 15 Duct loads -0% 0% 0 0 -0% 0% 0 0 Total room load 1905 188 2075 264 Air required (cfm) I 47 16I I 51 23 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. w1"1gFti[JTt Rig ht -Su ite®2018-May-1809:33:45Universa1201717.0.10 RSU20477 Paget tware\Roberts\FS5B7 princeton with basement.rup Calc = MJ8 House faces: SE wrightso€t Right -M Worksheet Entire House Modern Plumbing, Heating, and Electric P.O. Box 627, Rigby, Id 83442 Phone: 208-745-7021 Fax: 208-745-7329 Email: highcounlryph@yahoo.com Job: FS5B7 Date: 5/17/18 By: Vince Byram 1 Room name Room4 Rooms 2 Exposed wall 31.0 ft 14.0 ft 3 Room height 9.0 ft heat/cool 9.0 ft heat/cool 4 Room dimensions 1.0 x 250.0 ft 1.0 x 242.0 ft 5 Room area 250.0 ft' 242.0 fN Ty Construction U -value Or HTM Area (ft') I Load Area (ft') Load number (Btuh/ftz.F (Btuh/ft') or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 W 12F-0sw 0.065 ne 4.94 0.47 0 0 0 0 0 0 0 0 W 15819-0wc-6 0.069 ne 3.93 0.06 0 0 0 0 0 0 0 0 VL12F-0sw 0.065 se 4.94 0.47 135 106 524 50 0 0 0 0 2 61C 0.320 se 24.32 30.39 29 0 705 881 0 0 0 0 11 metal 0.150 se 11.40 2.78 0 0 0 0 0 0 0 0 W 151319-0wc-6 0.069 se 3.93 0.06 0 0 0 0 0 0 0 0 W 12F-0sw 0.065 sw 4.94 0.47 144 144 711 68 0 0 0 0 15819-Owc-6 0.069 sw 3.75 0.04 0 0 0 0 0 0 0 0 61C 0.320 sw 24.32 30.39 0 0 0 0 0 0 0 0 12F-0sw 0.065 nw 4.94 0.47 0 0 0 0 126 101 499 48 61C 0.320 nw 24.32 23.91 0 0 0 0 25 0 608 598 W 15819-0wc-6 0.069 nw 3.93 0.06 0 0 0 0 0 0 0 0 C 16B-50ad 0.020 1.52 0.84 0 0 0 0 0 0 0 0 C 16B-50ad 0.020 1.52 0.84 250 250 380 210 242 242 368 203 F 21A -24c 0.025 1.90 0.00 0 0 0 0 0 0 0 0 F 21A -24c 0.025 1.90 0.00 0 0 0 0 0 0 0 0 F 21A -24c 0.025 1.90 0.00 0 0 0 0 60 60 114 0 61 c) AED excursion 1 -53 1 1 1 119 Envelope loss/gain 1 2320 1157 1 1 1589 968 12 a) Infiltration 912 86 412 39 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13) 3232 1243 2001 1007 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 3232 1243 2001 1007 15 Duct loads _0% 0% 0 0 _0% 0% 0 0 Total room load 3232 1243 2001 1007 Air required (cfm) I I 79 109 1 1 49I 88 Calculations approved by ACCA to meet all reauirements of Manual J 8th Ed � Right-Suite®2018-May-18 09:33:45Universa1201717.0.10 RSU20477 Page3 tware\Roberts\FS5B7 princeton with basement.rup Calc = MJ8 House faces: SE wrightsoft- Right -J® Worksheet Entire House Modern Plumbing, Heating, and Electric P.O. Box 627, Rigby, Id 83442 Phone: 208-745-7021 Fax: 208-745-7329 Email: highcountryph@yahoo.com Job: FS5B7 Date: 5/17/18 By: Vince Byram 1 Room name Room7 Room8 2 Exposed wall 5.0 ft 14.0 ft 3 Room height 9.0 ft heat/cool 9.0 ft heat/cool 4 Room dimensions 9.0 x 5.0 ft 11.0 x 14.0 ft 5 Room area 45.0 ft2 154.0 ft' Ty Construction U -value. I HTM I Area (ft') I Load Area (ft') Load number (Btuh/ft'-°F (Btuh/ft') or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 W 12F-0sw 0.065 ne 4.94 0.47 45 45 222 21 18 18 89 9 W 15819-0wc-6 0.069 ne 3.93 0.06 0 0 0 0 0 0 0 0 VL212F-0sw 0.065 se 4.94 0.47 0 0 0 0 99 74 366 35 61C 0.320 se 24.32 30.39 0 0 0 0 25 0 608 760 11 metal 0.150 se 11.40 2.78 0 0 0 0 0 0 0 0 W 15819-0wc-6 0.069 se 3.93 0.06 0 0 0 0 0 0 0 0 W 12F-Osw 0.065 sw 4.94 0.47 0 0 0 0 9 9 44 4 15B19-0wc-6 0.069 sw 3.75 0.04 0 0 0 0 0 0 0 0 61C 0.320 sw 24.32 30.39 0 0 0 0 0 0 0 0 12F-Osw 0.065 nw 4.94 0.47 0 0 0 0 0 0 0 0 61C 0.320 nw 24.32 23.91 0 0 0 0 0 0 0 0 W 15819-0wc-6 0.069 nw 3.93 0.06 0 0 0 0 0 0 0 0 C 16B-50ad 0.020 1.52 0.84 0 0 0 0 0 0 0 0 C 1613-50ad 0.020 1.52 0.84 45 45 68 38 154 154 234 129 F 21A -24c 0.025 1.90 0.00 0 0 0 0 0 0 0 0 F 21A -24c 0.025 - 1.90 0.00 0 0 0 0 0 0 0 0 F 21A -24c 0.025 1.90 0.00 45 45 85 0 154 154 293 0 61 c) AED excursion -g -27 Envelope loss/gain 376 50 1 1634 910 12 a) Infiltration 147 14 412 39 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13) 523 64 2046 949 Less external load 0 0 0 0 Less transfer 0 p 0 0 Redistribution 0 0 0 0 14 Subtotal 523 64 2046 949 15 Duct loads -0% 0% 0 0 -0% 0% 0 0 Total room load 523 641 2046 949 Air required (cfm) 1 13 6 1 50 83 Calculations approved by ACCA to meet all reouirements of Manual J 8th Ed W r iigFilksC�ft 2018 -May -18 09:33:45 Rig ht -Suite® Universal 2017 17.0.10 RSU20477 Page 4 ...tware\Roberts\FS5B7 princeton with basement.rup Calc = MJ8 House faces: SE wriightsoft Right -M Worksheet Entire House Modern Plumbing, Heating, and Electric P.O. Box 627, Rigby, Id 83442 Phone: 208-745-7021 Fax: 208-745-7329 Email: highcountryph@yahoo.com Job: FS5B7 Date: 5/17/18 By: Vince Byram 1 Room name Room9 Room6 2 Exposed wall 22.0 ft 25.0 ft 3 Room height 9.0 ft heat/cool 9.0 ft heat/cool 4 Room dimensions 10.0 x 12.0 ft 12.0 x 13.0 ft 5 Room area 120.0 ft2 156.0 ft' Ty Construction U -value OrI HTM Area (ft') Load I Area (ft') Load number (Bt uh/ft'-°F (Btuh/ft') or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 W 12F-0sw 0.065 ne 4.94 0.47 108 108 534 51 117 117 578 56 W 15B19-Owc-6 0.069 ne 3.93 0.06 0 0 0 0 0 0 0 0 VL212F-0sw 0.065 se 4.94 0.47 90 65 321 31 0 0 0 0 61C 0.320 se 24.32 30.39 25 0 608 760 0 0 0 0 11 metal 0.150 se 11.40 2.78 0 0 0 0 0 0 0 0 W 15B19-0wc-6 0.069 se 3.93 0.06 0 0 0 0 0 0 0 0 W 12F-Osw 0.065 sw 4.94 0.47 0 0 0 0 0 0 0 0 15819-0wc-6 0.069 sw 3.75 0.04 0 0 0 0 0 0 0 0 61C 0.320 sw 24.32 30.39 0 0 0 0 0 0 0 0 12F-Osw 0.065 nw 4.94 0.47 0 0 0 0 108 83 410 39 61C 0.320 nw 24.32 23.91 0 0 0 0 25 0 608 598 W 15B19-Owc-6 0.069 nw 3.93 0.06 0 0 0 0 0 0 0 0 C 16B-50ad 0.020 1.52 0.84 0 0 0 0 0 0 0 0 C 16B-50ad 0.020 1.52 0.84 120 120 182 101 156 156 237 131 F 21A -24c 0.025 1.90 0.00 0 0 0 0 0 0 0 0 F 21A -24c 0.025 1.90 0.00 0 0 0 0 0 0 0 0 F 21A -24c 0.025 1.90 0.00 120 120 228 0 0 0 0 0 6 c) AED excursion 1 -31 118 Envelope loss/gain 1873 912 1833 942 12 a) Infiltration 647 61 736 69 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13) 2520 973 2569 1011 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 2520 973 2569 1011 15 Duct loads _0% 0% 0 0 -0% 0% 0 0 1 room l Air 1 25601 985731 256691 10$$1 equi dal (c m) 1 1 1 1 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed w rightsoft 2018 -May -18 09:33:45 Rig ht -Su ite®Universal 2017 17.0.10 RSU20477 Page 5 tware\Roberts\FS5B7 princeton with basement.rup Calc = MJ8 House faces: SE wrightsoft` Right -J® Worksheet Entire House Modern Plumbing, Heating, and Electric P.O. Box 627, Rigby, Id 83442 Phone: 208-745-7021 Fax: 208-745-7329 Email: highcountryph@yahoo.com Job: FS5B7 Date: 5/17/18 By: Vince Byram 1 Room name Room10 Room 11 2 Exposed wall 75.0 ft 59.0 ft 3 Room height 9.0 ft heat/cool 9.0 ft heat/cool 4 Room dimensions 1.0 x 441.0 ft 1.0 x 321.0 ft 5 Room area 441.0 ft2 321.0 ft2 Ty Construction U -value Or HTM Area (ft') I Load Area (ft') Load number (Btuh/ft'-°F) tuh/ft') or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 W 12F-Osw 0.065 ne 4.94 0.47 0 0 0 0 0 0 0 0 W 15619-0wc-6 0.069 ne 3.93 0.06 144 144 565 9 126 126 495 8 12F-()sw 0.065 se 4.94 0.47 0 0 0 0 0 0 0 0 61C 0.320 se 24.32 30.39 0 0 0 0 0 0 0 0 11 metal 0.150 se 11.40 2.78 0 0 0 0 0 0 0 0 W 15B19-0wc-6 0.069 se 3.93 0.06 153 153 601 9 180 180 707 11 W 12F-Osw 0.065 sw 4.94 0.47 0 0 0 0 0 0 0 0 15619-0wc-6 0.069 sw 3.75 0.04 261 229 857 10 9 9 35 1 61C 0.320 sw 24.32 30.39 32 0 778 973 0 0 0 0 12F-0sw 0.065 nw 4.94 0.47 0 0 0 0 0 0 0 0 61C 0.320 nw 24.32 23.91 0 0 0 0 0 0 0 0 W 15B19-0wc-6 0.069 nw 3.93 0.06 117 117 459 7 216 216 848 13 C 168-50ad 0.020 1.52 0.84 45 45 68 38 0 0 0 0 C 16B-50ad 0.020 1.52 0.84 0 0 0 0 0 0 0 0 F 21A -24c 0.025 1.90 0.00 441 441 838 0 321 321 610 0 F 21A -24c 0.025 1.90 0.00 0 0 0 0 0 0 0 0 F 21A -24c 0.025 1.90 0.00 0 0 0 0 0 0 0 0 61 c) AED excursion 1 234 -11 Envelope loss/gain 4167 1279 1 1 2695 21 12 a) Infiltration 736 69 579 55 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13) 4903 1349 3274 75 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 4903 1349 3274 75 15 Duct loads -0% 0% 0 0 -0% 0% 0 0 Total room load 4903 13493274 75 Air required (cfm) I 120 118 I I 80 7 Calculations approved by RCCA to meet all requirements of Manual J 8th Ed 40- w right�iof 2018 -May -18 09:33:45 i Rig ht -Su ite®Universa1201717.0.10 RSU20477 Page tware\Roberts\FS5B7 princeton with basement.rup Calc = MJ8 House faces: SE - + wrightsoft Right -M Worksheet Entire House Modern Plumbing, Heating, and Electric P.O. Box 627, Rigby, Id 83442 Phone: 208-745-7021 Fax: 208-745-7329 Email: highcountryph@yahoo.com Job: FS5B7 Date: 5/17/18 By: Vince Byram 1 Room name Room13 2 Exposed wall 5.0 ft 3 Room height 9.0 ft heat/cool 4 Room dimensions 5.0 x 5.0 ft 5 Room area 25.0 ft2 Ty Construction U -value Or HTM Area (ft') I Load Area Load number (Btuh/ft'-°F (Btuh/ft') or perimeter (ft) (Btuh) or perimeter Heat Cool Gross [__N/'/S Heat Cool Gross N/P/S Heat Cool 6 W 12F-Osw 0.065 ne 4.94 0.47 0 0 0 0 W 151319-0wc-6 0.069 ne 3.93 0.06 0 0 0 0 12F-0sw 0.065 se 4.94 0.47 0 0 0 0 61C 0.320 se 24.32 30.39 0 0 0 0 11 D metal 0.150 se 11.40 2.78 0 0 0 0 W 15B19-0wc-6 0.069 se 3.93 0.06 0 0 0 0 W 12F-Osw 0.065 sw 4.94 0.47 0 0 0 0 V)/ 151319-0wc-6 0.069 sw 3.75 0.04 0 0 0 0 L -G 61C 0.320 sw 24.32 30.39 0 0 0 0 12F-Osw 0.065 nw 4.94 0.47 45 45 222 21 61C 0.320 nw 24.32 23.91 0 0 0 0 W 151319-0wc-6 0.069 nw 3.93 0.06 0 0 0 0 C 16B-50ad 0.020 1.52 0.84 0 0 0 0 C 16B-50ad 0.020 1.52 0.84 0 0 0 0 F 21A -24c 0.025 1.90 0.00 0 0 0 0 F 21A -24c 0.025 1.90 0.00 0 0 0 0 F 21A -24c 0.025 1.90 0.00 0 0 0 0 61 c) AED excursion -5 Envelope loss/gain 222 17 12 a) Infiltration 147 14 b) Room ventilation 0 0 13 Internal gains: Occupants @ 230 0 0 Appliances/other 0 Subtotal (lines 6 to 13) 369 31 Less external load p 0 Less transfer 0 0 Redistribution 0 0 14 Subtotal 369 31 15 Duct loads -0% 0% 0 0 Total room load) 36991 31 Air required cfm I Calculations approved by ACCA to meet all requirements of Manual J 8th Ed wri9llt�oft 2018 -May -18 09:33:45 �1h. Right-Suite®Universal 2017 17.0.10 RSU20477 Page 7 tware\Roberts\FS5B7 princeton with basement.rup Calc = MJ8 House faces: SE 011 Main Floor 3b'-0" 101 Job #: FS5B7 Performed by Vince Byram for: Cody Puzey 3758 Yellowstones Hwy Idaho Falls, Id 83401 Phone: 208-529-2116 Modern Plumbing, Heating, and Ele P.O, Box 627 Rigby, Id 83442 Phone: 208-745-7021 Fax: 208-745-7329 highcountryph@yahoo.com Riser Riser Scale: 1 :85 Page 2 Right -Suite ®U ni versa 12017 17.0.10 RSU20477 2018 -May -18 09:34:16 ...S587 princeton with basement.rup tea, Duct System Summary Job: rs5B7 V1ii1C�l '�Q14 Date: 5117118 Entire House By: Vince Byram Modern Plumbing, Heating, and Electric P.O. Bax 627, Rigby, Id 83442 Phone: 208-745-7021 Fax: 208-745-7329 Email: highcountryph@yahoo.com For: Cody Puzey 3758 Yellowstones Hwy, Idaho Falls, Id 83401 Phone: 208-529-2116 External static pressure Pressure losses Available static pressure Supply / return available pressure Lowest friction rate Actual air flow Total effective length (TEL) Heating 0.70 in H2O 0.29 in H2O 0.41 in H2O 0.220 / 0.190 in H2O 0.070 in/100ft 850 cfm 585 ft Cooling 0.70 in H2O 0.29 in H2O 0.41 in H2O 0.220 / 0.190 in H2O 0.070 in/100ft 850 cfm Supply Branch Detail Table Name Design (Btuh) Htg (cfm) Clg (cfm) Design FR Diam (in) H x W (in) Duct Matl Actual Ln (ft) Ftg.Egv Ln (ft) Trunk Room1 h 2322 57 56 0.078 6.0 OX 0 ShMt 37.0 245.0 st1 B Rooms -A h 2322 57 56 0.133 6.0 Ox 0 ShMt 25.0 140.0 st1 Room1-B h 2322 57 56 0.070 6.0 Ox 0 ShMt 49.0 265.0 st1 B Room1-C h 2322 57 56 0.101 6.0 Oxo ShMt 38.0 180.0 st1A Room10 h 2451 60 59 0.096 6.0 Oxo ShMt 58.4 170.0 st2 Room10-A h 2451 60 59 0.099 6.0 Oxo ShMt 51.4 170.0 st2 Room11 h 3274 80 7 0.102 6.0 Ox 0 ShMt 35.4 180.0 st2 Room13 h 369 9 3 0.116 6.0 0x0 ShMt 14.0 175.0 SO Room2 h 953 23 8 0.120 6.0 Ox 0 ShMt 8.0 175.0 SO Room2-B h 953 23 8 0.128 6.0 OX 0 ShMt 12.0 160.0 st1 Room3 h 2075 51 23 0.088 6.0 0x0 ShMt 36.0 215.0 st1A Room4 C 622 40 54 0.100 6.0 Oxo ShMt 40.9 180.0 st1A Room4-A c 622 40 54 0.081 6.0 Ox 0 ShMt 46.0 225.0 st1 A Rooms c 1007 49 88 0.142 6.0 Oxo ShMt 25.0 130.0 SO Room6 c 1011 63 88 0.118 6.0 Ox 0 ShMt 12.0 175.0 st1 Room7 h 523 13 6 0.118 6.0 Oxo ShMt 11.0 175.0 st1 Room& c 949 50 83 0.120 6.0 0x0 ShMt 33.0 150.0 SO Room9 c 973 62 85 0.116 6.0 OX 0 ShMt 25.0 165.0 SO wr-i h,tsoft2018-May-18 09:33:46 Rig ht -Su ite®Universal 2017 17.0. 10 RSU20477 -ACCIN ...tware\RobertsTS5B7 princeton with basement.rup Calc = MJ8 House faces: SE Page 1 Supply Trunk Detail Table Name Trunk Htg Clg Design Veloc Diam H x W Duct Stud/Joist Opening (in) Name Type (cfm) (cfm) FR (fpm) (in) (in) Material Trunk st1A Peak AVF 301 300 0.070 451 9.4 8 x 12 ShtMetl st1 st2 Peak AVF 200 124 0.096 574 8.0 0 x 0 ShtMetl 85 st1 B Peak AVF 114 113 0.070 256 6.6 8 x 8 ShtMetl st1 A st1 Peak AVF 650 726 0.070 653 13.1 8 x 20 ShtMetl rt2 Name Grille Size (in) Htg (cfm) Clg (cfm) TEL (ft) Design FR VelocDiam (fpm) (in) H x W (in) Stud/Joist Opening (in) Duct Matl Trunk rb7 Ox 0 200 124 135.0 0.141 634 7.0 3.25x14 10x9 SJSp 726 rb2 Ox 0 63 88 96.1 0.198 280 4.8 3.25x14 10x9 SJSp rt2 rb3 Ox 0 62 85 92.1 0.206 269 4.7 3.25x14 10x9 SJSp rt2 rb4 Ox 0 50 83 99.1 0.192 262 4.8 3.25x14 10x9 SJSp rt2 rb6 Ox 0 62 94 114.1 0.166 296 5.1 3.25x14 10x9 SJSp rt2 rb1 Ox 0 283 244 177.1 0.107 448 8.5 2-3.25x14 2-10x18 SJSp rt2 rb5 Ox 0 130 132 271.1 0.070 417 6.9 3.25x14 10x9 SJSp 02A ,t7 e:,-- � VNilght5c°,ii Right -Suited Universal 2017 17 2018 -May -18 09:33:46.0.10 RSU20477 Page 2 JCCk ...tware\Roberts\FS5B7 princeton with basement.rup Calc = MJ8 House faces: SE Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm) (cfm) FR (fpm) (in) (in) Material Trunk rt2 Peak AVF 650 726 0.070 653 13.1 8 x 20 ShtMetl rt2A Peak AVF 130 132 0.070 197 6.9 8 x 12 ShtMetl rt2 ,t7 e:,-- � VNilght5c°,ii Right -Suited Universal 2017 17 2018 -May -18 09:33:46.0.10 RSU20477 Page 2 JCCk ...tware\Roberts\FS5B7 princeton with basement.rup Calc = MJ8 House faces: SE