HomeMy WebLinkAboutREVIEW REPORT 2/27/2018 - 18-00093 - Navex Global - Tenant FinishReview
Report
Current Building Review Status: REVISIONS
Application Number: 18-00093Permit Details
Application Received Date: 02/15/2018
Commercial Tenant Finish
Application Approved Date:
Application Approved Status: ACPTW/COND
02/15/2018
155 W 2nd S
Navex Global
Status of Plan Reviews Completed
02/16/2018Electrical Review COMPLETED
02/26/2018Plumbing Review COMPLETED
02/26/2018HVAC Review COMPLETED
02/27/2018Building Review REVISIONS
03/14/2018Fire Alarm Review COMPLETED
Permit Review Status
Plan Reviews Still in Progress
Building Review
DESCRIPTION COMMENTS STA TUS
*Please respond to "REVISIONS" status items, with appropriate comment/documentation as needed!
Exterior wall openings meet the requirements of
IBC Section 705.8
REVISIONSExhaust vents penetrate through fire wall and
open into parking garage.
*Revisions Response :
Exit and Exit Access Doorways meet the
requirements of IBC Section 1007
REVISIONS* Revision: Add exit sign in Open Office 215 at
south door going into Call Center 222
* Note: During construction, be sure exit sign
from Open Office 215 to elevator lobby is
readily visible upon exiting from Call Center into
Open Office.
*Revisions Response :
Special Inspection Contractor is identified (IBC
1704.2.1)
REVISIONSPlease identify agency to be performing special
inspection.
*Revisions Response :
Dwelling Unit Sound Transmission comply with
IBC Section 1207
Be sure floor/ceiling separation to dwelling units
above provides STC and IIC rating of 50 for
sound transmission.
COMPLETED
Special Inspections are required as per IBC
Chapter 17
Steel decking for floor opening infill.COMPLETED
Reviewed By: Quinton Owens
Review Date: 02/27/2018
Plan Review Details
quinton.owens@rexburg.org
Building Review Status: REVISIONS
Page 1 of 2
Approval of plans does not constitue approval of variance from code
Building Review (Continued)
D ESCRIPTIO N CO MMEN TS STATUS
Penetrations comply with IBC Section 714 for
rated assemblies
Penetrations shall maintain fire protection at fire
rated assemblies. Approval will be based on
inspections.
COMPLETED
Concealed spaces are fireblocked/draftstopped
per Section 718
Fire blocking will be approved based on
inspections per 718
COMPLETED
Additional Inspector Comments:
Drawings are NOT TO SCALE (printed to fit on smaller paper)
Page 2 of 2
Approval of plans does not constitue approval of variance from code