HomeMy WebLinkAboutRESCHECK - 18-00169 - 320 Baldwin Dr - SFRREScheck Software Version 4.6.2
Compliance Certificate
Project F56B5 - Logan
Energy Code:
2015 IECC
Location:
Rexburg, Idaho
Construction Type:
Single-family
Project Type:
New Construction
Orientation:
Bldg. faces 45 deg. from North
Conditioned Floor Area:
3,530 ft2
Glazing Area
19%
Climate Zone:
6 (8693 HDD)
Permit Date:
Permit Number:
6
Construction Site:
Owner/Agent:
1130 John hancook
0.056
founder's square subd.
488
Rexburg, ID 83440
0.0
/&-00161
Designer/Contractor:
Kartchner Homes
John@kartchnerhomes.com
'Compliance: Passes using UA trade-off;
Compliance: 1.4% Better Than Code Maximum UA: 284 Your UA: 280
The % Better or Worse Than Code Index reflects how close to compliance the house is based on code trade-off rules.
It DOES NOT provide an estimate of energy use or cost relative to a minimum -code home.
Envelope Assemblies
Ceiling 1: Flat Ceiling or Scissor Truss
Main Level - Front: Wood Frame, 16" o.c.
Orientation: Front
Window 1: Vinyl/Fiberglass Frame:Double Pane with Low -E
Orientation: Front
Door 1: Solid
Orientation: Front
Main Level - Right: Wood Frame, 16" o.c.
Orientation: Right side
Main Level - Rear: Wood Frame, 16" o.c.
Orientation: Back
Window 1: Vinyl/Fiberglass Frame:Double Pane with Low -E
Orientation: Back
Main Level - Right: Wood Frame, 16" o.c.
Orientation: Left side
Basement Wall 1: Solid Concrete or Masonry
Orientation: Front
Wall height: 8.0'
Depth below grade: 8.0'
Insulation depth: 8.0'
Window 4: Vinyl/Fiberglass Frame:Double Pane with Low -E
Orientation: Front
1,765
50.0
0.0
0.026
4b
608
22.0
0.0
0.056
27
90
0.320
29
40
0.150
6
175
22.0
0.0
0.056
10
488
22.0
0.0
0.056
22
99
0.320
32
278
22.0
0.0
0.056
16
608
0.0
15.0
0.042
25
20 0.320 6
Project Title: FS6B5 - Logan Report date: 03/27/18
Data filename: C:\Users\jhoel lei n. MAI N\Documents\REScheck\Test\FS6b5 - jamestown.rck Page 1 of 10
Basement Wall 2: Solid Concrete or Masonry 175 0.0 15.0 0.042 7
Orientation: Right side
Wall height: 8.0'
Depth below grade: 8.0'
Insulation depth: 8.0'
Basement Wall 3: Solid Concrete or Masonry 488 0.0 15.0 0.042 18
Orientation: Back
Wall height: 8.0'
Depth below grade: 8.0'
Insulation depth: 8.0'
Window 5: Vinyl/Fiberglass Frame:Double Pane with Low -E 60 0.320 19
Orientation: Back
Basement Wall 4: Solid Concrete or Masonry 278 0.0 15.0 0.042 11
Orientation: Left side
Wall height: 8.0'
Depth below grade: 8.0'
Insulation depth: 8.0'
Window 6: Vinyl/Fiberglass Frame:Double Pane with Low -E 20 0.320 6
Orientation: Left side
Compliance Statement: The proposed building design described here is consistent with the building plans, specifications, and other
calculations submitted with the permit application. The proposed building has been designed to meet the 2015 IECC requirements in
REScheck Version 4.6.2 and to comply with the mandatory requirements listed in the REScheck Inspection Checklist.
Name - Title Signature Date
Project Title: FS665 - Logan Report date: 03/27/18
Data filename: C:\Users\jhoellein.MAIN\Documents\REScheck\Test\FS6b5-jamestown.rck Page 2 of 10
REScheck Software Version 4.6.2
CY(i Inspection Checklist
Energy Code: 2015 IECC
Requirements: 0.0% were addressed directly in the REScheck software
Text in the "Comments/Assumptions" column is provided by the user in the REScheck Requirements screen. For each
requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception
is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided.
Section
#
Pre-Inspection/Plan Review
Plans Verified
Field Verified
Value
Complies?
Comments/Assumptions
Value
& Req ID
❑Complies
103.1,
;Construction drawings and
❑Does Not
103.2
documentation demonstrate
[PR1]1
energy code compliance for the
❑Not Observable
'building envelope. Thermal
❑Not Applicable
:envelope represented on
construction documents.
103.1,
lConstruction drawings and
❑Complies
❑Does Not
103.2,
documentation demonstrate
403.7
;energy code compliance for
❑Not Observable
[PR3]1
;lighting and mechanical systems.
❑Not Applicable
Systems serving multiple
-
dwelling units must demonstrate
compliance with the IECC
'Commercial Provisions.
302.1,
,Heating and cooling equipment is
Heating: Heating:
❑Complies
403.7
`sized per ACCA Manual S based
Btu/hr Btu/hr
❑Does Not
[PR2]2
on loads calculated per ACCA
Cooling: Cooling:
❑Not Observable
-
Manual J or other methods
Btu/hr Btu/hr
Applicable
approved by the code official.❑Not
Additional Comments/Assumptions:
111 High Impact (Tier 1) 2 Medium Impact (Tier 2) 1 3 1 Low Impact (Tier 3)
Project Title: FS665 - Logan Report date: 03/27/18
Data filename: C:\Users\jhoellein.MAIN\Documents\REScheck\Test\FS6b5 - jamestown.rck Page 3 of 10
Section
#
Plans Verified
Foundation Inspection
Field Verified F Complies? Comments/Assumptions
Value
Value
& Req.ID
402.1.1
Conditioned basement wall R-
R- ❑Complies ;See the Envelope Assemblies
table for values.
[F04]1
insulation R -value. Where interior R-
R - ❑Does Not
;insulation is used, verification
❑Not Observable
-
may need to occur during
❑Not Applicable
Insulation Inspection. Not
required in warm -humid locations:
in Climate Zone 3.
303.2
;Conditioned basement wall
❑Complies
[F05]1
'insulation installed per
❑Does Not
:manufacturer's instructions.
❑Not Observable '.
❑Not Applicable
402.2.9
;Conditioned basement wall ft
ft ❑Complies See the Envelope Assemblies
❑Does table for values.
[F06]1
insulation depth of burial or
Not
distance from top of wall.
❑Not Observable
❑Not Applicable
303.2.1
'A protective covering is installed
❑Complies
[FO11]2
to protect exposed exterior
❑Does Not
insulation and extends a
❑Not Observable
-
:minimum of 6 in. below grade.
❑Not Applicable
403.9
'Snow- and ice -melting system
❑Complies
[FO12]2
:controls installed.
❑Does Not
❑Not Observable
❑Not Applicable
Additional Comments/Assumptions:
111 High Impact (Tier 1) 2 1 Medium Impact (Tier 2) 3 1 Low Impact (Tier 3)
Project Title: FS6B5 - Logan Report date: 03/27/18
Data filename: C:\Users\jhoellein.MAIN\Documents\REScheck\Test\FS6b5 - jamestown.rck Page 4 of 10
Section
Plans Verified
Field Verified Complies? Comments/Assumptions
#
Framing / Rough-In Inspection Value
Value
& Req.ID
U ❑Complies See the Envelope Assemblies
402.1.1,
Door U-factor. U-
❑Does Not table for values.
402.3.4
[FRI]1
❑Not Observable `
❑Not Applicable
402.1.1,
Glazing U factor (area weighted U-
U- ❑Complies `.See the Envelope Assemblies
;table for values.
❑Does Not
4 02.3.1,
average).
402.3.3,
❑Not Observable
402.3.6,❑Not
Applicable
402.5
[FR2]1
3013.1.3
U-factors of fenestration products
❑Complies
❑Does Not;
[FR4]1
pare determined in accordance
;with the NFRC test procedure or
[]Not Observable
taken from the default table.
❑Not Applicable
402.4.1.1 ;Air barrier and thermal barrier
❑Complies
❑Does Not
[FR23]1
installed per manufacturer's
instructions.
❑Not Observable
_
❑Not Applicable
402.4.3
Fenestration that is not site built
❑Complies
❑Does Not
[FR20]1
' is listed and labeled as meeting
iAAMA /WDMA/CSA 101/l.S.2/A440
❑Not Observable `
-
;or has infiltration rates per NFRC
❑Not Applicable E
400 that do not exceed code
t
limits.
402.4.5
IC-rated recessed lighting fixtures.
❑Complies
❑Does Not
[FR16]2
'sealed at housing/interior finish
,and labeled to indicate :52.0 cfm
❑Not Observable
leakage at 75 Pa.
❑Not Applicable
403.2.1
;Supply and return ducts in attics
'insulated
❑Complies
❑Does Not
[FR12]1
>= R-8 where duct is
>= 3 inches in diameter and >_
❑Not Observable
=
R-6 where < 3 inches. Supply and
❑Not Applicable
3return ducts in other portions of
.the building insulated >= R-6 for !
E
;diameter >= 3 inches and R-4.2
'for < 3 inches in diameter.
403.3.3.5 ;Building cavities are not used as
❑Complies
[FR15]3
ducts or plenums.
❑Does Not
❑Not Observable
-
❑Not Applicable
403.4
HVAC piping conveying fluids R-
'above
R-❑Complies i
Not
[FR17]2
105 °F or chilled fluids❑Does
below 55 °F are insulated to >_R
❑Not Observable `
3
❑Not Applicable
403.4.1
!Protection of insulation on HVAC
❑Complies i
❑Does Not
[FR24]1
:piping.
❑Not Observable ;
❑Not Applicable
403.5.3
i Hot water pipes are insulated to R-
R- ❑Complies E
❑Does Not ;
[FR18]2:>_R-3.
❑Not Observable
❑Not Applicable-
pplicable403.6
403.6
Automatic or gravity dampers are:
❑Complies
❑Does Not
[FR19]2
'installed on all outdoor air
!intakes and exhausts.
❑Not Observable
❑Not Applicable
11 High Impact (Tier 1) 2 Medium Impact (Tier 2) 3 Low Impact (Tier 3)
Project Title: FS665 - Logan Report date: 03/27/18
Data filename: C:\Users\jhoellein.MAIN\Documents\REScheck\Test\FS6b5 - jamestown.rck Page 5 of 10
Additional Comments/Assumptions:
1 JHigh Impact (Tier 1) 12 1 Medium Impact (Tier 2) 1 3 1 Low Impact (Tier 3)
Project Title: FS6135 - Logan Report date: 03/27/18
Data filename: C:\Users\jhoellein.MAIN\Documents\REScheck\Test\FS6b5-jamestown.rck Page 6 of 10
Additional Comments/Assumptions:
1 High Impact (Tier 1) 2 1 Medium Impact (Tier 2) 3 1 Low Impact (Tier 3)
Project Title: FS6135 - Logan Report date: 03/27/18
Data filename: C:\Users\jhoeIlein.MAIN\Documents\REScheck\Test\FS6b5 - jamestown.rck Page 7 of 10
Inspection
Plans Verified
Field Verified
-T
Complies?
-
Comments/Assumptions
Section
#
Insulation
Value
Value
& Req.ID
303.1
`All installed insulation is labeled
❑Complies
❑Does Not
[IN13]2
=or the installed R -values
;provided.
❑Not Observable
-
[]Not Applicable
402.1.1,
i Wall insulation R -value. If this is a
! R-
R
`❑Complies see the Envelope Assemblies
❑Does Not 'table for values.
402.2.5,
mass wall with at least 1/2 of the
F-1Wood
1771Wood
402.2.6
wall insulation on the wall
❑Mass
E]Mass
[]Not Observable
[I1\13]1
exterior, the exterior insulation
❑ Steel
❑ Steel
❑Not Applicable
requirement applies (FR10).
303.2
;Wall insulation is installed per
❑Complies
❑Does Not
[IN4]1
:manufacturer's instructions.
❑Not Observable
❑Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1) 2 1 Medium Impact (Tier 2) 3 1 Low Impact (Tier 3)
Project Title: FS6135 - Logan Report date: 03/27/18
Data filename: C:\Users\jhoeIlein.MAIN\Documents\REScheck\Test\FS6b5 - jamestown.rck Page 7 of 10
Section
#
Final Inspection Provisions
Plans Verified
Value
Field Verified
Value
Complies?
Comments/Assumptions
& Req.ID
402.1.1,
Ceiling insulation R -value.
R- R-
❑Complies :See the Envelope Assemblies
402.2.1,
F-1Wood F1 wood
❑Does Not Mable for values.
402.2.2,
❑ Steel ❑ Steel
EJ Observable
402.2.6
Applicable
[FI1]1❑Not
303.1.1.1, ;Ceiling insulation installed per
❑Complies
303.2
manufacturer's instructions.
❑Does Not
[FI2]1
Blown insulation marked every
Observable
300 ftp.❑Not
❑Not Applicable
402.2.3
'Vented attics with air permeable
❑Complies
[F122]2
insulation include baffle adjacent
❑Does Not
to soffit and eave vents that
[:]Not Observable
,extends over insulation.
❑Not Applicable
402.2.4
;Attic access hatch and door
R- R-
❑Complies
[F13]1
insulation >_R -value of the
❑Does Not
;adjacent assembly.
❑Not Observable
❑Not Applicable
402.4.1.2
' Blower door test @ 50 Pa. <=5
ACH 50 = ACH 50 =
❑Complies
IF11711
each in Climate Zones 1-2, and
❑Does Not
<<=3 ach in Climate Zones 3-8.
❑Not Observable `
❑Not Applicable
403.2.3
Duct tightness test result of <=4
cfm/100 cfm/100
❑Complies
[F14]1
cfm/100 ft2 across the system or
ft2 ft2
❑Does Not E
z<=3 cfm/100 ft2 without air
[]Not Observable
handler @ 25 Pa. For rough -in
❑Not Applicable
'tests, verification may need to
,occur during Framing Inspection.
403.3.2
Ducts are pressure tested to
cfm/100 cfm/100
❑Complies
[FI27]1
'determine air leakage with
ft2 ft2
❑Does Not
,either: Rough -in test: Total
❑Not Observable
;leakage measured with a
❑Not Applicable
pressure differential of 0.1 inch
w.g. across the system including
;the manufacturer's air handler
enclosure if installed at time of
;test. Postconstruction test: Total
,leakage measured with a
pressure differential of 0.1 inch
;w.g. across the entire system
including the manufacturer's air
handler enclosure.
403.3.2.1
;Air handler leakage designated
❑Complies
[F124]1
by manufacturer at <=2% of
❑Does Not
:design airflow.
❑Not Observable
❑Not Applicable
403.1.1
';Programmable thermostats
❑Complies
[Flg]2
installed for control of primary
❑Does Not
;heating and cooling systems and
❑Not Observable
initially set by manufacturer to
E
❑Not Applicable
code specifications.
403.1.2
;Heat pump thermostat installed
❑Complies
[FI10]2
'on heat pumps.
❑Does Not
❑Not Observable
❑Not Applicable
403.5.1
'Circulating service hot water
❑Complies
[Fl 1112
systems have automatic or
❑Does Not
,accessible manual controls.
❑Not Observable
❑Not Applicable
111 High Impact (Tier 1) 12 1 Medium Impact (Tier 2) 13 1 Low Impact (Tier 3)
Project Title: FS6135 - Logan Report date: 03/27/18
Data filename: C:\Users\jhoeIlei n. MAI N\Documents\REScheck\Test\FS6b5 -jamestown.rck Page 8 of 10
111 High Impact (Tier 1) 2 Medium Impact (Tier 2) 3 Low Impact (Tier 3)
Project Title: FS6135 - Logan Report date: 03/27/18
Data filename: C:\Users\jhoeIlein.MAIN\Documents\REScheck\Test\FS6b5-jamestown.rck Page 9 of 10
Plans Verified
Provisions
Field Verified
Complies?
Comments/Assumptions
Section
#
Final Inspection Value
Value
& Req.ID
❑Complies
403.6.1
'All mechanical ventilation system
❑Does Not
[F125]2
fans not part of tested and listed
HVAC equipment meet efficacy
[]Not Observable
and air flow limits.
❑Not Applicable
403.2
Hot water boilers supplying heat
❑Complies
❑Does Not
[F126]2
Ahrough one- or two -pipe heating
,systems have outdoor setback
❑Not Observable
'control to lower boiler water
❑Not Applicable
;temperature based on outdoor
temperature.
❑Complies
403.5.1.1
'.Heated water circulation systems
❑Does Not
[F128]2
have a circulation pump. The
;system return pipe is a dedicated
❑Not Observable ,
return pipe or a cold water supply
❑Not Applicable
pipe. Gravity and thermos -
;syphon circulation systems are
;not present. Controls for
circulating hot water system
;pumps start the pump with signal
;for hot water demand within the
;occupancy. Controls
automatically turn off the pump
',when water is in circulation loop
is at set -point temperature and
no demand for hot water exists.
403.5.1.2 ;Electric heat trace systems
❑Complies
❑Does Not
[F129]2
'comply with IEEE 515.1 or UL
;515. Controls automatically
❑Not Observable
:adjust the energy input to the
❑Not Applicable
-heat tracing to maintain the
desired water temperature in the
piping.
403.5.2
Water distribution systems that
❑Complies
❑Does Not
[F130]2
have recirculation pumps that
pump water from a heated water
❑Not Observable
supply pipe back to the heated
❑Not Applicable
water source through a cold
=water supply pipe have a
,demand recirculation water
system. Pumps have controls
that manage operation of the
pump and limit the temperature
of the water entering the cold
water piping to 1049F.
403.5.4
Drain water heat recovery units
❑Complies
❑Does Not
[FI31]2
tested in accordance with CSA
1355.1. Potable water -side
❑Not Observable
,,pressure loss of drain water heat
❑Not Applicable
;recovery units < 3 psi for
individual units connected to one
!or two showers. Potable water-
side pressure loss of drain water ,
?heat recovery units < 2 psi for
individual units connected to
:three or more showers.
404.1
;75% of lamps in permanent
❑Complies
[]Does Not
[FI6]1
fixtures or 75% of permanent
fixtures have high efficacy lamps.
[]Not Observable
,Does not apply to low -voltage
❑Not Applicable
lighting.
404.1.1
Fuel gas lighting systems have
❑Complies
❑Does Not
[FI23]3
no continuous pilot light.
❑Not Observable
❑Not Applicable
111 High Impact (Tier 1) 2 Medium Impact (Tier 2) 3 Low Impact (Tier 3)
Project Title: FS6135 - Logan Report date: 03/27/18
Data filename: C:\Users\jhoeIlein.MAIN\Documents\REScheck\Test\FS6b5-jamestown.rck Page 9 of 10
Section
#
& Req ID
Final Inspection Provisions
Plans Verified
Value
Field Verified
Value
Complies?
Comments/Assumptions
401.3
;Compliance certificate posted.
❑Complies
[F17 ]2
❑Does Not
❑Not Observable
❑Not Applicable
303.3
Manufacturer manuals for
❑Complies
[F118 ]3
,mechanical and water heating
❑Does Not
;systems have been provided.
[]Not Observable F
❑Not Applicable
Additional Comments/Assumptions:
111 High Impact (Tier 1) 2 1 Medium Impact (Tier 2) 3 1 Low Impact (Tier 3)
Project Title: F56135 - Logan Report date: 03/27/18
Data filename: C:\Users\jhoellein.MAIN\Documents\REScheck\Test\FS6b5 -jamestown.rck Page 10 of 10
2015 IECC Energy
Efficiency Certificate
Above -Grade Wall 22.00
Below -Grade Wall 15.00
Floor 0.00
Ceiling / Roof 50.00
Ductwork (unconditioned spaces):
Window 0.32
Door 0.15
Heating System:
Cooling System:
Water Heater:
Name: Date:
Comments