City of Rexburg: Building Review
Sweetwater Housing, #1-4
Permit Number. 14-00435
Items Addressed
1. Exterior walls will have One Hour Stucco fire rating on walls that are closer than 10',
with hardy backer over the sheeting, a cement coat, 1" foam over the cement, and the
brown coat. They will also have 5/8's sheetrock inside.
2. All interior walls will be 5/8's type sheetrock, with hat channel on the ceiling on the
main floor to stop heat transfer. Second floor will be insulated with blown cellulose to
meet the one hour fire rating between floors. Second floor ceiling will be double layerd
5/8's type sheetrock, and a one hour fire rated draft stop will be installed between the
units in the attic.
3. Heating will be PTAC type heaters, so there will be no duct work.
4. Insulation R values: See attached res check from Advanced Insulation.
5. Phoenix Fire Procetion will install a fire sprinkler system to meet the required NPFA
13R.
6. Rated Wall?
7. Ground floor dwelling Type B, ICC Al 17.1
8. Energy Compliance Report: See Attached res -check