Current Building Review Status: REVISIONS
Application Number: 18-00187Permit Details
Application Received Date: 04/11/2018
Commercial Remodel
Application Approved Date:
Application Approved Status: ACPTW/COND
04/12/2018
819 S Yellowstone Hwy
Taylor Chevrolet - Remodel
Status of Plan Reviews Completed
04/17/2018Building Review REVISIONS
Permit Review Status
Plan Reviews Still in Progress
Electrical Review
Plumbing Review
HVAC Review
DESCRIPTION COMMENTS STA TUS
*Please respond to "REVISIONS" status items, with appropriate comment/documentation as needed!
Mixed use occupancies meet the requirements of
IBC Section 508
REVISIONSBased on size of building it should have rated
separation between B & S1 occupancy and the
S-2 occupancy.
* As an existing building the actual separation
and rating is not identified on plans. Removing
the door between the service center and the
main section of the building without replacing it,
eliminates the existing separation and creates a
higher hazard. This door will need to remain or
have a properly rated door if being replaced.
Existing separation from the S-2 occupancy
needs to remain as is or meet required fire
rating if altered.
*Revisions Response :
Handrails and Guards meet the requirements of
IBC Sections 1014 and 1015
REVISIONSRequired guards shall be 42" minimum above
the walking surface and the front edge of stair
treads
*Revisions Response :
Service Facilities comply with IBC 1109.12 REVISIONSService counters shall be no more than 36"
above floor for a length of 36" (parallel
approach) or 30" (forward approach).
*Revisions Response :
Reviewed By: Quinton Owens
Review Date: 04/17/2018
Plan Review Details
quinton.owens@rexburg.org
Building Review Status: REVISIONS
Page 1 of 2
Approval of plans does not constitute approval of variance from code
All guards have been changed to 42"
All applicable counters have been lowered to 36" for the parallel approach
The door between the main section and the service center will remain
Building Review (Continued)
D ESCRIPTIO N CO MMEN TS STATUS
Fire resistance rating of building elements meet
Sect. 704 & Table 601
Existing V-B construction? Normally, storage on
second floor requires V-A construction if
designated as S-1. Owners should make the
effort to store only low hazard, non-combustible
materials (S-2) on the second story as much as
possible if not doing so already.
COMPLETED
Concealed spaces are fireblocked/draftstopped
per Section 718
Fire blocking shall be installed per section 718
and approved based on inspection.
COMPLETED
Stairways meet the requirements of IBC Section
1011 & 1019
Riser height noted as 6-1/2" +/- (shall be no
greater than 7")
COMPLETED
Exterior Exit Stairs & Ramps comply with IBC
Section 1027
Swing doors at car ramp are not allowed for
pedestrian traffic. Due to lack of landings at
doors and unidentified slope, the car ramp is
limited to operation of doors for vehicle use
only.
COMPLETED
Special Inspections are required as per IBC
Chapter 17
Special inspections required on structural steel
(see structural general notes)
COMPLETED
Page 2 of 2
Approval of plans does not constitute approval of variance from code